PFR-X+ 12R, Power Factor Regulator (Beluk BLR-CX 12RL), 12 Step, 110-480V 50/60HZ
Single CT Sensing
Isolated Switching of Power Factor Correction Contactors
Cos ϕ Setting 0.85 to 0.95 CAP
Auto CT Secondary Selection
Backlit LCD Display
Various Program Combinations
IP41
Up to 12 steps
Measurement System - Automatic/Manual
230VAC Aux Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
Specification
Electronicon Part Number
PFR-X+ 12R
Function
Reactive Power Correction
Nominal Voltage (Un)
110-480VAC Line to Line
Supply Voltage
90-300VAC (L-N), 15VA 45-65Hz
Relay Rating
250VAC/10Amp
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature Alarm
1 x Relay as above
Re-connection Delay Time
50 - 1200s User Adjustable
Desired Power Factor
0.80 IND - 0.80 CAP
Number of Output Relays
12
Smallest Capacitor Current
10mA
CT Input Range
15mA - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
N/A
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP50 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
User Manual
Modbus RS485 User Manual
Iskra Quick Setup Guide
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)
Iskra Doo PFC-CX-06R Power Factor Regulator, Controller (Beluk BLR-CX 06R) or Vishay Estamat PFC-6N), 6 Step, 110-480V 50/60HZ, See Rebadged PFR-X+ 06R
Single CT Sensing
Isolated Switching of Power Factor Correction Contactors
Cos ϕ Setting 0.85 to 0.95 CAP
Auto CT Secondary Selection
Backlit LCD Display
Various Program Combinations
IP41
Up to 6 steps
Measurement System - Automatic/Manual
230VAC Aux Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
Specification
Iskra Doo Part Number
PFC-CX-06R
Function
Reactive Power Correction
Nominal Voltage (Un)
110-480VAC Line to Line
Supply Voltage
90-300VAC (L-N), 15VA 45-65Hz
Relay Rating
250VAC/10Amp
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature Alarm
1 x Relay as above
Re-connection Delay Time
50 - 1200s User Adjustable
Desired Power Factor
0.80 IND - 0.80 CAP
Number of Output Relays
6
Smallest Capacitor Current
10mA
CT Input Range
0 - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
N/A
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP50 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
User Manual
Modbus RS485 User Manual
Iskra Quick Setup Guide
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)
Alternative in Stock
Beluk BLR-CX
Beluk BLR-CX12R, Power Factor Regulator (Beluk BLR-CX 12RL), 12 Step, 110-480V 50/60HZ, See Rebadged PFR-X+ 12R
Single CT Sensing
Isolated Switching of Power Factor Correction Contactors
Cos ϕ Setting 0.85 to 0.95 CAP
Auto CT Secondary Selection
Backlit LCD Display
Various Program Combinations
IP41
Up to 12 steps
Measurement System - Automatic/Manual
230VAC Aux Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
Specification
Beluk Part Number
BLR-CX12R
Function
Reactive Power Correction
Nominal Voltage (Un)
110-480VAC Line to Line
Supply Voltage
90-300VAC (L-N), 15VA 45-65Hz
Relay Rating
250VAC/10Amp
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature Alarm
1 x Relay as above
Re-connection Delay Time
50 - 1200s User Adjustable
Desired Power Factor
0.80 IND - 0.80 CAP
Number of Output Relays
12
Smallest Capacitor Current
10mA
CT Input Range
0 - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
N/A
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP50 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
User Manual
Modbus RS485 User Manual
Iskra Quick Setup Guide
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)
Iskra Doo PFC-CX-12R Power Factor Regulator, Controller (Beluk BLR-CX 12RL and Vishay Estamat PFC-12N), 12 Step, 110-480V 50/60HZ, Rebadged PFR-X+ 12R
Single CT Sensing
Isolated Switching of Power Factor Correction Contactors
Cos ϕ Setting 0.85 to 0.95 CAP
Auto CT Secondary Selection
Backlit LCD Display
Various Program Combinations
IP41
Up to 12 steps
Measurement System - Automatic/Manual
230VAC Aux Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
Specification
Iskra Doo Part Number
PFC-CX-12R
Function
Reactive Power Correction
Nominal Voltage (Un)
110-480VAC Line to Line
Supply Voltage
90-300VAC (L-N), 15VA 45-65Hz
Relay Rating
250VAC/10Amp
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature Alarm
1 x Relay as above
Re-connection Delay Time
50 - 1200s User Adjustable
Desired Power Factor
0.80 IND - 0.80 CAP
Number of Output Relays
12
Smallest Capacitor Current
10mA
CT Input Range
0 - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
N/A
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP50 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
User Manual
Modbus RS485 User Manual
Iskra Quick Setup Guide
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)
Alternative in Stock
Beluk BLR-CX12R
Vishay Estamat PFC-12N, Power Factor Controller, 12 Step, 90-690V 50/60HZ, See Rebadged PFR-X+ 12R & Beluk BLR-CX12R
Isolated Switching of Power Factor Correction Contactors
Cos ϕ Setting 0.85 to 0.95 CAP
Auto CT Secondary Selection
Programmable Primary CT Ratio
Backlit LCD Display
Various Program Combinations
IP41
Up to 12 steps
Measurement System - Automatic/Manual
230VAC Aux Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Temperature Sensing via NTC Sensor
Specification
Vishay Part Number
Estamat PFC-12N
Function
Reactive Power Correction
Nominal Voltage (Un)
90-690VAC Line to Line (4 Wire)
Supply Voltage
90-300VAC (L-N), 15VA 45-65Hz
Relay Rating
250VAC/5Amp
Switch Delay Time
1s - 6500s User Adjustable
Alarm
1 x Relay as above
Temperature Alarm
1 x Relay as above
Re-connection Delay Time
50ms - 1200s User Adjustable
Desired Power Factor
0.85 IND - 1.0 CAP
Number of Output Relays
14
Smallest Capacitor Current
10mA
CT Input Range
0 - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
N/A
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP40 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
Product Datasheet
Modbus RS485 User Manual
User Manual
Original Beluk User manual (with PIN code)
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)
Alternative in Stock
Beluk BLR-CX12R
Vishay Estamat MH-12N Automatic Reactive Power Controller 12 Step, 3 Phase
Isolated Switching of Power Factor Correction Contactors
Cos ϕ Setting 0.85 to 0.95 CAP
Auto CT Secondary Selection
Programmable Primary CT Ratio
Luminous Display
Various Program Combinations
IP40
Up to 12 steps
Measurement System - Automatic/Manual
230VAC Aux Supply
Overvoltage and Under/Overcompensation Alarm
Specification
Vishay Part Number
Estamat MH-12N
Function
Reactive Power Correction
Nominal Voltage (Un)
415V Line to Line (4 Wire)
Supply Voltage
230VAC (L-N), 12VA 45-65Hz
Relay Rating
250VAC/3Amp
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature Alarm
N/A
Re-connection Delay Time
1s - 1200s User Adjustable
Desired Power Factor
0.85 IND - 1.00 CAP
Number of Output Relays
13
Smallest Capacitor Current
50mA
CT Input Range
0.05 - 5.5 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
N/A
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP40 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
Product Datasheet
User Manual
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
RTR Energia REG12DPR1400000 PR-14D.12 8/10/12 Step Automatic Reactive Power Controller, 3 Phase
Isolated Switching of Power Factor Correction Contactors
Cos ϕ Setting 0.80 to 0.95 CAP
Single CT Sensing
1A/5A Programmable Primary and secondary CT Ratio
Backlit LCD Display
Various Program Combinations
IP40
Up to 12 steps
Measurement System - Automatic/Manual
230VAC Aux Supply
Overvoltage and Under/Overcompensation management
Overtemperature alarm
Specification
RTR Energia Part Number
PR-14D.12
Function
Reactive Power Correction
Nominal Voltage (Un)
90-550V L to L, 11-300V L-N
Supply Voltage
90-550V L to L, 15VA (max) 45-65Hz
Relay Rating
250VAC/6Amp NO
Switch Delay Time
1s - 999s User Adjustable
Fan Alarm
1 x 250VAC/6Amp NO
Temperature Alarm
1 x 250VAC/6Amp NO
Re-connection Delay Time
1s - 999s User Adjustable
Desired Power Factor
0.85 IND - 0.95 CAP
Number of Output Relays
14 (12 steps, fan and temperature alarm)
Smallest Capacitor Current
50mA
CT Input Range
0.05 - 5.5 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
RS485 Target PFC (Optional)
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP40 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
0...60 °C
Datasheet
Product Datasheet/User Manual
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
ACXP12T-MB-D (BLR-CX Plus 12T-MB-D), CX-Plus Power Factor Regulator, 12/13 Step SOLID SATE OUTPUTS, 1 Phase Measurement, 3 Phase Control, 110-480V 50/60HZ, Modbus RTU Comms, Step Time Recording, Alarm Recording, RS485 Modbus, with Internal Data Logger
Single CT Sensing
Isolated Switching of Power Factor Correction Contactors
Cos ϕ Setting 0.85 to 0.95 CAP
Auto CT Secondary Selection
Backlit LCD Display
Various Program Combinations
IP41
Up to 13 steps
Measurement System - Automatic/Manual
90-550VAC Aux/Measurement Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
Specification
Beluk Part Number
ACXP12T-MB-D (BLR-CX Plus 12T-MB-D) / 3ACXP12T-BEL-G-MB-D
Function
Reactive Power Correction
Nominal Voltage (Un)
110-480VAC Line to Line
Supply Voltage
90-300VAC (L-N), 15VA 45-65Hz
Relay Rating
SOLID STATE TRANSISTOR OUTPUT
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature/Fan Alarm
1 x Relay as above (Can be used as 13th Step)
Re-connection Delay Time
50 - 1200s User Adjustable
Desired Power Factor
0.80 IND - 0.80 CAP
Number of Output Relays
6
Smallest Capacitor Current
10mA
CT Input Range
5mA - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
RS485 Modbus
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP50 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
User Manual
Modbus user Manual
Comparison of CX and CX Plus Controllers
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)
ACXP12R-MB-D (BLR-CX Plus 12R-MB-D), CX-Plus Power Factor Regulator, 12/13 Step, 1 Phase Measurement, 3 Phase Control, 110-480V 50/60HZ, Modbus RTU Comms, Step Time Recording, Alarm Recording, RS485 Modbus, with Internal Data Logger
Single CT Sensing
Isolated Switching of Power Factor Correction Contactors
Cos ϕ Setting 0.85 to 0.95 CAP
Auto CT Secondary Selection
Backlit LCD Display
Various Program Combinations
IP41
Up to 13 steps
Measurement System - Automatic/Manual
90-550VAC Aux/Measurement Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
Specification
Beluk Part Number
ACXP12R-MB-D (BLR-CX Plus 12R-MB-D) / 3ACXP12R-BEL-G-MB-D
Function
Reactive Power Correction
Nominal Voltage (Un)
110-480VAC Line to Line
Supply Voltage
90-300VAC (L-N), 15VA 45-65Hz
Relay Rating
250VAC/10Amp
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature/Fan Alarm
1 x Relay as above (Can be used as 13th Step)
Re-connection Delay Time
50 - 1200s User Adjustable
Desired Power Factor
0.80 IND - 0.80 CAP
Number of Output Relays
6
Smallest Capacitor Current
10mA
CT Input Range
5mA - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
RS485 Modbus
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP50 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
User Manual
Modbus user Manual
Comparison of CX and CX Plus Controllers
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)
MPFC-PF (PF12R1A)MPFC-PF (PF24R1A), Power Factor Regulator, 24 Step, 1 Phase Measurement, 3 Phase Control, 50-530V 50/60HZ
Single CT Sensing
32nd Harmonic Measurement
Isolated Switching of Power Factor Correction Contactors
Cos ϕ Setting 0.9 to 0.9 CAP
Auto CT Secondary Selection
Backlit LCD Display
Various Program Combinations
IP41
Up to 12 steps
Measurement System - Automatic/Manual
50-530VAC Measurement
100-132V / 207-253VAC (L-N) Aux Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
Specification
Beluk Part Number
MPFC-PF / PF24R1A
Function
Reactive Power Correction
Nominal Voltage (Un)
50-530VAC Line to Line
Supply Voltage
100-132V / 207-253VAC (L-N), 45-65Hz, max fuse 6A
Relay Rating
250VAC/5Amp
Static Output Rating (T Models)
8-48VDC / 100mA
Internal 2MB Logger
Optional
3 x CT Measurement
Optional
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature/Fan/THD Alarm
1 x Relay as above
Re-connection Delay Time
50 - 1200s User Adjustable
Desired Power Factor
0.90 IND - 0.90 CAP
Number of Output Relays
12
Smallest Capacitor Current
10mA
CT Input Range
15mA - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
Optional
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP50 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
User Manual
Modbus user Manual
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)
MPFC-PF (PF12R1A), Power Factor Regulator, 12 Step, 1 Phase Measurement, 3 Phase Control, 50-530V 50/60HZ
Single CT Sensing
32nd Harmonic Measurement
Isolated Switching of Power Factor Correction Contactors
Cos ϕ Setting 0.9 to 0.9 CAP
Auto CT Secondary Selection
Backlit LCD Display
Various Program Combinations
IP41
Up to 12 steps
Measurement System - Automatic/Manual
50-530VAC Measurement
100-132V / 207-253VAC (L-N) Aux Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
Specification
Beluk Part Number
MPFC-PF / PF12R1A
Function
Reactive Power Correction
Nominal Voltage (Un)
50-530VAC Line to Line
Supply Voltage
100-132V / 207-253VAC (L-N), 45-65Hz, max fuse 6A
Relay Rating
250VAC/5Amp
Static Output Rating (T Models)
8-48VDC / 100mA
Internal 2MB Logger
Optional
3 x CT Measurement
Optional
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature/Fan/THD Alarm
1 x Relay as above
Re-connection Delay Time
50 - 1200s User Adjustable
Desired Power Factor
0.90 IND - 0.90 CAP
Number of Output Relays
12
Smallest Capacitor Current
10mA
CT Input Range
15mA - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
Optional
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP50 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
User Manual
Modbus user Manual
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)
BLR-Q(U)12R DM (3ACM12R-BEL-O-DM), Power Factor Regulator & Power Quality Analyser, 12 Step, 1 Phase Measurement, Power Quality Alarms, WITH BATTERY BACKUP, 3 Phase Control, 50-530V 50/60HZ
Single CT Sensing
32nd Harmonic Measurement
Isolated Switching of Power Factor Correction Contactors
Cos ϕ Setting 0.9 to 0.9 CAP
Auto CT Secondary Selection
Backlit LCD Display
Various Program Combinations
IP41
Up to 12 steps
Measurement System - Automatic/Manual
50-530VAC Measurement
100-132V / 207-253VAC (L-N) Aux Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
Specification
Beluk Part Number
BLR-Q(U)12R DM / 3ACM12R-BEL-O-DM
Function
Reactive Power Correction & Power Quality Analyser
Nominal Voltage (Un)
50-530VAC Line to Line
Supply Voltage
100-132V / 207-253VAC (L-N), 45-65Hz, max fuse 6A
Relay Rating
250VAC/5Amp
Static Output Rating (T Models)
8-48VDC / 100mA
Internal 2MB Logger
Optional
Battery Backup
YES
3 x CT Measurement
Optional
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature/Fan/THD Alarm
1 x Relay as above
Re-connection Delay Time
50 - 1200s User Adjustable
Desired Power Factor
0.90 IND - 0.90 CAP
Number of Output Relays
12
Smallest Capacitor Current
10mA
CT Input Range
15mA - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
Optional
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP50 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
User Manual
Modbus user Manual
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)