Crouzet Automation 84903020, Three Phase Voltage Control Relay, Phase Sequence or Phase Failure - 17.5 mm EMWS, 208-480 VAC, Self Powered
For Phase Sequence of Phase Failure Monitoring of AC Voltages up to 480VAC
Features:
Control Monitoring of AC voltages
Automatic recognition of AC
Measurement ranges from 288 V to 480 VAC
Choice between under and overvoltage
True RMS measurement
Selectable latching (memory) function
Specification
Crouzet Part Number
84903020 (Three Phase C-Lynx Voltage Monitoring Relay With SPDT Contacts)
Function
Phase Sequence/Phase Failure
Nominal Voltage
1 x 208 - 480 VAC/DC
Digital Outputs
1 x C/O Relays, 250VAC/DC @ 5 Amp
Min Breaking Current
10mA/5VDC
Delay on Threshhold Crossing
0.1 → 3s (0, +10%)
Delay on Pickup
600ms
Alarm Delay on Time (max)
200ms
Reset Time
1500ms
Adjustable Hysteresis
5 - 50% of Threshhold
Maximum Measurement Cycle Time
30ms/True RMS Measurement
Measurement Accuracy
1%
Supply Voltage Range
Same as Measurement 3 x 220 → 3 x 480 V ∿
Termination Style
Screw
Weight
170g
Certification
CE, UL, CSA, GL, ROHS
Factory Pack Qty
1
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
Fastron FRV 8-04/265, 127 to 265VAC L-N Voltage Monitoring Relay, 3 Phase 4 Wire Over/Under Voltage Detection, 1 x CO SPDT 8 Amp Contact, Adjustable Timer Delay, Adjustable Upper and Lower Voltage Limits
FRV 8 Series serves to monitor voltage, phase failure and sequence in switchboards, protection of devices in 3-phase 4 wire mains
Features
Upper and lower level of monitoring voltage
Adjustable time delay eliminates short voltage peaks and failures in the main
Supply is done from monitored voltage
Faulty state is indicated by red LED and by opening of output relay contact
Output contact 1 x Changeover / SPDT 10 A /250 V AC1
In case supply voltage falls below 60 %Un (U lower level) relay off immediately opens without delay
FRV8-04/460 - supply from all phases which means that relay is functional also in case when one phase is faulty
Variant FRV 8-04/265 - supply L1-N, means that relay monitors also failure of neutral wire
1-MODULE, DIN rail mounting
Specification
Technical Data
FRV 8
Supply and measuring
L1, L2, L3 (127,132,138,220,230,240,254,265VAC)
Supply terminals
L1, L2, L3
Supply/measured voltage
3 x 127-265 V (L-N) / 50 Hz
Level Umax
105 - 125 % Un
Level Umin
75 - 95 % Un
Burden
max. 2 VA
Hysteresis
2 %
Max. permanent overload
AC 3 x 265 V
Peak overload <1ms
AC 3 x 265 V
Time delay T1
max. 500 ms
Time delay T2
adjustable 0.1-10 s
Output
Number of contacts
1 x changeover/ SPDT (AgNi / Silver Alloy)
Current rating
10 A / AC1
Breaking capacity
2500 VA / AC1, 240 W / DC
Inrush current
10 A
Switching voltage
250 V AC1 / 24 V DC
Min. breaking capacity DC
500 mW
Indication of state
red LED
Mechanical life
1 x 107
Electrical life (AC1)
1 x 105
Other information
Operating temperature
-20 ... +55 °C
Storage temperature
-30 ... +70 °C
Electrical strength
4 kV (supply - output)
Operating position
any
Mounting
DIN rail EN 60715
Protection degree
IP 40 from front panel / IP 10 terminals
Overvoltage cathegory
III.
Pollution degree
2
Max. cable size (mm )2
solid wire max. 2x2.5 or 1x4 ; with sleeve max. 1x2.5 or 2x1.5
Dimensions
90 x 17,6 x 64 mm
Weight
69 g
Standards
EN 60255-6, EN 61010-1, RoHS, CE, CE
Datasheet
Product Datasheet
Fastron Monitoring/Time Relays Catalogue
For items in our catalogue which are not listed online please Contact Us for Possible Replacement
Application Notes
Relay in 3-phase main monitors size of phase voltage. It is possible to set two independent voltage levels and thus it is possible to set two independent voltage levels and monitor e.g. undervoltage and overvoltage independently. In normal state when voltage is within set levels, output relay is closed and red LED shines.
In case voltage exceeds or falls below the set levels, output relay opens and red LED shines ( LED indicates faulty state – flashes when timing). In case supply voltage falls below 60 % Un (UOFF lower level)relay immediately opens without delay and faulty state is indicated by red LED.In case timing is in progress and faulty state is indicated, timing is immediately stopped.
Fastron FRV 8-04/460, 220-460VAC L-L Voltage Monitoring Relay, 3 Phase Over/Under Voltage Detection, 1 x CO SPDT 8 Amp Contact, Adjustable Timer Delay, Adjustable Upper and Lower Voltage Limits
FRV 8 Series serves to monitor voltage, phase failure and sequence in switchboards, protection of devices in 3-phase mains
Features
Upper and lower level of monitoring voltage
Adjustable time delay eliminates short voltage peaks and failures in the main
Supply is done from monitored voltage
Faulty state is indicated by red LED and by opening of output relay contact
Output contact 1 x Changeover / SPDT 10 A /250 V AC1
In case supply voltage falls below 60 %Un (U lower level) relay off immediately opens without delay
FRV 8-04/460 - supply from all phases which means that relay is functional also in case when one phase is faulty
Variant FRV 8-04/265 - supply L1-N, means that relay monitors also failure of neutral wire
1-MODULE, DIN rail mounting
Specification
Technical Data
FRV 8
Supply and measuring
L1, L2, L3 (220,230,240,380,400,415,440,460VAC)
Supply terminals
L1, L2, L3
Supply/measured voltage
3 x 220-460 V / 50 Hz
Level Umax
105 - 125 % Un
Level Umin
75 - 95 % Un
Burden
max. 2 VA
Hysteresis
2 %
Max. permanent overload
AC 3 x 460 V
Peak overload <1ms
AC 3 x 500 V
Time delay T1
max. 500 ms
Time delay T2
adjustable 0.1-10 s
Output
Number of contacts
1 x changeover/ SPDT (AgNi / Silver Alloy)
Current rating
10 A / AC1
Breaking capacity
2500 VA / AC1, 240 W / DC
Inrush current
10 A
Switching voltage
250 V AC1 / 24 V DC
Min. breaking capacity DC
500 mW
Indication of state
red LED
Mechanical life
1 x 107
Electrical life (AC1)
1 x 105
Other information
Operating temperature
-20 ... +55 °C
Storage temperature
-30 ... +70 °C
Electrical strength
4 kV (supply - output)
Operating position
any
Mounting
DIN rail EN 60715
Protection degree
IP 40 from front panel / IP 10 terminals
Overvoltage cathegory
III.
Pollution degree
2
Max. cable size (mm )2
solid wire max. 2x2.5 or 1x4 ; with sleeve max. 1x2.5 or 2x1.5
Dimensions
90 x 17,6 x 64 mm
Weight
69 g
Standards
EN 60255-6, EN 61010-1, RoHS, CE
Datasheet
Product Datasheet
Fastron Monitoring/Time Relays Catalogue
For items in our catalogue which are not listed online please Contact Us for Possible Replacement
Application Notes
Relay in 3-phase main monitors size of phase voltage. It is possible to set two independent voltage levels and thus it is possible to set two independent voltage levels and monitor e.g. undervoltage and overvoltage independently. In normal state when voltage is within set levels, output relay is closed and red LED shines.
In case voltage exceeds or falls below the set levels, output relay opens and red LED shines ( LED indicates faulty state – flashes when timing). In case supply voltage falls below 60 % Un (UOFF lower level)relay immediately opens without delay and faulty state is indicated by red LED.In case timing is in progress and faulty state is indicated, timing is immediately stopped.
Fastron FRV 8-06/265, 127 to 265VAC L-N Voltage Monitoring Relay, 3 Phase 4 Wire Over/Under Voltage Detection, 1 x CO SPDT 8 Amp Contact, Fixed 2s Timer Delay, Adjustable Upper and Lower Voltage Limits, Adjustable Asymmetry
FRV 8 Series serves to monitor voltage, phase failure and sequence in switchboards, protection of devices in 3-phase 4 wire mains
Features
Upper and lower level of monitoring voltage
Asymmetry
Adjustable time delay eliminates short voltage peaks and failures in the main
Supply is done from monitored voltage
Faulty state is indicated by red LED and by opening of output relay contact
Output contact 1 x Changeover / SPDT 10 A /250 V AC1
In case supply voltage falls below 60 %Un (U lower level) relay off immediately opens without delay
FRV8-06/460 - supply from all phases which means that relay is functional also in case when one phase is faulty
Variant FRV 8-04/265 - supply L1-N, means that relay monitors also failure of neutral wire
1-MODULE, DIN rail mounting
Specification
Technical Data
FRV 8
Supply and measuring
L1, L2, L3 (127,132,138,220,230,240,254,265VAC)
Supply terminals
L1, L2, L3
Supply/measured voltage
3 x 127-265 V (L-N) / 50 Hz
Level Umax
105 - 125 % Un
Level Umin
75 - 95 % Un
Burden
max. 2 VA
Hysteresis
2 %
Max. permanent overload
AC 3 x 265 V
Peak overload <1ms
AC 3 x 265 V
Time delay T1
max. 500 ms
Time delay T2
adjustable 0.1-10 s
Output
Number of contacts
1 x changeover/ SPDT (AgNi / Silver Alloy)
Current rating
10 A / AC1
Breaking capacity
2500 VA / AC1, 240 W / DC
Inrush current
10 A
Switching voltage
250 V AC1 / 24 V DC
Min. breaking capacity DC
500 mW
Indication of state
red LED
Mechanical life
1 x 107
Electrical life (AC1)
1 x 105
Other information
Operating temperature
-20 ... +55 °C
Storage temperature
-30 ... +70 °C
Electrical strength
4 kV (supply - output)
Operating position
any
Mounting
DIN rail EN 60715
Protection degree
IP 40 from front panel / IP 10 terminals
Overvoltage cathegory
III.
Pollution degree
2
Max. cable size (mm )2
solid wire max. 2x2.5 or 1x4 ; with sleeve max. 1x2.5 or 2x1.5
Dimensions
90 x 17,6 x 64 mm
Weight
69 g
Standards
EN 60255-6, EN 61010-1, RoHS, CE, CE
Datasheet
Product Datasheet
Fastron Monitoring/Time Relays Catalogue
For items in our catalogue which are not listed online please Contact Us for Possible Replacement
Application Notes
Relay in 3-phase main monitors size of phase voltage. It is possible to set two independent voltage levels and thus it is possible to set two independent voltage levels and monitor e.g. undervoltage and overvoltage independently. In normal state when voltage is within set levels, output relay is closed and red LED shines.
In case voltage exceeds or falls below the set levels, output relay opens and red LED shines ( LED indicates faulty state – flashes when timing). In case supply voltage falls below 60 % Un (UOFF lower level)relay immediately opens without delay and faulty state is indicated by red LED.In case timing is in progress and faulty state is indicated, timing is immediately stopped.
GIC Controls MG73BQ 3 Phase 4 Wire or Single Phase Voltage Monitoring Relay With DPDT Contacts, Undervoltage, Selectable Overvoltage, 3 x 120-240 VAC
Relay control, on 3-phase networks :
Overvoltage between phases,
Undervoltage between phases
Overvoltage between phases and neutral,
Undervoltage between phases and neutral,
Loss of neutral
Multi-voltage Products
Controls its own supply voltage
True RMS measurement
LED status indication
3-phase voltage controllers which monitor :
Undervoltage, adjustable from -20 to -2 % of Un
Overvoltage, adjustable from 2 to 20 % of Un
Measurements are taken between neautral and Phases for MG73BQ
MG73BQ and between Phases and Neutral for the H3USN Faults are signalled via LEDs, distinguishing the origin of the fault (one LED for the upper threshold, one LED for the lower threshold). Set the selector switch to the 3-phase network voltage Un.
The position of this selector switch is only taken into account when the unit is powered up. If the switch position changes while the unit is operating, all the LEDs flash but the product continues to work normally with the voltage selected on energisation prior to the change of position. The LEDs return to their normal state if the switch is reset to its initial position defined before the last energisation.
Specification
GIC Controls Part Number
MG73BQ (3 Phase 4 Wire/Single Phase Monitoring Relay With DPDT Contacts)
Function
Undervoltage/Overvoltage between phases
Nominal Voltage
3 x 120 → 3 x 240 V ∿
Digital Outputs
2 x C/O Relays, 250VAC/DC @ 5 Amp
Min Breaking Current
10mA/5VDC
Timing Range
0.3 → 30s (0, +10%)
Delay on Pickup
500ms
Alarm Delay on Time (max)
200ms
Reset Time
1500ms
Fixed Hysteresis
2% of Un
Maximum Measurement Cycle Time
150ms/True RMS Measurement
Measurement Accuracy
1%
Supply Voltage Range
Same as Measurement 3 x 220 → 3 x 480 V ∿
Termination Style
Screw
Weight
170g
Certification
CE, UL, CSA, GL, ROHS
Factory Pack Qty
1
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
Crouzet Automation 84872152, Single Phase Voltage Control Relay Under/Overvoltage Detection - 17.5 mm MUS, 65-260 VAC/DC Measurement/Supply, Replaces DSR2 Series
For under and over voltage monitoring of Single phase AC or DC Voltages 65 to 260V
Features:
Control of AC and DC voltages
Automatic recognition of AC/DC
Measurement ranges from 65 V to 260 V
Choice between under and over voltage
True RMS measurement
Selectable latching (memory) function
Specification
Crouzet Part Number
84872142 (Single Phase MUSF Voltage Monitoring Relay With Non-Latching SPDT Contacts)
Function
Undervoltage/Overvoltage
Supply Voltage
65 - 260 VAC/DC
Measurement Voltage
1 x 15-600VAC/DC
Digital Outputs
1 x C/O Relays, 250VAC/DC @ 5 Amp
Min Breaking Current
10mA/5VDC
Delay on Threshhold Crossing
0.1 → 3s (0, +10%)
Delay on Pickup
600ms
Alarm Delay on Time (max)
200ms
Reset Time
1500ms
Adjustable Hysteresis
5 - 50% of Threshhold
Maximum Measurement Cycle Time
30ms/True RMS Measurement
Measurement Accuracy
1%
Supply Voltage Range
Same as Measurement
Termination Style
Screw
Weight
170g
Certification
CE, UL, CSA, GL, ROHS
Factory Pack Qty
1
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
Iskra Doo MVR 54N 400VAC Series Voltage Monitoring Relay
MVR 54N Series serves to monitor voltage, phase failure and sequence in switchboards, protection of devices in 3-phase 4 wire mains
Features
Upper and lower level of monitoring voltage
Adjustable time delay eliminates short voltage peaks and failures in the main
Supply is done from monitored voltage
Faulty state is indicated by red LED and by opening of output relay contact
Output contact 1 x Changeover / SPDT 8 A /250 V AC1
In case supply voltage falls below 60 %Un (U lower level) relay off immediately opens without delay
MVR 54 - supply from all phases which means that relay is functional also in case when one phase is faulty
Variant MVR 54N - supply L1-N, means that relay monitors also failure of neutral wire
1-MODULE, DIN rail mounting
Specification
Technical Data
MVR 54
MVR 54N
Supply and measuring
L1, L2, L3
L1, L2, L3, N
Supply terminals
L1, L2, L3
L1, N
Supply/measured voltage
3 x 400 V / 50 Hz
3 x 400 V / 230 V /50 Hz
Level Umax
105 - 125 % Un
Level Umin
75 - 95 % Un
Burden
max. 2 VA
Hysteresis
2 %
Max. permanent overload
AC 3 x 460 V
AC 3 x 265 V
Peak overload <1ms
AC 3 x 500 V
AC 3 x 288 V
Time delay T1
max. 500 ms
Time delay T2
adjustable 0.1-10 s
Output
Number of contacts
1x changeover/ SPDT (AgNi / Silver Alloy)
Current rating
8 A / AC1
Breaking capacity
2500 VA / AC1, 240 W / DC
Inrush current
10 A
Switching voltage
250 V AC1 / 24 V DC
Min. breaking capacity DC
500 mW
Indication of state
red LED
Mechanical life
1 x 107
Electrical life (AC1)
1 x 105
Other information
Operating temperature
-20 ... +55 °C
Storage temperature
-30 ... +70 °C
Electrical strength
4 kV (supply - output)
Operating position
any
Mounting
DIN rail EN 60715
Protection degree
IP 40 from front panel / IP 10 terminals
Overvoltage cathegory
III.
Pollution degree
2
Max. cable size (mm )2
solid wire max. 2x2.5 or 1x4 ; with sleeve max. 1x2.5 or 2x1.5
Dimensions
90 x 17,6 x 64 mm
Weight
69 g
67 g
Standards
EN 60255-6, EN 61010-1
Datasheet
Product Datasheet
Application Notes
Relay in 3-phase main monitors size of phase voltage. It is possible to set two independent voltage levels and thus it is possible to set two independent voltage levels and monitor e.g. undervoltage and overvoltage independently. In normal state when voltage is within set levels, output relay is closed and red LED shines.
In case voltage exceeds or falls below the set levels, output relay opens and red LED shines ( LED indicates faulty state – flashes when timing). In case supply voltage falls below 60 % Un (UOFF lower level)relay immediately opens without delay and faulty state is indicated by red LED.In case timing is in progress and faulty state is indicated, timing is immediately stopped.
Crouzet Automation 84872120, Single Phase Multi-Function Voltage Control Relay Under/Overvoltage Detection and Latching (Memory) Function- 35 mm HUL, 0.2-60 VAC/DC Measurement, 24/240 VAC/DC Supply
For under and overvoltage monitoring of Single phase AC or DC Voltages up to 600V
Features:
Control of AC and DC voltages
Automatic recognition of AC/DC
Measurement ranges from 0.2 V to 60 V
Choice between under and overvoltage
True RMS measurement
Selectable latching (memory) function
Specification
Crouzet Part Number
84872120 (Single Phase C-Lynx Voltage Monitoring Relay With DPDT Contacts)
Function
Undervoltage/Overvoltage
Nominal Voltage
1 x 0.2 - 60 VAC/DC
Digital Outputs
2 x C/O Relays, 250VAC/DC @ 8 Amp
Min Breaking Current
10mA/5VDC
Delay on Threshhold Crossing
0.1 → 3s (0, +10%)
Delay on Pickup
600ms
Alarm Delay on Time (max)
200ms
Reset Time
1500ms
Adjustable Hysteresis
5 - 50% of Threshhold
Maximum Measurement Cycle Time
30ms/True RMS Measurement
Measurement Accuracy
1%
Supply Voltage Range
Same as Measurement
Termination Style
Screw
Weight
170g
Certification
CE, UL, CSA, GL, ROHS
Factory Pack Qty
1
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
Crouzet 84873034, 3 Phase Voltage Monitoring Relay With 17.5mm DPDT Contacts, 3 x 230 - 460 V AC EWS2, Sequence, Failure, OBSOLETE WITH NO DIRECT REPLACEMENT, SEE 84873029 For Possible Replacement
EWS2 relays control, on 3-phase networks :
Phase Failure
Sequence Detection
Controls its own supply voltage
True RMS measurement
LED status indication
Specification
Crouzet Part Number
84873034 (3 Phase Voltage Monitoring Relay With DPDT Contacts)
Function
Phase Sequence, Phase Failure
Nominal Voltage
3 x 230 → 3 x 460 V ∿
Digital Outputs
2 x C/O Relays, 250VAC/DC @ 8 Amp
Min Breaking Current
10mA/5VDC
Timing Range
N/A
Delay on Pickup
500ms
Alarm Delay on Time (max)
200ms
Reset Time
1500ms
Fixed Hysteresis
2% of Un
Maximum Measurement Cycle Time
150ms/True RMS Measurement
Measurement Accuracy
1%
Supply Voltage Range
Same as Measurement 3 x 208 → 3 x 480 V ∿
Termination Style
Screw
Weight
170g
Certification
CE, UL, CSA, GL, ROHS
Factory Pack Qty
1
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
Alternatives
84873029
Crouzet 84873029, 3 Phase Voltage Monitoring Relay With 17.5mm SPDT Contacts, 3 x 208 - 480 V AC MWA, Phase Sequence, Total Failure, Can Replace 84892290, 84873034
RMC2 MWS relays control, on 3-phase networks :
Sequence Detection
Total Phase Failure
Controls its own supply voltage
True RMS measurement
LED status indication
3-phase voltage controllers which monitor :
Non Adjustable
Specification
Crouzet Part Number
84873029 (3 Phase Voltage Monitoring Relay With SPDT Contacts)
Function
Total Phase Failure, Phase Sequence
Nominal Voltage
3 x 208 → 3 x 480 V ∿
Digital Outputs
1 x C/O Relays, 250VAC/DC @ 5 Amp
Min Breaking Current
10mA/5VDC
Timing Range
0.3 → 30s (0, +10%)
Delay on Pickup
500ms
Alarm Delay on Time (max)
200ms
Reset Time
1500ms
Fixed Hysteresis
2% of Un
Maximum Measurement Cycle Time
150ms/True RMS Measurement
Measurement Accuracy
1%
Supply Voltage Range
Same as Measurement 3 x 208 → 3 x 480 V ∿
Termination Style
Screw
Weight
170g
Certification
CE, UL, CSA, GL, ROHS
Factory Pack Qty
1
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
Fastron FRV 8-06/460, 220-460VAC L-L Voltage Monitoring Relay, 3 Phase Over/Under Voltage Detection, 1 x CO SPDT 8 Amp Contact, Fixed 2s Timer Delay, Adjustable Upper and Lower Voltage Limits, Adjustable Asymmetry
FRV 8 Series serves to monitor voltage, phase failure and sequence in switchboards, protection of devices in 3-phase mains
Features
Upper and lower level of monitoring voltage
Asymmetry
Adjustable time delay eliminates short voltage peaks and failures in the main
Supply is done from monitored voltage
Faulty state is indicated by red LED and by opening of output relay contact
Output contact 1 x Changeover / SPDT 10 A /250 V AC1
In case supply voltage falls below 60 %Un (U lower level) relay off immediately opens without delay
FRV 8-04/460 - supply from all phases which means that relay is functional also in case when one phase is faulty
Variant FRV 8-06/265 - supply L1-N, means that relay monitors also failure of neutral wire
1-MODULE, DIN rail mounting
Specification
Technical Data
FRV 8
Supply and measuring
L1, L2, L3 (220,230,240,380,400,415,440,460VAC)
Supply terminals
L1, L2, L3
Supply/measured voltage
3 x 220-460 V / 50 Hz
Level Umax
105 - 125 % Un
Level Umin
75 - 95 % Un
Burden
max. 2 VA
Hysteresis
2 %
Max. permanent overload
AC 3 x 460 V
Peak overload <1ms
AC 3 x 500 V
Time delay T1
max. 500 ms
Time delay T2
adjustable 0.1-10 s
Output
Number of contacts
1 x changeover/ SPDT (AgNi / Silver Alloy)
Current rating
10 A / AC1
Breaking capacity
2500 VA / AC1, 240 W / DC
Inrush current
10 A
Switching voltage
250 V AC1 / 24 V DC
Min. breaking capacity DC
500 mW
Indication of state
red LED
Mechanical life
1 x 107
Electrical life (AC1)
1 x 105
Other information
Operating temperature
-20 ... +55 °C
Storage temperature
-30 ... +70 °C
Electrical strength
4 kV (supply - output)
Operating position
any
Mounting
DIN rail EN 60715
Protection degree
IP 40 from front panel / IP 10 terminals
Overvoltage cathegory
III.
Pollution degree
2
Max. cable size (mm )2
solid wire max. 2x2.5 or 1x4 ; with sleeve max. 1x2.5 or 2x1.5
Dimensions
90 x 17,6 x 64 mm
Weight
69 g
Standards
EN 60255-6, EN 61010-1, RoHS, CE
Datasheet
Product Datasheet
Fastron Monitoring/Time Relays Catalogue
For items in our catalogue which are not listed online please Contact Us for Possible Replacement
Application Notes
Relay in 3-phase main monitors size of phase voltage. It is possible to set two independent voltage levels and thus it is possible to set two independent voltage levels and monitor e.g. undervoltage and overvoltage independently. In normal state when voltage is within set levels, output relay is closed and red LED shines.
In case voltage exceeds or falls below the set levels, output relay opens and red LED shines ( LED indicates faulty state – flashes when timing). In case supply voltage falls below 60 % Un (UOFF lower level)relay immediately opens without delay and faulty state is indicated by red LED.In case timing is in progress and faulty state is indicated, timing is immediately stopped.
Crouzet 84873024, 3 Phase Voltage Monitoring Relay With 17.5mm SPDT Contacts, 3 x 208 - 480 V AC MWA, Sequence, Failure, Imbalance (asymmetry), Under/Over
MWA relays control, on 3-phase networks :
Overvoltage between phases,
Undervoltage between phases
Asymmetry (Imbalance)
Sequence Detection
Controls its own supply voltage
True RMS measurement
LED status indication
3-phase voltage controllers which monitor :
Undervoltage, adjustable from -20 to -2 % of Un
Overvoltage, adjustable from 2 to 20 % of Un
Asymmetry, adjustable from 5 to 15% of Selected Un
Presence of the neutral (H3USN only) Measurements are taken between Phases for the H3US
M3US and between Phases and Neutral for the H3USN Faults are signalled via LEDs, distinguishing the origin of the fault (one LED for the upper threshold, one LED for the lower threshold). Set the selector switch to the 3-phase network voltage Un.
The position of this selector switch is only taken into account when the unit is powered up. If the switch position changes while the unit is operating, all the LEDs flash but the product continues to work normally with the voltage selected on energisation prior to the change of position. The LEDs return to their normal state if the switch is reset to its initial position defined before the last energisation.
Specification
Crouzet Part Number
84873224 (3 Phase Voltage Monitoring Relay With SPDT Contacts)
Function
Undervoltage/Overvoltage between phases
Nominal Voltage
3 x 208 → 3 x 480 V ∿
Digital Outputs
1 x C/O Relays, 250VAC/DC @ 5 Amp
Min Breaking Current
10mA/5VDC
Timing Range
0.3 → 30s (0, +10%)
Delay on Pickup
500ms
Alarm Delay on Time (max)
200ms
Reset Time
1500ms
Fixed Hysteresis
2% of Un
Maximum Measurement Cycle Time
150ms/True RMS Measurement
Measurement Accuracy
1%
Supply Voltage Range
Same as Measurement 3 x 208 → 3 x 480 V ∿
Termination Style
Screw
Weight
170g
Certification
CE, UL, CSA, GL, ROHS
Factory Pack Qty
1
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
Application Notes
Legend
1
Overvoltage
2
Hysteresis
3
Undervoltage
4
Phases L1, L2, L3
5
Relay R1
6
Relay R2
7
Overvoltage threshold delay
8
Undervoltage threshold delay
The relay monitors its own supply voltage. It controls :
Undervoltage, adjustable from - 2 to - 20 % of Un (-2 to -12 % over the 3 x 220 V ∿ range due to the minimum voltage 194 V ∿)
Overvoltage, adjustable from + 2 to +20 % (+2 to +10 % over the 3 x 480 V ∿ range due to the maximum voltage 528 V ∿). Each threshold has its own time delay with independent setting between 0.3 and 30 s. In the event of a voltage fault, the corresponding relay (one undervoltage output/one overvoltage output) opens at the end of the time delay set by the user. In the event of phase failure, both relays open instantaneously, without waiting for the end of the time delay. The two relay LEDs go out. The relay monitors its own supply voltage. It controls :
Presence of the neutral, - Undervoltage, adjustable from -2 to -20 % of Un, - Overvoltage, adjustable from +2 to +20 %. Each threshold has its own time delay with independent setting between 0.3 and 30 s. In the event of a voltage fault, the corresponding relay (one undervoltage output/one overvoltage output) opens at the end of the time delay set by the user. If neutral is lost, both relays open instantaneously and the corresponding LED is extinguished, without waiting for the end of the time delay. The two relay LEDs are extinguished.