Rishabh Rish Con M+ CM44111111, Class 0.5 Power Transducer 4 wire, 100-600V L-L, 1 or 5Amp measurement, 85-285VAC/DC Aux Supply, 4 x Analogue -20-20mA/4-20mA/-10-10V Outputs, 2 x Relay Outputs, USB Programming Port, Modbus RTU Comms, without display
Measures Active Power/Phase Angle/Power Factor
Measures Apparent/Reactive/Active Power
Analogue output setting 0-20mA/4-20mA/0-10V (Programmable)
Free Program Software
300mS response time
PC 94 UL V0
Input Voltages, Current or Power Measurements can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 122.5 x 66 x 106.5mm depth DIN Rail cabinet space
Specification
Rishabh Part Number
Rish Con M+ CM44111111
Functions
Active Power/Phase Angle/Power Factor Transducer 4 wire
Measurement Output
4 x 4-20mA/0-20mA/0-10V User Selectable and Programable
Relay Output
2
Relay Type
Voltage Free Contact, 0.5 Amp @ 250VAC
Input
100 - 600VAC L-L 50/60Hz
Overload (Continuous)
120%
Overload (1 second)
150%
Operating Temperature
-10 - 55°C
Supply Voltage
85-285VAC/DC
Accuracy
0.2% Current, Voltage (0.5% Power)
Response Time
300mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Mounting Size
122.5 x 66 x 106.5mm
Safety
IP40/IP20 EN60529 Protection Class II EN61010
Weight
400g
Factory Pack Qty
1
Datasheet
Product Datasheet
Product User Manual
Technical Support
Rish Con P setup procedure blog
Brand Comparison to Iskra UMT540 or MT540 Series
MC330 S ARNG SUDNNPT, Panel Mount Multifunction Meter, Class 1, 50-500VAC Autorange, 61 Parameter (U, I, P, Q, S, PF, PA, f, ϴ, THD, MD …), 4 Energy Counters, RS485 Comms, Universal 20-300VDC, 48-276VAC Aux, IP54, CT Terminals, Internal Logger
Internal 8MB Logger
Universal AC/DC Power Supply
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 500 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
Optional RS 232/RS 485 communication up to 115,200 bit/s
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Harmonic Measurements to the 31st
Measurements of energy in all 4 quadrants Average values of measurands per interval
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 60 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy class 1
Internal Logger
Measurement of 20 minimal and maximal values in different time periods
Optional dual tariff inputs and pulse or relay outputs
Wide frequency range from 16 Hz to 400 Hz
RS 232/RS 485 communication up to 115,200 bit/s or Ethernet communication
MODBUS communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal or AC power supply
Graphic LCD 128 x 64 dots with illumination
Automatic range of nominal current up to 5 A and nominal voltage up to 600 V
Multilingual support
User-friendly PC MiQen software
Specification
Iskra Doo Part Number
MC330 S ARNG SUDNNPT
Functions
Power Quality Meter, Energy Meter
Supply Voltage
Universal 20-300VDC, 48-276VAC < 5VA
Nominal Measurement Range
500V L-N, 5 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
N/A
Tariff Input
N/A (Optional 4 x )
Accuracy
Class 1 (I,U,F,PF,θ,THD) Class 2(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Internal Logger
Yes (8MB)
RS485
2400-115200 b/s
Weight
500g
Certification
UL, CSA, ROHS
Factory Pack Qty
1
EU Directives
Degree on electrical equipment designed for use within certain voltage limits URLRS 53/00 (Directive 73/23/EEC on low voltage): SIST EN 61010-1:2002
Safety Requirement for electrical equipment for measurement, control and laboratory use, part1 : general requirement
Decree on electromagnetic Compatibility (EMC) URLRS 61/00 (Directive 89/336/EEC on electromagnetic compatibility): SIST EN 61036 item 4.5: 1998 Meters for active energy (class 1 and 2)
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP52 (IP00 for terminals) in compliance with SIST EN 60529:1997
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
User Manual
MC330 H ARNG SUDMNAT, Panel Mount Multifunction Meter, Class 0.5, 50-500VAC Autorange, 61 Parameter (U, I, P, Q, S, PF, PA, f, ϴ, THD, MD …), 4 Energy Counters, 2 x Relay Outputs 0-20mA, RS485 Comms, Universal 20-300VDC, 48-276VAC Aux, Internal Logger
Internal 8MB Logger
Universal AC/DC Power Supply
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 500 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
Optional RS 232/RS 485 communication up to 115,200 bit/s
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Internal Logger
Measurement of instantaneous values of more than 60 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy class 0.5
Measurement of 20 minimal and maximal values in different time periods
Optional dual tariff inputs and pulse or relay outputs
Wide frequency range from 16 Hz to 400 Hz
RS 232/RS 485 communication up to 115,200 bit/s or Ethernet communication
MODBUS communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal or AC power supply
Graphic LCD 128 x 64 dots with illumination
Automatic range of nominal current up to 5 A and nominal voltage up to 600 V
Multilingual support
User-friendly PC MiQen software
Specification
Iskra Doo Part Number
MC330 H ARNG SUDMNAT
Functions
Power Quality Meter, Energy Meter
Supply Voltage
Universal 20-300VDC, 48-276VAC < 5VA
Nominal Measurement Range
500V L-N, 5 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
2 x Analogue Outputs 0-20mA
Tariff Input
N/A (Optional 4 x )
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS232/RS485
2400-115200 b/s
Weight
500g
Certification
UL, CSA, ROHS
Factory Pack Qty
1
EU Directives
Degree on electrical equipment designed for use within certain voltage limits URLRS 53/00 (Directive 73/23/EEC on low voltage): SIST EN 61010-1:2002
Safety Requirement for electrical equipment for measurement, control and laboratory use, part1 : general requirement
Decree on electromagnetic Compatibility (EMC) URLRS 61/00 (Directive 89/336/EEC on electromagnetic compatibility): SIST EN 61036 item 4.5: 1998 Meters for active energy (class 1 and 2)
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP52 (IP00 for terminals) in compliance with SIST EN 60529:1997
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
User Manual
Lumel P43 221300M0, Class 0.5 Power Transducer 4 wire, 20-480V L-L, 5Amp measurement, 85-253VAC/90-320VDC Supply, 4 x Analogue -20-20mA/4-20mA/-10-10V output, USB Programming Port, Modbus RTU Comms, 750 OHM Load Resistance, without display
Measures Active Power/Phase Angle/Power Factor
Measures Apparent/Reactive/Active Power
Analogue output setting 0-20mA/4-20mA/0-10V
300mS response time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 122.5 x 66 x 106.5mm depth DIN Rail cabinet space
Specification
Lumel Part Number
P43 221300M0
Functions
Active Power/Phase Angle/Power Factor Transducer 4 wire
Measurement Output
4 x 4-20mA/0-20mA/0-10V User Selectable
Relay Output
N/A
Relay Type
Voltage Free Contact, 0.5 Amp @ 250VAC
Input
20 - 480VAC L-L 50/60Hz
Overload (Continuous)
120%
Overload (1 second)
150%
Operating Temperature
-10 - 55°C
Supply Voltage
85-253VAC/90-320VDC
Accuracy
0.2%
Response Time
300mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Mounting Size
122.5 x 66 x 106.5mm
Safety
IP40/IP20 EN60529 Protection Class II EN61010
Weight
400g
Factory Pack Qty
1
Datasheet
Product Datasheet
Iskra Doo MC740 S SFUNC, Panel Mount Measuring Center 3 Phase, Class 0.5 50-500VAC L-L 50/60Hz Measurement, 240VAC Supply, USB Comms, w/ Supercap
Smart Meter
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 750 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
Optional RS 232/RS 485 communication up to 115,200 bit/s or Ethernet communication
Usage
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 140 quantities (U, I, P, Q, S, PF, PA, f, f, MD, energy, energy price by tariffs, etc.).
Accuracy class 0.5 or 0.2 (on demand)
Measurement of 40 minimal and maximal values in different time periods
32 adjustable alarms
Wide frequency range from 16 Hz to 400 Hz
RS 232/RS 485 communication up to 115,200 bit/s or Ethernet communication
MODBUS and DNP3 communication protocol
MMC memory card for setting and upgrading the meter
Up to 4 inputs or outputs (analogue outputs, pulse outputs, alarm outputs, tariff inputs)
Universal or AC power supply
Graphic LCD 128 x 64 dots with illumination
Automatic range of nominal current up to 5 A and nominal voltage up to 750 V
Adjustable tariff clock, display of electric energy consumption in optional currency
Multilingual support
User-friendly PC MiQen software
128 samples in one period
Measurement of THD on Current or Voltage from 0 to 400%
Specification
Iskra Doo Part Number
MC740 S SFUNC
Functions
Power Quality Meter, Energy Meter, Power Transducer, Network Analyser
Supply Voltage
240VAC < 5VA 50/60Hz
Nominal Measurement Range
50-500VAC L-L, 5 Amp
Maximum Measurement Range
750V L-N, 12.5 Amp
Alarm
N/A (Optional 4 Relays, 32 Alarms, 4 Groups)
Analogue Output
N/A (Optional 4 x 20mA)
Digital Input
N/A (Optional 4 x 230VAC/DC,75..130VAC/DC..5..48VAC/DC)
Pulse Output
N/A (Optional)
Pulse Input
N/A (Optional)
Bistable Switch/Latching Relay Alarm
N/A (Optional)
Status (Watchdog) Output
N/A (Optional)
Tariff Input
N/A (Optional 4 x 230VAC/DC,75..130VAC/DC..5..48VAC/DC)
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) (Class 0.2 Optional) Class 1(Active), Class 2 (Reactive)
Battery Backup
Supercap
Real Time Clock
1min/month (30ppm)
Internal Memory
8MB
MMC
up to 2GB
Isolation
3.7kV
Ethernet
RJ45 10/100Mbit/s
USB
Yes (2400-115200 b/s)
RS232/RS485
N/A (optional 2400-115200 b/s)
Weight
600g
Certification
UL, CSA, ROHS
Factory Pack Qty
1
EU Directives
Degree on electrical equipment designed for use within certain voltage limits URLRS 53/00 (Directive 73/23/EEC on low voltage): SIST EN 61010-1:2002
Safety Requirement for electrical equipment for measurement, control and laboratory use, part1 : general requirement
Decree on electromagnetic Compatibility (EMC) URLRS 61/00 (Directive 89/336/EEC on electromagnetic compatibility): SIST EN 61036 item 4.5: 1998 Meters for active energy (class 1 and 2)
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP52 (IP00 for terminals) in compliance with SIST EN 60529:1997
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
User Manual
Iskra Doo MC330 S 110V SUDNNP, Panel Mount Mutifunction Meter, Class 1, 110VAC 50/60Hz Measurement, Universal 20-300VDC, 48-265VAC Aux, RS485 Comms, Internal Logger
Internal 8MB Logger
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 500 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
Optional RS 232/RS 485 communication up to 115,200 bit/s
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Internal Logger
Measurement of instantaneous values of more than 60 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.). Includes Harmonics
Accuracy class 1
Measurement of 20 minimal and maximal values in different time periods
Optional dual tariff inputs and pulse or relay outputs
Wide frequency range from 16 Hz to 400 Hz
RS 232/RS 485 communication up to 115,200 bit/s or Ethernet communication
MODBUS communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal or AC power supply
Graphic LCD 128 x 64 dots with illumination
Automatic range of nominal current up to 5 A and nominal voltage up to 600 V
Multilingual support
User-friendly PC MiQen software
Specification
Iskra Doo Part Number
MC330 S 110V SUDNNP
Functions
Power Quality Meter, Energy Meter
Supply Voltage
Universal 20-300VDC, 48-276VAC
Nominal Measurement Range
110VAC L-N, 5 Amp
Maximum Measurement Range
132V L-N, 12.5 Amp
Alarm
Optional 2 x Relay Output
Tariff Input
Optional 2 x
Analogue Output
Optional 2 x
Accuracy
Class 1 (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Internal Logger
Yes (8MB)
RS232/RS485
N/A Optional
CT Terminations
Through Hole CT
Environmental
IP54
Weight
500g
Certification
UL, CSA, ROHS
Factory Pack Qty
1
EU Directives
Degree on electrical equipment designed for use within certain voltage limits URLRS 53/00 (Directive 73/23/EEC on low voltage): SIST EN 61010-1:2002
Safety Requirement for electrical equipment for measurement, control and laboratory use, part1 : general requirement
Decree on electromagnetic Compatibility (EMC) URLRS 61/00 (Directive 89/336/EEC on electromagnetic compatibility): SIST EN 61036 item 4.5: 1998 Meters for active energy (class 1 and 2)
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP52 (IP00 for terminals) in compliance with SIST EN 60529:1997
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
User Manual
Iskra Doo MC740 S SFENC, Panel Mount Measuring Center 3 Phase, Class 0.5 50-500 L-L 50/60Hz Measurement, 240VAC Supply, Ethernet & USB Comms, w/ Supercap
Smart Meter
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 750 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
Optional RS 232/RS 485 communication up to 115,200 bit/s or Ethernet communication
Usage
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 140 quantities (U, I, P, Q, S, PF, PA, f, f, MD, energy, energy price by tariffs, etc.).
Accuracy class 0.5 or 0.2 (on demand)
Measurement of 40 minimal and maximal values in different time periods
32 adjustable alarms
Wide frequency range from 16 Hz to 400 Hz
RS 232/RS 485 communication up to 115,200 bit/s or Ethernet communication
MODBUS and DNP3 communication protocol
MMC memory card for setting and upgrading the meter
Up to 4 inputs or outputs (analogue outputs, pulse outputs, alarm outputs, tariff inputs)
Universal or AC power supply
Graphic LCD 128 x 64 dots with illumination
Automatic range of nominal current up to 5 A and nominal voltage up to 750 V
Adjustable tariff clock, display of electric energy consumption in optional currency
Multilingual support
User-friendly PC MiQen software
128 samples in one period
Measurement of THD on Current or Voltage from 0 to 400%
Specification
Iskra Doo Part Number
MC740 S SFENC
Functions
Power Quality Meter, Energy Meter, Power Transducer, Network Analyser
Supply Voltage
240VAC < 5VA 40-70Hz
Nominal Measurement Range
50-500V L-N, 5 Amp 50/60Hz
Maximum Measurement Range
800V L-N, 12.5 Amp
Alarm
N/A (Optional 4 Relays, 32 Alarms, 4 Groups)
Analogue Output
N/A (Optional 4 x 20mA)
Digital Input
N/A (Optional 4 x 230VAC/DC,75..130VAC/DC..5..48VAC/DC)
Pulse Output
N/A (Optional)
Pulse Input
N/A (Optional)
Bistable Switch/Latching Relay Alarm
N/A (Optional)
Status (Watchdog) Output
N/A (Optional)
Tariff Input
N/A (Optional 4 x 230VAC/DC,75..130VAC/DC..5..48VAC/DC)
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) (Class 0.2 Optional) Class 1(Active), Class 2 (Reactive)
Battery Backup
Supercap
Real Time Clock
1min/month (30ppm)
Internal Memory
8MB
MMC
up to 2GB
Isolation
3.7kV
Ethernet
RJ45 10/100Mbit/s
USB
Yes (2400-115200 b/s)
RS232/RS485
N/A (optional 2400-115200 b/s)
Weight
600g
Certification
UL, CSA, ROHS
Factory Pack Qty
1
EU Directives
Degree on electrical equipment designed for use within certain voltage limits URLRS 53/00 (Directive 73/23/EEC on low voltage): SIST EN 61010-1:2002
Safety Requirement for electrical equipment for measurement, control and laboratory use, part1 : general requirement
Decree on electromagnetic Compatibility (EMC) URLRS 61/00 (Directive 89/336/EEC on electromagnetic compatibility): SIST EN 61036 item 4.5: 1998 Meters for active energy (class 1 and 2)
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP52 (IP00 for terminals) in compliance with SIST EN 60529:1997
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
User Manual
Iskra Doo MT440-SSUDAAMNA, Multifunction Power Transducer, Class 0.5, 4 Wire, 600V L-N, 1/5/10Amp AC Input 50/60Hz, 24-300VDC or 40-276VAC Aux Input, 2 Programmable analogue outputs, 1 relay output, RS485 & USB Comms
Class 0.5 (EN 60688)
USB Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 50 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy class 0.5
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Specification
Iskra Doo Part Number
MT440-SSUDAAMNA
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
600V L-N, 1/5/10 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
1 x Relay Output
Tariff Input
N/A
Output(s)
2 x Analogue
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Comms
USB (standard) RS232 2400-115200 b/s (RS485 Optional)
Weight
370g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
MiQen Setting Software
MIPACK Programmer
Iskra Doo MC750 S SERNNT, Panel Mount Network Recorder 3 Phase, 4 Wire, Class 0.5, 50..500VAC 5Amp AC 50/60Hz AC 16-400Hz, 140 Parameter (U, I, P, Q, S, PF, PA, f, φ, THD, MD, energy, energy cost by tariffs...) 240VAC Aux Supply, RS232/RS485
Smart Meter
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 750 V L-N 50/60Hz
Adjustable tariff clock, display of electric energy consumption in optional currency
Optional RS 232/RS 485 communication up to 115,200 bit/s or Ethernet communication
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 140 quantities (U, I, P, Q, S, PF, PA, f, f, MD, energy, energy price by tariffs, etc.).
Accuracy class 0.5 or 0.2 (on demand)
Measurement of 40 minimal and maximal values in different time periods
Optional 32 adjustable alarms
Optional wide frequency range from 16 Hz to 400 Hz
Optional RS 232/RS 485 communication up to 115,200 bit/s or Ethernet communication
Optional MODBUS and DNP3 communication protocol
MMC memory card for setting and upgrading the meter
Up to 4 inputs or outputs (analogue outputs, pulse outputs, alarm outputs, tariff inputs)
Universal or AC power supply
Graphic LCD 128 x 64 dots with illumination
Automatic range of nominal current up to 5 A and nominal voltage up to 750 V
Adjustable tariff clock, display of electric energy consumption in optional currency
Multilingual support
User-friendly PC MiQen software
128 samples in one period
Measurement of THD on Current or Voltage from 0 to 400%
Specification
Iskra Doo Part Number
MC750 S SERNNT
Functions
Power Quality Meter, Energy Meter, Power Transducer, Network Recorder/Analyser
Supply Voltage
240VAC < 5VA
Nominal Measurement Range
500V L-N, 5 Amp 50/60Hz
Maximum Measurement Range
750V L-N, 12.5 Amp 50/60Hz
Alarm
N/A (Optional 4 Relays, 32 Alarms, 4 Groups)
Analogue Output
N/A (Optional 4 x 20mA)
Digital Input
N/A (Optional 4 x 230VAC/DC,75..130VAC/DC..5..48VAC/DC)
Pulse Output
N/A (Optional)
Pulse Input
N/A (Optional)
Bistable Switch/Latching Relay Alarm
N/A (Optional)
Status (Watchdog) Output
N/A (Optional)
Tariff Input
N/A (Optional 4 x 230VAC/DC,75..130VAC/DC..5..48VAC/DC)
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) (Class 0.2 Optional) Class 1(Active), Class 2 (Reactive)
Battery Backup
Supercap
Real Time Clock
1min/month (30ppm)
Internal Memory
8MB
MMC
up to 512MB
Isolation
3.7kV
Ethernet
Optional (RJ45 10/100Mbit/s)
USB
Yes (2400-115200 b/s)
RS232/RS485
2400-115200 b/s
Weight
600g
Certification
UL, CSA, ROHS
Factory Pack Qty
1
EU Directives
Degree on electrical equipment designed for use within certain voltage limits URLRS 53/00 (Directive 73/23/EEC on low voltage): SIST EN 61010-1:2002
Safety Requirement for electrical equipment for measurement, control and laboratory use, part1 : general requirement
Decree on electromagnetic Compatibility (EMC) URLRS 61/00 (Directive 89/336/EEC on electromagnetic compatibility): SIST EN 61036 item 4.5: 1998 Meters for active energy (class 1 and 2)
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP52 (IP00 for terminals) in compliance with SIST EN 60529:1997
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
User Manual
Iskra Doo MC740 S SURAC Series 3 Phase Measuring Centre
Smart Meter
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 750 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
Optional RS 232/RS 485 communication up to 115,200 bit/s or Ethernet communication
Usage
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 140 quantities (U, I, P, Q, S, PF, PA, f, f, MD, THD, energy, energy price by tariffs, etc.).
Accuracy class 0.5 or 0.2 (on demand)
Measurement of 40 minimal and maximal values in different time periods
32 adjustable alarms
Wide frequency range from 16 Hz to 400 Hz
RS 232/RS 485 communication up to 115,200 bit/s or Ethernet communication
MODBUS and DNP3 communication protocol
MMC memory card for setting and upgrading the meter
Up to 4 inputs or outputs (analogue outputs, pulse outputs, alarm outputs, tariff inputs)
Universal or AC power supply
Graphic LCD 128 x 64 dots with illumination
Automatic range of nominal current up to 5 A and nominal voltage up to 750 V
Adjustable tariff clock, display of electric energy consumption in optional currency
Multilingual support
User-friendly PC MiQen software
128 samples in one period
Measurement of THD on Current or Voltage from 0 to 400%
Specification
Iskra Doo Part Number
MC740 S SURAC
Functions
Power Quality Meter, Energy Meter, Power Transducer, Network Analyser
Supply Voltage
48-276VAC < 5VA 40-70Hz, 20-300VDC
Nominal Measurement Range
500V L-N, 5 Amp
Maximum Measurement Range
800V L-N, 12.5 Amp
Alarm
N/A (Optional 4 Relays, 32 Alarms, 4 Groups)
Analogue Output
N/A (Optional 4 x 20mA)
Digital Input
N/A (Optional 4 x 230VAC/DC,75..130VAC/DC..5..48VAC/DC)
Pulse Output
N/A (Optional)
Pulse Input
N/A (Optional)
Bistable Switch/Latching Relay Alarm
N/A (Optional)
Status (Watchdog) Output
N/A (Optional)
Tariff Input
N/A (Optional 4 x 230VAC/DC,75..130VAC/DC..5..48VAC/DC)
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) (Class 0.2 Optional) Class 1(Active), Class 2 (Reactive)
Battery Backup
Supercap
Real Time Clock
1min/month (30ppm)
Internal Memory
8MB
MMC
N/A (MC750,MC760 optional up to 512MB)
Isolation
3.7kV
Ethernet
Opitonal (RJ45 10/100Mbit/s)
USB
Yes
RS232/RS485
Yes 2400-115200 b/s
CT Termination
Through Hole CT
Weight
600g
Certification
UL, CSA, ROHS
Factory Pack Qty
1
EU Directives
Degree on electrical equipment designed for use within certain voltage limits URLRS 53/00 (Directive 73/23/EEC on low voltage): SIST EN 61010-1:2002
Safety Requirement for electrical equipment for measurement, control and laboratory use, part1 : general requirement
Decree on electromagnetic Compatibility (EMC) URLRS 61/00 (Directive 89/336/EEC on electromagnetic compatibility): SIST EN 61036 item 4.5: 1998 Meters for active energy (class 1 and 2)
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP52 (IP00 for terminals) in compliance with SIST EN 60529:1997
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
User Manual
Iskra Doo MT440-SSUDAANNA, Multifunction Power Transducer, Class 0.5, 4 Wire, 600V L-N, 1/5/10Amp AC Input 50/60Hz, 24-300VDC or 40-276VAC Aux Input, 2 Programmable analogue outputs, RS485 & USB Comms
Class 0.5 (EN 60688)
USB Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 50 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy class 0.5
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Specification
Iskra Doo Part Number
MT440-SSUDAANNA
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
600V L-N, 1/5/10 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
N/A
Tariff Input
N/A
Output(s)
2 x Analogue
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Comms
USB (standard) RS232 2400-115200 b/s (RS485 Optional)
Weight
370g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
MiQen Setting Software
MIPACK Programmer
Iskra Doo MC740 S SUENC Series 3 Phase Measuring Center
Smart Power Meter
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 750 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
Optional RS 232/RS 485 communication up to 115,200 bit/s or Ethernet communication
Usage
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 140 quantities (U, I, P, Q, S, PF, PA, f, f, MD, energy, energy price by tariffs, etc.).
Accuracy class 0.5 or 0.2 (on demand)
Measurement of 40 minimal and maximal values in different time periods
32 adjustable alarms
Wide frequency range from 16 Hz to 400 Hz
RS 232/RS 485 communication up to 115,200 bit/s or Ethernet communication
MODBUS and DNP3 communication protocol
MMC memory card for setting and upgrading the meter
Up to 4 inputs or outputs (analogue outputs, pulse outputs, alarm outputs, tariff inputs)
Universal or AC power supply
Graphic LCD 128 x 64 dots with illumination
Automatic range of nominal current up to 5 A and nominal voltage up to 750 V
Adjustable tariff clock, display of electric energy consumption in optional currency
Multilingual support
User-friendly PC MiQen software
128 samples in one period
Measurement of THD on Current or Voltage from 0 to 400%
Specification
Iskra Doo Part Number
MC740 S SUENC
Functions
Power Quality Meter, Energy Meter, Power Transducer, Network Analyser
Supply Voltage
Universal 48-240VAC 40-70Hz, 20-300VDC, < 5VA
Nominal Measurement Range
50-500V L-N, 5 Amp 50/60Hz
Maximum Measurement Range
750V L-N, 12.5 Amp
Alarm
N/A (Optional 4 Relays, 32 Alarms, 4 Groups)
Analogue Output
N/A (Optional 4 x 20mA)
Digital Input
N/A (Optional 4 x 230VAC/DC,75..130VAC/DC..5..48VAC/DC)
Pulse Output
N/A (Optional)
Pulse Input
N/A (Optional)
Bistable Switch/Latching Relay Alarm
N/A (Optional)
Status (Watchdog) Output
N/A (Optional)
Tariff Input
N/A (Optional 4 x 230VAC/DC,75..130VAC/DC..5..48VAC/DC)
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) (Class 0.2 Optional) Class 1(Active), Class 2 (Reactive)
Battery Backup
Supercap
Real Time Clock
1min/month (30ppm)
Internal Memory
8MB
MMC
up to 2GB
Isolation
3.7kV
Ethernet
RJ45 10/100Mbit/s
USB
Yes (2400-115200 b/s)
RS232/RS485
N/A (optional 2400-115200 b/s)
Weight
600g
Certification
UL, CSA, ROHS
Factory Pack Qty
1
EU Directives
Degree on electrical equipment designed for use within certain voltage limits URLRS 53/00 (Directive 73/23/EEC on low voltage): SIST EN 61010-1:2002
Safety Requirement for electrical equipment for measurement, control and laboratory use, part1 : general requirement
Decree on electromagnetic Compatibility (EMC) URLRS 61/00 (Directive 89/336/EEC on electromagnetic compatibility): SIST EN 61036 item 4.5: 1998 Meters for active energy (class 1 and 2)
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP52 (IP00 for terminals) in compliance with SIST EN 60529:1997
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
User Manual