Iskra Doo MT440-SSUDAAMAA, Multifunction Power Transducer, Class 0.5, 4 Wire, 600V 1/5/10Amp AC Input 50/60Hz, 24-300VDC or 40-276VAC Aux Input, 3 Programmable Analogue Outputs, 1 relay output, RS485 + USB Comms
Class 0.5 (EN 60688)
USB Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 50 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy class 0.5
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Specification
Iskra Doo Part Number
MT440-SSUSAAMAA
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
600V L-N, 1/5/10 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
1 x Relay Output
Tariff Input
N/A
Output
3 x Analogue
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Comms
USB (standard) RS485 2400-115200 b/s (RS232 Optional)
Weight
370g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
MiQen Setting Software
MIPACK Programmer
Iskra Doo MT440-SSUDAAAAA, Multifunction Power Transducer, Class 0.5, 4 Wire, 600V 1/5/10Amp AC Input 50/60Hz, 24-300VDC or 40-276VAC Aux Input, 4 Programmable Analogue Outputs, RS485 + USB Comms
Class 0.5 (EN 60688)
USB Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 50 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy class 0.5
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Specification
Iskra Doo Part Number
MT440-SSUDAAAAA
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
600V L-N, 1/5/10 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
N/A
Tariff Input
N/A
Output
4 x Analogue
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Comms
USB (standard) RS485 2400-115200 b/s (RS232 Optional)
Weight
370g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
MiQen Setting Software
MIPACK Programmer
Iskra Doo MT440-SSUSAAAAA, Multifunction Power Transducer, Class 0.5, 4 Wire, 600V 1/5/10Amp AC Input 50/60Hz, 24-300VDC or 40-276VAC Aux Input, 4 Programmable Analogue Outputs, RS232 + USB Comms
Class 0.5 (EN 60688)
USB Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 50 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy class 0.5
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Specification
Iskra Doo Part Number
MT440-SSUSAAAAA
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
600V L-N, 1/5/10 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
N/A
Tariff Input
N/A
Output
4 x Analogue
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Comms
USB (standard) RS232 9RS485 Optional)
Weight
370g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
MiQen Setting Software
MIPACK Programmer
Iskra Doo MT550-SSHFNAASS (DIN), Multifunction Power Transducer, Class 0.1, 4 Wire, 50-500V L-N, 5A AC Input 16-400Hz, 70-300VDC or 80-276VAC Aux Input, 2 Programmable analogue outputs, 2 Pulse Outputs, USB, Ethernet, RS485 Comms
Class 0.1 Active, Class 0.2 Reactive (EN 60688)
RS485 Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 140 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy Class 0.5s Active, Class 0.2 Reactive (EN 60688), Class 0.1 on Comms
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Optional Remote Display Support
Specification
Iskra Doo Part Number
MT550-SSHFNAASS (DIN)
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
500V L-N, 5 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
N/A
Tariff Input
N/A
Output(s)
2 x Analogue
Accuracy
Class 0.2 (I,U,F,PF,θ,THD) Class 0.1(Active), Class 0.2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Terminations
EU Style Clamp Terminals
Isolation
3.5kV
Comms
USB (standard) RS232 2400-115200 b/s (RS485 Optional)
Weight
900g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
MiQen Setting Software
Iskra Doo UMT540-HSHFNAAAM, Multifunction Power Transducer, Class 0.5S, 4 Wire, 600V L-N, 5A AC Input 50/60Hz, 24-300VDC or 40-276VAC Aux Input, 3 Programmable analogue outputs, 1 Relay Alarm Output, USB, Ethernet, RS485 Comms
(U)MT version = Ring type terminal block
Class 0.5S Active, Class 0.2 Reactive (EN 60688) , Class 0.1 on Comms
RS485 Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 140 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy Class 0.5s Active, Class 0.2 Reactive (EN 60688), Class 0.1 on Comms
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Optional Remote Display Support
Specification
Iskra Doo Part Number
UMT540-HSHFNAAAM
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
600V L-N, 5 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
N/A
Tariff Input
N/A
Output(s)
3 x Analogue, 1 x Relay Alarm
Accuracy
Class 0.2 (I,U,F,PF,θ,THD) Class 0.5s(Active), Class 0.2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Terminations
Ring Type Terminal Block
Isolation
3.5kV
Comms
USB (standard) RS232 2400-115200 b/s (RS485 Optional)
Weight
900g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
MiQen Setting Software
Iskra Doo MT540-HSHFNAAAA, Multifunction Power Transducer, Class 0.5S, 4 Wire, 600V L-N, 5A AC Input 50/60Hz, 24-300VDC or 40-276VAC Aux Input, 2 Programmable analogue outputs, USB, Ethernet, RS485 Comms
Class 0.5S Active, Class 0.2 Reactive (EN 60688) , Class 0.2 on Comms
RS485 Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 140 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy Class 0.5s Active, Class 0.2 Reactive (EN 60688), Class 0.1 on Comms
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Optional Remote Display Support
Specification
Iskra Doo Part Number
MT540-HSHFNAAAA
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
600V L-N, 5 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
N/A
Tariff Input
N/A
Output(s)
4 x Analogue
Accuracy
Class 0.2 (I,U,F,PF,θ,THD) Class 0.5s(Active), Class 0.2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Terminations
EU Style Clamp Terminals
Isolation
3.5kV
Comms
USB (standard) RS232 2400-115200 b/s (RS485 Optional)
Weight
900g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
MiQen Setting Software
Iskra Doo UMT540-HSHFNAAAA, Multifunction Power Transducer, Class 0.5S, 4 Wire, 600V L-N, 5A AC Input 50/60Hz, 24-300VDC or 40-276VAC Aux Input, 4 Programmable analogue outputs, USB, Ethernet, RS485 Comms
(U)MT version = Ring type terminal block
Class 0.5S Active, Class 0.2 Reactive (EN 60688) , Class 0.1 on Comms
RS485 Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 140 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy Class 0.5s Active, Class 0.2 Reactive (EN 60688), Class 0.1 on Comms
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Optional Remote Display Support
Specification
Iskra Doo Part Number
UMT540-HSHFNAAAA
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
600V L-N, 5 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
N/A
Tariff Input
N/A
Output(s)
4 x Analogue
Accuracy
Class 0.2 (I,U,F,PF,θ,THD) Class 0.5s(Active), Class 0.2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Terminations
Ring Type Terminal Block
Isolation
3.5kV
Comms
USB (standard) RS232 2400-115200 b/s (RS485 Optional)
Weight
900g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
MiQen Setting Software