Risbabh EM94-Z-V3-M-M, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 201-1000VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,10-60V AC/DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 201-1000VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
4 x DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
10-60VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V3-M-M
Functions
kWh Meter, Energy Meter
Supply Voltage
10-60VAC/DC
Nominal Measurement Range
201-1000VDC
Maximum Measurement Range
201-1000VDC
Display
4 Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Risbabh EM94-Z-V1-M-M, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input,10-60VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,10-60V AC/DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
4 x DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
10-60VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V1-M-M
Functions
kWh Meter, Energy Meter
Supply Voltage
10-60VAC/DC
Nominal Measurement Range
60-300VDC
Maximum Measurement Range
60-300VDC
Display
4 Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Crydom ED06E5, EMR plug in Solid State Relay, 18-36VAC control, 5 Amp 1-48V DC output
Features
Ratings 5 Amp @ 60/80VDC
Plug in EMR relay style
Motor controller rated
Mosfet output for reliable DC switching
Multiple modules can be wired in parallel for higher currents
UL/CSA/VDE Approved, CE Compliant to EN60950-1
EMC compliant to Level 3
Epoxy free design
Spec
Crydom Part Number
ED06E5
Switching Type
DC Load
ROHS
Yes (Details)
Control Voltage
18-36VAC
Load Current
5 Amp DC
Surge Capability (10ms)
60 Amp DC
Special Feature
Plug in EMR style
Mounting Style
EMR Base
Load Voltage Range
1 - 48VDC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
11g
Factory Pack Qty
20
Datasheet
Product Datasheet
Socket
DRSED
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
E62.E58-103D10, 10uF, 40x58mm Heavy Duty AC Film Power Capacitor w/Stud -40 to 85 °C 200,000 hrs, 1000VDC/640VAC
Characteristics and utility
10uF 1000VDC/640VAC
Metalized Polypropylene Film
Connector type - M6 x 12mm Studs
M8 Stud mounting
Standards
IEC 60831-1/2
EN 60831-1/2
Specification
Electronicon Part Number
E62.E58-103D10
Technology
Metalized Polypropylene Film Capacitor
Dimensions
ø40x58mm
Mounting
M8 Stud
Standards
IEC 60831-1/2, EN 60831-1/2
Voltage
1000VDC/640VAC
Operating Temperature Range
-40 to 85 °C
Capacitance
10uF
Tolerance On Capacitance
+10 / -10%
Lifetime
200,000 Hours @ 85 °C (Statistical Life)
Termination Style
Faston
Unit Weight
0.07kg
Factory Pack Quantity
21 (MOQ = 105)
Datasheet
Product Datasheet
Trent 200BBF Series 690V, 200 Amp aR Semiconductor I²t Fuse BS88 Style 200kA Breaking
Features
British Standard Fuse Links Package
Wide Range of I²t
Ratings up to 1000 Amp
Busbar or Standoff Mounting
IEC Standard 60269.1 AND 4
690 V Voltage Rating complying with IEC 33
Applications
Protection of High Powered Semiconductors according to I²t
Short Circuit Protection
DC or AC Motor I²t Protection
Battery Fuse
Specification
Trent Part Number
200BBF
Fuse Type
I²t aR Class
Nominal Voltage
690VAC @ 50Hz
I²t Rating
Nominal Current (RMS + DC)
200 Amp
Tested Breaking Capacity
200kA @ 690VAC
Dimensions
79.4 x 24 x 110mm
Hole Centers
75.2 x 93.6mm
Mounting Style
Busbar or Panel Mount with Standoff
Operating Temperature Range
-40°C / 125°C
Watt Loss
62W
Termination Style
M6
Unit Weight
400g
Factory Pack Qty
10
Datasheet
Product Datasheet
Cross Reference Chart
SDM630MCT-LORAWAN-MID-AS923, DIN Rail Mount kWh Meter, 3 Phase, 240VAC aux, Class 1, 1/5 Amp CT Connect, w/ 2 x pulse outputs and LoRaWaN AS923 Wireless Comms
1/5 Amp CT Input
LoRaWaN AS923
Optional Mbus Model available
True RMS values of currents and voltages
1 x Configurable Pule Output (via Display Menu or Modbus)
1 x Fixed Pulse Output (1000imp/kwh)
The meter is intended for measuring, and monitoring single-phase or three phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
Accuracy class 1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM630MCT-LORAWAN-MID-AS923
Functions
Three Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
1/5 Amp
Pulse Output
2 x Passive, (1 x Configurable 60/100/200ms)
Tariff Input
N/A
Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
Comms
LoRaWaN AS923
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Setup Video - CT Ratio Unlock
Modbus Utility
EEM Meter Setting Software Utility
GIC Controls, LA25F1 90-264VAC, Hours Run Meter 90-264VAC, 48x48mm Panel Mount
Features
IP40 (IP66 with Gasket)
90-264VAC
6 Digit Display
99999.9 Hours
48x48mm Panel Mount
Rectangular Cutout
UL Approved
Datasheet
Product Datasheet
GIC Controls, LD17F1 10-80VDC, Hours Run Meter 10-80VAC, 48x48mm Panel Mount
Features
IP40 (IP66 with Gasket)
10-80VDC
6 Digit Display
99999.9 Hours
48x48mm Panel Mount
Rectangular Cutout
UL Approved
Datasheet
Product Datasheet
Trent I²t Semiconductor Fuse, NBR-FWP-600A 700V AC/DC, Semiconductor Fuse, 600 Amp, 700VAC/DC, Round Barrel 7.09 x 2.0 x 2.5 Inches. Clearing I2t 250kA, Breaking Capacity 200kAand Microswitch
Features
Square Body DIN 43 653
Wide Range of I²t
Ratings up to 2000 Amp
Busbar or Fuse Holder Mounted
IEC Standard 60269.1 AND 4
690 V Voltage Rating complying with IEC 33
Fuse Blown Indicator and Microswitch
Applications
Protection of High Powered Semiconductors according to I²t
Short Circuit Protection
DC or AC Motor I²t Protection
Battery Fuse
Specification
Trent Part Number
NBR-FWP-600A 700V AC/DC
Fuse Type
I²t AR Class
Nominal Voltage
700VAC @ 50Hz
I²t Rating (660V)
250000A²/s
Nominal Current (RMS + DC)
600 Amp
Tested Breaking Capacity
200kA @ 700VAC/DC
Dimensions
138 x 61 x 50mm
Hole Centers
108mm +
Mounting Style
Busbar or Panel Mount with Standoff
Operating Temperature Range
-40°C / 125°C
Watts Dissipation
75W
Termination Style
M10
Unit Weight
350g
Factory Pack Qty
10
Datasheet
Product Datasheet