LEM ART-B22-D125-SP3 + AI-PMUL - 3 Pcs, 3 Phase Rogowski Coil Set, Class 1, User Selectable 0.333v, 0.166v, True RMS 4-20mA, 0-20mA, 0-10V, 0-5V Outputs, Sensitivity, and Measurement Range, 12.5cm Diameter
The universal Rogowski coil integrator AI-PMUL complements LEM’s flexible clip-around coil ART and ARU range. The design is based on digital processing to give combined dynamic range, accuracy and versatility of use. It offers a wide range of output signals both RMS and instantaneous. AI-PMUL is DIN rail mounted and can be stacked for multiphase application without spacing thanks to its low power dissipation.
Input signal
Accuracy Class 1 (IEC 61869-2) [1].
Linearity error ≤ 0.10 %. Protection degree IP2X.
35 mm DIN rail mounted.
Push-in terminals.
4 selectable true RMS output signals: 0…20 mA, 4…20 mA, 0…5 V, 0…10 V.
2 selectable instantaneous output signals: 225 mV, 333 mV.
6 selectable sensitivities depending on Rogowski coil: 22.5, 70, 80, 85, 100, 120 mV/kA at 50 Hz.
12 selectable ranges: 100, 200, 300, 400, 500, 600, 800, 1000, 1500, 2000, 4000, 5000 A.
Ambient operating temperature −25...+70 °C.
Advantages
Compact design for DIN rail assembly
High accuracy Class 1 (IEC 61869-2)
Setup by user via Select / Edit buttons
Clear status indication via bi-color led
Applications
MV/LV substations on LV side: Transformer Condition Monitoring
Power metering: current measurement for active power calculation
Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation
Power quality monitoring: electrical loads and distribution system equipment
Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault
Remote Terminal Units (RTU)
Phasor Measurement Units (PMU)
Standards
IEC 61010-1: 2010
UL
EMC: IEC 61326-1:2012
Options
Cross Power Plug-in: side contacts to stack up to 3 Integrator modules and use only one power supply.
Specification
LEM Part Number
ART-B22-D125-SP3 + AI-PMUL - 3 Pcs
Function
3 Phase AC Current Measurement
Measuring Range
Selectable 5000,4000,2000,1500,1000,800,600,500,400,300,200,100Amp
Sensitivity
Selectable 22.5,70,80,85,100,120mV/kA @ 50 Hz
Output
Selectable; Signal Conditioned True RMS 0-20mA, True RMS 4-20mA, True RMS 5V, True RMS 10V or 225mV, 333mV Direct Output (1 Amp output coming soon)
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
10-32VDC
Accuracy
1% from 25 to 5000 Amp
Current Consumption
100mA (max)
Dimensions
100mm x 78mm x 15mm (Integrator), 12.5cm Diameter (Coils)
Mounting
Din Rail Mount
Integrator to Coil cable
3M Twisted and Screened
Integrator to Meter cable
User Supplied Shielded cable 1.5mm sqr, up to 6m long
Operating Temperature
-25°C - 70°C
Storage Temperature
-45°C to 80°C
Isolation (50Hz, 1 min)
1.5kV
True RMS Response Time
160-190ms
Termination Style
Push-in for 1.5mm sqr wire
Weight
58g
Factory Pack Qty
1
Certifications
UL, ROHS
Datasheet
AI-PMUL Datasheet
ART Series Datasheet
Application Notes
User Notice
1) The Rogowski coil can measure any primary current as there is no saturation effect.
2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts)
3) Frequency bandwidth and phase shift modelling schematic can be provided on request.
4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5) Considering a primary conductor of at least ⌀ 15 mm, perpendicular and in contact with the Rogowski coil.
6) Considering an external conductor of at least ⌀ 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.
Fastron Electronics SCT-F50-300, 0.333V, 300Amp measurement Split Core CT's
Features
Quick Release Split Core System
Cable Mount
0.333V Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Fastron Part Number
SCT-F50-300
Technology
Split Core AC Current Transformer
Ratio
300/0.333V
Aperture Size
ø 50 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
0.333V (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
300Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
300g
Factory Pack Qty
9
Â
Datasheet
Product Datasheet
Stocked Split Core CT's Listing
Application Notes
Installation Guide
Types of Current Transformers - Blog
Cable Losses and CT's
High Accuracy or High Burden Requirements for CT's
LEM ART-B22-D175-SP3 + AI-PMUL, Single Phase Rogowski Coil Set, Class 1, User Selectable 0.333v, 0.166v, True RMS 4-20mA, 0-20mA, 0-10V, 0-5V Outputs, Sensitivity, and Measurement Range, 12.5cm Diameter
The universal Rogowski coil integrator AI-PMUL complements LEM’s flexible clip-around coil ART and ARU range. The design is based on digital processing to give combined dynamic range, accuracy and versatility of use. It offers a wide range of output signals both RMS and instantaneous. AI-PMUL is DIN rail mounted and can be stacked for multiphase application without spacing thanks to its low power dissipation.
Input signal
Accuracy Class 1 (IEC 61869-2) [1].
Linearity error ≤ 0.10 %. Protection degree IP2X.
35 mm DIN rail mounted.
Push-in terminals.
4 selectable true RMS output signals: 0…20 mA, 4…20 mA, 0…5 V, 0…10 V.
2 selectable instantaneous output signals: 225 mV, 333 mV.
6 selectable sensitivities depending on Rogowski coil: 22.5, 70, 80, 85, 100, 120 mV/kA at 50 Hz.
12 selectable ranges: 100, 200, 300, 400, 500, 600, 800, 1000, 1500, 2000, 4000, 5000 A.
Ambient operating temperature −25...+70 °C.
Advantages
Compact design for DIN rail assembly
High accuracy Class 1 (IEC 61869-2)
Setup by user via Select / Edit buttons
Clear status indication via bi-color led
Applications
MV/LV substations on LV side: Transformer Condition Monitoring
Power metering: current measurement for active power calculation
Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation
Power quality monitoring: electrical loads and distribution system equipment
Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault
Remote Terminal Units (RTU)
Phasor Measurement Units (PMU)
Standards
IEC 61010-1: 2010
UL
EMC: IEC 61326-1:2012
Options
Cross Power Plug-in: side contacts to stack up to 3 Integrator modules and use only one power supply.
Specification
LEM Part Number
AI-PMUL + ART-B22-D175
Function
Single Phase AC Current Measurement
Measuring Range
Selectable 5000,4000,2000,1500,1000,800,600,500,400,300,200,100Amp
Sensitivity
Selectable 22.5,70,80,85,100,120mV/kA @ 50 Hz
Output
Selectable; Signal Conditioned True RMS 0-20mA, True RMS 4-20mA, True RMS 5V, True RMS 10V or 225mV, 333mV Direct Output (1 Amp output coming soon)
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
10-32VDC
Accuracy
1% from 25 to 5000 Amp
Current Consumption
100mA (max)
Dimensions
100mm x 78mm x 15mm (Integrator), 12.5cm Diameter (Coils)
Mounting
Din Rail Mount
Integrator to Coil cable
3M Twisted and Screened
Integrator to Meter cable
User Supplied Shielded cable 1.5mm sqr, up to 6m long
Operating Temperature
-25°C - 70°C
Storage Temperature
-45°C to 80°C
Isolation (50Hz, 1 min)
1.5kV
True RMS Response Time
160-190ms
Termination Style
Push-in for 1.5mm sqr wire
Weight
58g
Factory Pack Qty
1
Certifications
UL, ROHS
Datasheet
AI-PMUL Datasheet
ART Series Datasheet
Application Notes
User Notice
1) The Rogowski coil can measure any primary current as there is no saturation effect.
2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts)
3) Frequency bandwidth and phase shift modelling schematic can be provided on request.
4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5) Considering a primary conductor of at least ⌀ 15 mm, perpendicular and in contact with the Rogowski coil.
6) Considering an external conductor of at least ⌀ 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.
RCS-1800-3000 Three-Phase Flexible Current Sensor System (Rogowski Coils):
The RCS-1800 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-1800 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Suitable Alternative to Solar Edge CTRC-07500-3000
Specification
Magnelab Part Number
RCS-1800-3000
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
3000 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 3000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
6 Inch
Coil Circumference
18 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
LEM ART-B22-D125-SP3 + AI-P1A - 3 Pcs, 3 Phase Rogowski Coil Set, Class 1, 1 Amp AC, Sensitivity, and Measurement Range, 12.5cm Diameter, 3M integrator Cable
The universal Rogowski coil integrator AI-P1A complements LEM’s flexible clip-around coil ART and ARU range. The design is based on digital processing to give combined dynamic range, accuracy and versatility of use. It offers a wide range of output signals both RMS and instantaneous. AI-P1A is DIN rail mounted and can be stacked for multiphase application without spacing thanks to its low power dissipation.
Input signal
Accuracy Class 1 (IEC 61869-2) [1].
Linearity error ≤ 0.10 %. Protection degree IP2X.
35 mm DIN rail mounted.
Push-in terminals.
1 Amp instantaneous output.
6 selectable sensitivities depending on Rogowski coil: 22.5, 70, 80, 85, 100, 120 mV/kA at 50 Hz.
12 selectable ranges: 100, 200, 300, 400, 500, 600, 800, 1000, 1500, 2000, 4000, 5000 A.
Ambient operating temperature −25...+70 °C.
Advantages
Compact design for DIN rail assembly
High accuracy Class 1 (IEC 61869-2)
Setup by user via Select / Edit buttons
Clear status indication via bi-color led
Applications
MV/LV substations on LV side: Transformer Condition Monitoring
Power metering: current measurement for active power calculation
Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation
Power quality monitoring: electrical loads and distribution system equipment
Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault
Remote Terminal Units (RTU)
Phasor Measurement Units (PMU)
Standards
IEC 61010-1: 2010
UL
EMC: IEC 61326-1:2012
Options
Cross Power Plug-in: side contacts to stack up to 3 Integrator modules and use only one power supply.
Specification
LEM Part Number
ART-B22-D125-SP3 + AI-P1A - 3 Pcs
Function
3 Phase AC Current Measurement
Measuring Range
Selectable 5000,4000,2000,1500,1000,800,600,500,400,300,200,100Amp
Sensitivity
Selectable 22.5,70,80,85,100,120mV/kA @ 50 Hz
Output
1 Amp Instantaneous
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
10-32VDC
Accuracy
1% from 25 to 5000 Amp
Current Consumption
100mA (max)
Dimensions
100mm x 78mm x 15mm (Integrator), 12.5cm Diameter (Coils)
Mounting
Din Rail Mount
Integrator to Coil cable
3M Twisted and Screened
Integrator to Meter cable
User Supplied Shielded cable 1.5mm sqr, up to 6m long
Operating Temperature
-25°C - 70°C
Storage Temperature
-45°C to 80°C
Isolation (50Hz, 1 min)
1.5kV
True RMS Response Time
160-190ms
Termination Style
Push-in for 1.5mm sqr wire
Weight
1125g
Factory Pack Qty
1
Certifications
Â
UL, ROHS
Datasheet
AI-P1A Datasheet
ART Series Datasheet
Application Notes
User Notice
1) The Rogowski coil can measure any primary current as there is no saturation effect.
2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts)
3) Frequency bandwidth and phase shift modelling schematic can be provided on request.
4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5) Considering a primary conductor of at least ⌀ 15 mm, perpendicular and in contact with the Rogowski coil.
6) Considering an external conductor of at least ⌀ 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.
Â
Fastron Electronics SCT-F24-50, 50Amp/0.333V Measurement, Class 1 Split Core CT's
Features
Quick Release Split Core System
Cable Mount
333mV Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Fastron Part Number
SCT-F24-50
Technology
Split Core AC Current Transformer
Ratio
50/333mV
Aperture Size
ø 24 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
333mV (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
50Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Â
Datasheet
Product Datasheet
Application Notes
Installation Guide
Eastron SDM630MCT-MODBUS-MID-CL0.5 V2, DIN Rail Mount kWh Meter, 3 Phase, 240VAC aux, Class 0.5S, 1/5Amp Connect, w/ 2 x pulse outputs and RS485 Modbus RTU Comms, MID Approved
1/5 Amp CT Input
RS 485 communication up to 38,400 bit/s as standard
Optional Mbus Model available
True RMS values of currents and voltages
1 x Configurable Pule Output (via Display Menu or Modbus)
1 x Fixed Pulse Output (1000imp/kwh)
Â
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Â
Features :
Accuracy class 0.5S
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Part Number
SDM630MCT-MODBUS-MID-CL0.5 V2
Functions
Three Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
1/5Amp
Pulse Output
2 x Passive, (1 x Configurable 60/100/200ms)
Tariff Input
N/A
Accuracy
Class 0.5 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Â
Documents
Product Datasheet
User Manual
Modbus Protocol
Setup Video - CT Ratio Unlock
Alternatives
WM3-6 230DB
Modbus Utility
EEM Meter Setting Software Utility
Eastron SDM630MCT-MV, DIN Rail Mount kWh Meter, 3 Phase, 240VAC aux, Class 1, 0.333V CT Connect, w/ 2 x pulse outputs and RS485 Modbus RTU Comms, SAA Approved
0.333V CT Input
RS 485 communication up to 38,400 bit/s as standard
Optional Mbus Model available
True RMS values of currents and voltages
1 x Configurable Pule Output (via Display Menu or Modbus)
1 x Fixed Pulse Output (1000imp/kwh)
Â
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Â
Features :
Accuracy class 1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM630MCT-MV
Functions
Three Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
0.333V
Pulse Output
2 x Passive, (1 x Configurable 60/100/200ms)
Tariff Input
N/A
Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
150g
Certification
EN 61010-1 Installation Category III, CE, SAA220473
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Â
Documents
Product Datasheet
User Manual
Modbus Protocol
Setup Video - CT Ratio Unlock
Alternatives
WM3-6 230DB
Modbus Utility
EEM Meter Setting Software Utility
RCS-3605-VAR, 5 Amp Output, Class 1 Three Phase 500/1000/2500/5000\10000\25000\50000 Amp AC Measurement 12 Inch Diameter Rogowski Coils with Integrator Flexible Current Sensor System (Rogowski Coils):
The RCS-3605 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 5 Amp.
A 24VDC Power Supply is included to operate these coils. The RCS-3605 comes with 5 Amp integrator..
Included is an 36 inch circumference rope CT with Integrator, and power supply.
Magnelab Coils come with 10 year warranty
Â
Specification
Magnelab Part Number
RCS-3605-VAR
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
500/1000/2500/5000\10000\25000\50000 Amp RMS Selectable
Measurement Range
10% - 130% if Ipn
Output Range
0-5 Amp
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
24VDC
Accuracy
1% from 25 to 5000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
12 Inch
Coil Circumference
36 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
3500g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS-VAR Series Installation Guide
GIC Z2301N0G1FT00, Totalizer/Counter or HOUR METER with Green Backlit Display 9-30VDC, Mosfet Output
IP40
Direct Voltage Inputs
7 Digit Display (8mm)
9-30VDC Aux Supply
48 x 24mm Cutout
Reset On Panel or via Rear Terminals
Datasheet
Product Datasheet
Fastron Electronics FESCT-6000-4000-0.333V, 4000Amp 0.333V Class 1 Measurement Split Core CT's, w/terminals, 153x157mm Aperture
Features
Quick Release Split Core System
1m Flying Leads
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.60/3kV
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Fastron Electronics Part Number
FESCT-6000-4000-0.333V
Technology
Split Core AC Current Transformer
Ratio
4000/0.333V
Aperture Size
153x157mm
VA Rating
N/A
Accuracy Class
Class 1
Output
0.333VAC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 55°C
Continuous Current (max)
4000Amp x 1.2
Termination Style
Terminals
Unit Weight
3000g
Factory Pack Qty
9
Â
Datasheet
Product Datasheet
Application Notes
Installation Guide
Risbabh EM94-Z-V2-H-M, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 61-200VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display, 60-300V AC/DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
4 x DC Measurement Only
Â
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Â
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DCÂ power supply
Specification
Rishabh Part Number
EM94-Z-V2-H-M
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
61-200VDC
Maximum Measurement Range
61-200VDC
Display
4Â Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YESÂ 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
Â
IP54
Â
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Â
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Â
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Â