Fastron Electronics SCT-F16-60-5A-CL2, 60/5 Amp Measurement, Class 2 Split Core CT's
Features
Quick Release Split Core System
Cable Mount
5 Amp Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F16-60-5A-CL2
Technology
Split Core AC Current Transformer
Ratio
60/5 Amp
Aperture Size
ø 16 mm
VA Rating
N/A
Accuracy Class
Class 2
Output
5 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
60Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
ESCT-RC150-3000A, Rogowski Coil, 150mm Diameter, 85mV/kA Rated for 3000 Amp Recommended, 3 Meter Cable length
Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and the secondary circuit (measurement).
Features
Rated insulation voltage 1000 V Cat III PD2
Accuracy Class 0.5 (IEC 61869-2)
Protection degree IP67
3 m output cable (other lengths available see page 8)
Ambient temperature 40 °C … +80 °C
Very flexible and thin coil: 6.1 mm
Slot for attaching the loop on the primary with a cable tie
An innovative patented clasp drastically reduces the positioning error near the closing
Internal shield for enhanced measurement accuracy at low primary currents.
Advantages
Thin, flexible, and light weight solution
Very low positioning error
Quick, non-intrusive and easy setup
A single sensor for a large current range without overload
Less influenced by external fields
Adaptable for a large range of cable diameters
Applications
MV/LV substations on LV side: Transformer Condition Monitoring
Power metering: current measurement for active power calculation
Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation
Power quality monitoring: electrical loads and distribution system equipment
Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault
Remote Terminal Units (RTU)
Phasor Measurement Units (PMU)
Standards
IEC 61010-1: 2010; IEC 61010-2-32 ed.3: 2012
1) IEC 61869-1 ed1.0: 2007; IEC 61869-2: ed1.0: 2012
1) IEC 61869-6: draft 2016; IEC 61869-10: draft 2016
Specification
LEM Part Number
ESCT-RC150-3000A
Function
AC Current Measurement
Measuring Range
0 - 5,000 Amp RMS (Contact Us for Possible Replacement for wider range)
Secondary Voltage (Sensitivity)
85mV
Frequency Measuring Range
50-300kHz
Operating Voltage
Self Powered
Accuracy
0.5% from 25 to 5000 Amp
Phase Angle
< 0.004
Coil Diameter
15cm
Coil Circumference
Integrator to Coil Cable
3M Twisted Pair
Maximum Voltage
1000V Reinforced insulation according to EN 61010-1
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Isolation (50Hz, 1 min)
7.4kV
Overload
300,000 Amp
Termination Style
2 Stripped Wires
Weight
130g
Factory Pack Qty
1
Certifications
UL, ROHS
Datasheet
Product Datasheet
Application Notes
1) The Rogowski coil can measure any primary current as there is no saturation effect.
2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts)
3) Frequency bandwidth and phase shift modeling schematic can be provided on request.
4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5) Considering a primary conductor of at least ? 15 mm, perpendicular and in contact with the Rogowski coil.
6) Considering an external conductor of at least ? 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.
Fastron FES2151-FP-V10, Split Core AC Current Transducer, Multirange 0-100A,150A, 200A, Self Powered, Average RMS 0-10V Output. 1% Accuracy FCS2151-SP-V10
Compact and versatile current switches for detection of AC Currents, Multirange 0-10Amp, 0-20Amp, 0-50Amp via jumper, 0-10V True RMS output
Features
Average RMS 0-10V output
Multirange selector
Panel mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Highly accurate low current measurement down to 1Amp
High isolation between primary and secondary circuits
Easy installation
Applications
Fault Detection
Motor or Fan Protection
Application Domain
Energy and Automation
Specification
Fastron Part Number
FES2151-FD-V10
Technology
Solid Core Split Core AC Current Transducer
Range
0-100Amp, 0-150Amp, 0-200Amp via jumper
Supply Voltage
Self Powered
Load Current (RMS)
1Amp to 200 Amp
Output
0-10V Average RMS
Isolation
2kV (AC, 50Hz, 1 min)
Bandwidth
50/60Hz
Mounting Style
Panel Mount
Operating Temperature Range
-25°C / 70°C
Accuracy
1%
Termination Style
Screw Terminals
Unit Weight
200g
Certifications
UL E320368, CE, Rohs compliant
Datasheet
Product Datasheet
Installation Guide
Risbabh LM1360-MA4L-4-3-01-02-R-H-2, Panel Mount kWh Meter, Class 0.2S, 1/5Amp input, 2 Pulse Outputs, RS485 Comms, Three Section LCD Display
2 Pulse Outputs
Nominal current up to 1.2/6 A (For 1/5A CT Input) and nominal voltage up to 240V L-N
Three Section Display
RS 485 communication up to 19,200 bit/s
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
THD up to 31sth Harmonic
85 Parameter Measurement
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.2
Simple Menu
RS 485 communication up to 19,200 bit/s
MODBUS communication protocol
240V AC power supply
Specification
Rishabh Part Number
LM1360-MA4L-4-3-01-02-R-H-2
Functions
kWh Meter, Energy Meter
Supply Voltage
240VAC < 5VA
Nominal Measurement Range
600V L-L 350V L-N, 5 Amp
Maximum Measurement Range
600V L-L 350V L-N, 6 Amp
Display
Three Line LCD
Pulse Output
2 (input or output)
Accuracy
Class 0.2S (kW,kWh) Class 0.5(Active) Class 2(kVar,PF)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Ethernet
Modbus RTU Over TCP/IP 2400-19200 b/s
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Crouzet Syr-Line Single Pole Multifunction Timer With SP-NO/NC Contacts
MDE Timers Syrline 48x48mm - 1 Relay 5A :
Large LED or LCD Screen (13.2 mm)
Multi-function and single-function
Basic & Advance configuration modes
Multi-range (0.05 s – 9999 h)
Multi-voltage (24-240 V AC/DC)
1 or 2 relay outputs (Changeover)
Memory option in event of a break in supply (Note Memory available for A function only in LCD models)
Lock function › Up or down timing
DIN Sized (48x48 mm) Housing
Compact body (63 mm long)
Water & Dust-proof (IP66)
8-Pin
Multifunction Timers Include The Following :
Function A Delay on energisation 1 relay (With or without Memory)
Function B Timing on impulse one shot 1 relay
Function C Timing after impulse 1 relay
Function H Timing on energisation 1 relay
Function D Symmetrical Flashing (OFF start) with Memory 1 relay
Function Di Symmetrical Flashing (ON start) with Memory 1 relay
Specification
Crouzet Part Number
MDE1R0524U (Syr-Line Timer Single Pole 5A Multifunction, 24VAC/DC, 48x48mm)
Function
Multifunction Timer A - B - C - H - D - Di
Nominal Voltage
24VAC/DC
Digital Output
1 x C/O (SPDT) (Changeover -Single Pole Double Throw), 250VAC/DC @ 5 Amp
Min Breaking Current
10mA/12VDC
Timing Ranges
Selectable 0.05→9999h
Minimum Pulse Duration
30ms/100ms with load
Repeatability
0.5%
Reset Time
120ms
Memory
YES -> Function A only for MDE (LCD display) series
Isolation
1kV
Repetition Accuracy
0.5%
Threshold Adjustment Range
10 → 100 % of the range
Termination Style
8 Pin Base
Weight
80g
Certification
CE, cULus,CCC, ROHS, Reach, WEEE
Factory Pack Qty
1
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP66 (Front), IP40 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
Risbabh LM1360-MA4L-4-3-01-02-U-H-2, Panel Mount kWh Meter, Class 0.2S, 1/5Amp input, 2 Pulse Outputs, RS485 & USB Comms, Three Section LCD Display, Internal Logging
2 Pulse Outputs
Nominal current up to 1.2/6 A (For 1/5A CT Input) and nominal voltage up to 240V L-N
Three Section Display
RS 485 communication up to 19,200 bit/s
USB Port
8MB Internal Storage
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
THD up to 31sth Harmonic
85 Parameter Measurement
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.2
Simple Menu
RS 485 communication up to 19,200 bit/s
USB Comms
8MB Internal Logger
240V AC power supply
Specification
Rishabh Part Number
LM1360-MA4L-4-3-01-02-U-H-2
Functions
kWh Meter, Energy Meter
Supply Voltage
240VAC < 5VA
Nominal Measurement Range
600V L-L 350V L-N, 5 Amp
Maximum Measurement Range
600V L-L 350V L-N, 6 Amp
Display
Three Line LCD
Pulse Output
2 (input or output)
Accuracy
Class 0.2S (kW,kWh) Class 0.5(Active) Class 2(kVar,PF)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Ethernet
Optional
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
LEM DHAB S/124, O/L Automotive AC/DC Current Transducer, Multirange +/-25A +/-500A, 5VDC Supply, 22.5mm Round Aperture
Features
Open Loop Transducer using Hall Effect
Low Voltage Application
Unipolar +5V Power Supply
Primary Current Measuring Range up to +/-25A, and +/-500A for Channel 2
Maximum RMS primary admissable current: defined by busbar to have T° < +150°C
Operating Temperature Range: -40°C < T° < +125°C
Output Voltage: Full ratio-metric (in sensitivity and offset)
Dual Channel Sensor for Wider Measurement Range and Redundancy
Advantages
Good Accuracy for High and Low Current Range
Good Linearity
Low Thermal Offset Drift
Low Thermal Sensitivity Drift
Hermetic Package
Automotive Applications
Battery Pack Monitoring
Hybrid Vehicles
EV and Utility Vehicles
Specification
LEM Part Number
DHAB S/124
Technology
Multirange Open Loop Hall Effect
ROHS
Yes
Supply Voltage
5 VDC
Load Current Channel 1 (RMS)
+/-75 Amp
Load Current Channel 2 (RMS)
+/-500 Amp
Output
0.25 - 4.75V (2.5Vref)
Isolation
2.5kV (AC, 50Hz, 1 min)
Bandwidth
DC - 70Hz
Mounting Style
Panel Mount/Cable Mount
Aperture
⌀22.5mm
Operating Temperature Range
-40°C - 70°C
CH1 Accuracy @ 25 Deg C
0.15%(0A),0.7%(37A),1.3%(75A)
CH2 Accuracy @ 25 Deg C
1%(0A),6%(250A),9%(500A)
Termination Style
TYCO 1-1456426-5
Unit Weight
100g
Factory Pack Qty
6
Datasheet
Product Datasheet
Fastron Electronics SCT-F24-30-100mV, 30Amp/100mV Measurement, Class 1 Split Core CT's
Features
Quick Release Split Core System
Cable Mount
100mV Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F24-30-100mV
Technology
Split Core AC Current Transformer
Ratio
30/100mV
Aperture Size
ø 24 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
100mV (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
30Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Northern Design Power Rail PR350-M2-C-0.333V, kWh Meter, 3 Phase, DIN Rail, 240VAC aux, Class 1, 0.333V input, w/ pulse output and RS485 Comms, Power quality measurements
0.333V CT Input
Optional RS 485 communication up to 19,200 bit/s
True RMS values of currents and voltages
Power Quality Measurements
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, Hours Run, Peak Demand etc to the 30th Harmonic) from the measured signals.
Features :
Accuracy class 1
Measurement of Active and Reactive Power
Optional MODBUS RS 485 communication up to 19,200 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Northern Design Part Number
Power Rail PR350-M2-C-0.333V
Functions
Three Phase Energy Meter
Supply Voltage
230V L-N, 5 Amp +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 5 Amp +/-15%
Nominal Current Input
0.333 Volt AC
Pulse Output
3 x NO Voltage Free Contacts 100mA @ 100VAC/DC
Tariff Input
N/A (Optional)
Accuracy
Class 1 (I,U,F,PF,) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
106mm x 90mm x 58mm (6 modules wide)
Isolation
3.5kV
RS485
1200-19200 b/s
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 6 Modules
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Product Manual
Product Comms Manual
Option Links
Application Notes
CT Cable Losses
Meter Accuracy at Low Current
Current Input Isolation
LEM ART-B22-D70-SP3 + AI-P1A, 3 Phase Rogowski Coils & Universal Multi Range Integrator with Signal Conditioner
The universal Rogowski coil integrator AI-P1A complements LEM’s flexible clip-around coil ART and ARU range. The design is based on digital processing to give combined dynamic range, accuracy and versatility of use. It offers a wide range of output signals both RMS and instantaneous. AI-P1A is DIN rail mounted and can be stacked for multiphase application without spacing thanks to its low power dissipation.
Input signal
Accuracy Class 1 (IEC 61869-2) [1].
Linearity error ≤ 0.10 %. Protection degree IP2X.
35 mm DIN rail mounted.
Push-in terminals.
1 Amp instantaneous output.
6 selectable sensitivities depending on Rogowski coil: 22.5, 70, 80, 85, 100, 120 mV/kA at 50 Hz.
12 selectable ranges: 100, 200, 300, 400, 500, 600, 800, 1000, 1500, 2000, 4000, 5000 A.
Ambient operating temperature −25...+70 °C.
Advantages
Compact design for DIN rail assembly
High accuracy Class 1 (IEC 61869-2)
Setup by user via Select / Edit buttons
Clear status indication via bi-color led
Applications
MV/LV substations on LV side: Transformer Condition Monitoring
Power metering: current measurement for active power calculation
Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation
Power quality monitoring: electrical loads and distribution system equipment
Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault
Remote Terminal Units (RTU)
Phasor Measurement Units (PMU)
Standards
IEC 61010-1: 2010
UL
EMC: IEC 61326-1:2012
Included Options
Cross Power Plug-in: side contacts to stack up to 3 Integrator modules and use only one power supply.
Specification
LEM Part Number
AI-P1A + ART-B22-D70 (3Pcs)
Function
3 Phase AC Current Measurement
Measuring Range
Selectable 5000,4000,2000,1500,1000,800,600,500,400,300,200,100Amp
Sensitivity
Selectable 22.5,70,80,85,100,120mV/kA @ 50 Hz
Output
1 Amp output
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
10-32VDC
Accuracy
1% from 25 to 5000 Amp
Current Consumption
100mA (max)
Dimensions
100mm x 78mm x 15mm (Integrator), 7cm Diameter (Coils)
Mounting
Din Rail Mount
Integrator to Coil cable
3M Twisted and Screened
Integrator to Meter cable
User Supplied Shielded cable 1.5mm sqr, up to 6m long
Operating Temperature
-25°C - 70°C
Storage Temperature
-45°C to 80°C
Isolation (50Hz, 1 min)
1.5kV
True RMS Response Time
160-190ms
Termination Style
Push-in for 1.5mm sqr wire
Weight
58g
Factory Pack Qty
1
Certifications
UL, ROHS
Datasheet
AI-P1A Datasheet
ART Series Datasheet
Applicaton Notes
User Notice
1) The Rogowski coil can measure any primary current as there is no saturation effect.
2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts)
3) Frequency bandwidth and phase shift modelling schematic can be provided on request.
4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5) Considering a primary conductor of at least ⌀ 15 mm, perpendicular and in contact with the Rogowski coil.
6) Considering an external conductor of at least ⌀ 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.
Eastron SDM630MCT-1L 3 Phase DIN Rail Mount kWh Meter with Easyclick, 240VAC aux, Class 1, 100mA RJ12 CT Connect, w/RS485 Modbus RTU Comms
100mA RJ12 CT 4 x 3 Phase Connect
100mA RJ12 12 x Single Phase RJ12 CT with adapter
RS 485 communication up to 38,400 bit/s as standard
True RMS values of currents and voltages
Easyclick CT system reduces installation costs
Dual Metering System Reduces Cost and saves space
The meter is intended for measuring, and monitoring 1 x three phase or 3 x single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
System Accuracy Class B/Class1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM630MCT-1L
Functions
Quad Three Phase Energy Meter/ 12 x Single Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
100mA via RJ12 Easyclick CT's
Pulse Output
N/A
Tariff Input
N/A
System Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
700g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Suitable RJ12 CT's
Three Phase J12 Connected CT's
Split Core Single Phase CT's for RJ12 Connected Meters
Modbus Utility
EEM Meter Setting Software Utility
Risbabh EMDC 6002-1000-LA-C-2R, 4 Channel DC kWh Meter, Class 0.5, 150-150mV Shunt input, 201-1000VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, 4 Line LCD Display, 12-70VDC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 10-60VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EMDC 6002-1000-LA-C-2R
Functions
4 Channel DC kWh Meter, Energy Meter
Supply Voltage
12-70VDC
Nominal Measurement Range
201-1000VDC
Maximum Measurement Range
201-1000VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.