LEM DHR 200 C420, Hall Effect Current Sensor, 200Amp , True RMS 4-20mA output
Compact and versatile transducers for high AC and DC currents from 100 to 1000A True RMS with signal conditioning. Choice of output types: 4-20 mA, 0-5 V or 0-10 V, Bandwidth: DC 20..6000 Hz
Features
VFD and SCR waveforms current measurement
True RMS output
4-20mA current output
Panel mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable up to ?32mm
High isolation between primary and secondary circuits
Easy installation
Applications
-VFD Controlled Loads
VFD output indicates how the motor and attached load are operating
-SCR Controlled Loads
Accurate measurement of phase angle fired or burst fired(time proportional) SCR's. Current measurement gives faster response than temperature measurement
-Application Domain
Energy and Automation
Specification
LEM Part Number
DHR 200 C420
Technology
Open Loop Hall Effect
ROHS
Yes
Supply Voltage
20 - 50V
Load Current (RMS + DC)
200 Amp
Output
4-20mA
Isolation
4kV (AC, 50Hz, 1 min)
Bandwidth
20-6000Hz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
Level 3
Termination Style
SFKC 2.5/4-ST-5.08-RF(Phoenix Contact)
Unit Weight
260g
Factory Pack Qty
6
Datasheet
Product Datasheet
LEM DHR 300 C420, Hall Effect Current Sensor, 300Amp , True RMS 4-20mA output
Compact and versatile transducers for high AC and DC currents from 100 to 1000A True RMS with signal conditioning. Choice of output types: 4-20 mA, 0-5 V or 0-10 V, Bandwidth: DC 20..6000 Hz
Features
VFD and SCR waveforms current measurement
True RMS output
4-20mA current output
Panel mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable up to ?32mm
High isolation between primary and secondary circuits
Easy installation
Applications
-VFD Controlled Loads
VFD output indicates how the motor and attached load are operating
-SCR Controlled Loads
Accurate measurement of phase angle fired or burst fired(time proportional) SCR's. Current measurement gives faster response than temperature measurement
-Application Domain
Energy and Automation
Specification
LEM Part Number
DHR 300 C420
Technology
Open Loop Hall Effect
ROHS
Yes
Supply Voltage
20 - 50V
Load Current (RMS + DC)
300 Amp
Output
4-20mA
Isolation
4kV (AC, 50Hz, 1 min)
Bandwidth
20-6000Hz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
Level 3
Termination Style
SFKC 2.5/4-ST-5.08-RF(Phoenix Contact)
Unit Weight
260g
Factory Pack Qty
6
Datasheet
Product Datasheet
F922 Series AC Average RMS or DC Current Transducer, 9-36VDC Supply, 0-8 Amp, 4 Output types available
Features
Isolated measurement of AC or DC currents using internal Hall effect transducer.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned AC or DC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty. Otherwise 4-6 weeks
Specification
Oztherm Part Number
F922-X-XX-XX
Functions
Single Phase AC or DC Current Transducer
Supply Voltage
9-36VDC
Nominal Measurement Range
0-8 Amp (Sensor dependant)
Maximum Measurement Range
8 Amp
Alarm
C/O Relay 4Amp @ 30VDC, 0.5Amp @ 150VAC
Response Time
250mS
Accuracy @ 25 Deg C
Class 1
Bandwidth
DC - 1kHz
linearity
< 0.15%
Isolation
2.5kV
Comms
N/A
Weight
250g
Enclosure Size
79 x 60 x 85mm
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
Polyamide non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP40
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
F920-A-XX-XX-XX - Signal Conditioner and +/-15VDC Bipolar Power Supply with Adjustable High and Low C/O Relay Alarm. +/- 4V Bipolar Input, For External LEM Hall Effect Sensor
Features
Isolated measurement of AC or DC currents using a Hall effect transducer with external aperture.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned AC Average RMS or DC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty, Otherwise 4-6 weeks
Datasheet
Datasheet
LEM HAZ 20000-SB, Hall Effect Current Transducer, 20000A, +/-10V Instant Output, +/-15V supply
For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).
Features
Instantaneous output version +/-10V, +/-20mA
True RMS output versions 4-20mA, 0-10V putput
Hall effect measuring principle
Galvanic isolation between primary and secondary circuit
Instantaneous voltage output
Isolation voltage 17kV Rms /50 Hz /1min
Low power consumption
Package in PBT meeting UL 94-V0
Instantaneous voltage output
Advantages
Easy installation
Small size and space savings
Only one design for wide current ratings range
High immunity against external interference
Applications
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Power supplies for welding and telecom applications
Application domain
Industrial
Traction
Specification
LEM Part Number
HAZ 20000-SB
Technology
Open Loop Hall Effect
ROHS
Yes
Supply Voltage
+/- 15VDC
Load Current (RMS + DC)
20000 Amp
Overload Rating
30000 At
Output
+/-10 V Instantaneous
Isolation
17kV (AC, 50Hz, 1 min)
Bandwidth
DC-3kHz
Mounting Style
Busbar Mount
Operating Temperature Range
-25°C / 85°C
Accuracy
1%
Termination Style
F2023A (FUJICON)
Unit Weight
6kg
Factory Pack Qty
2
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM DHR 1000 C420, Hall Effect Current Sensor, 1000Amp , True RMS 4-20mA output
Compact and versatile transducers for high AC and DC currents from 100 to 1000A True RMS with signal conditioning. Choice of output types: 4-20 mA, 0-5 V or 0-10 V, Bandwidth: DC 20..6000 Hz
Features
VFD and SCR waveforms current measurement
True RMS output
4-20mA current output
Panel mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable up to ⌀32mm
High isolation between primary and secondary circuits
Easy installation
Applications
-VFD Controlled Loads
VFD output indicates how the motor and attached load are operating
-SCR Controlled Loads
Accurate measurement of phase angle fired or burst fired(time proportional) SCR's. Current measurement gives faster response than temperature measurement
-Application Domain
Energy and Automation
Specification
LEM Part Number
DHR 1000 C420
Technology
Open Loop Hall Effect
ROHS
Yes
Supply Voltage
20 - 50V
Load Current (RMS + DC)
1000 Amp
Output
4-20mA
Isolation
4kV (AC, 50Hz, 1 min)
Bandwidth
20-6000Hz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
Level 3
Termination Style
SFKC 2.5/4-ST-5.08-RF(Phoenix Contact)
Unit Weight
260g
Factory Pack Qty
6
Datasheet
Product Datasheet
LEM AHR 1000 B10, Hall Effect Current Sensor, 1000Amp, True RMS 0-10V output, 104 x 40mm aperture
Compact and versatile transducers for high AC and DC currents from 500 to 2000A True RMS with signal conditioning. Choice of output types: 4-20 mA, 0-5 V or 0-10 V, Bandwidth: DC 20..6000 Hz
Features
Split Core
VFD and SCR waveforms current measurement
True RMS output
0-10V voltage output
Busbar mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable or busbar up to 104 x 40mm
High isolation between primary and secondary circuits
Easy installation
Applications
-AC Power Supplies or Motors
True RMS sensing - the most accurate way to monitor power supply or input power
-VFD Controlled Loads
VFD output indicates how the motor and attached load are operating
-SCR Controlled Loads
Accurate measurement of phase angle fired or burst fired(time proportional) SCR's and switch mode rectifiers. Current measurement gives faster response than temperature measurement.
-Renewable Energy Installations or Backup Batteries
Continuous condition monitoring allowing automatic failure detection and prediction
-Application Domain
Energy and Automation
Specification
LEM Part Number
AHR 1000 B10
Technology
Open Loop Hall Effect
ROHS
Yes
Supply Voltage
20 - 50V
Nominal Current (RMS + DC)
1000 Amp
Maximum Measurement Current (Peak)
2000 Amp
Output
0-10V
Isolation
5.8kV (AC, 50Hz, 1 min)
Bandwidth
20-6000Hz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
1%
Termination Style
SFKC 2.5/4-ST-5.08-RF(Phoenix Contact)
Unit Weight
650g
Factory Pack Qty
6
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM AHR 1000 B420, Hall Effect Current Sensor, 1000Amp, True RMS 4-20mA output, 104 x 40mm aperture
Compact and versatile transducers for high AC and DC currents from 500 to 2000A True RMS with signal conditioning. Choice of output types: 4-20 mA, 0-5 V or 0-10 V, Bandwidth: DC 20..6000 Hz
Features
Split Core
VFD and SCR waveforms current measurement
True RMS output
4-20mA current output
Busbar mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable or busbar up to 104 x 40mm
High isolation between primary and secondary circuits
Easy installation
Applications
-AC Power Supplies or Motors
True RMS sensing - the most accurate way to monitor power supply or input power
-VFD Controlled Loads
VFD output indicates how the motor and attached load are operating
-SCR Controlled Loads
Accurate measurement of phase angle fired or burst fired(time proportional) SCR's and switch mode rectifiers. Current measurement gives faster response than temperature measurement.
-Renewable Energy Installations or Backup Batteries
Continuous condition monitoring allowing automatic failure detection and prediction
-Application Domain
Energy and Automation
Specification
LEM Part Number
AHR 1000 B420
Technology
Open Loop Hall Effect
ROHS
Yes
Supply Voltage
20 - 50V
Nominal Current (RMS + DC)
1000 Amp
Maximum Measurement Current (Peak)
2000 Amp
Output
4-10mA
Isolation
5.8kV (AC, 50Hz, 1 min)
Bandwidth
20-6000Hz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
1%
Termination Style
SFKC 2.5/4-ST-5.08-RF(Phoenix Contact)
Unit Weight
650g
Factory Pack Qty
6
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM AHR 1000 B5, Hall Effect Current Sensor, 1000Amp, True RMS 0-5V output, 104 x 40mm aperture
Compact and versatile transducers for high AC and DC currents from 500 to 2000A True RMS with signal conditioning. Choice of output types: 4-20 mA, 0-5 V or 0-10 V, Bandwidth: DC 20..6000 Hz
Features
Split Core
VFD and SCR waveforms current measurement
True RMS output
0-5V voltage output
Busbar mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable or busbar up to 104 x 40mm
High isolation between primary and secondary circuits
Easy installation
Applications
-AC Power Supplies or Motors
True RMS sensing - the most accurate way to monitor power supply or input power
-VFD Controlled Loads
VFD output indicates how the motor and attached load are operating
-SCR Controlled Loads
Accurate measurement of phase angle fired or burst fired(time proportional) SCR's and switch mode rectifiers. Current measurement gives faster response than temperature measurement.
-Renewable Energy Installations or Backup Batteries
Continuous condition monitoring allowing automatic failure detection and prediction
-Application Domain
Energy and Automation
Specification
LEM Part Number
AHR 1000 B5
Technology
Open Loop Hall Effect
ROHS
Yes
Supply Voltage
20 - 50V
Nominal Current (RMS + DC)
1000 Amp
Maximum Measurement Current (Peak)
2000 Amp
Output
0-5V
Isolation
5.8kV (AC, 50Hz, 1 min)
Bandwidth
20-6000Hz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
1%
Termination Style
SFKC 2.5/4-ST-5.08-RF(Phoenix Contact)
Unit Weight
650g
Factory Pack Qty
6
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM AHR 1500 B420, AHR 1500 B420, Hall Effect Current Sensor, 1500Amp, True RMS 4-20mA output, 104 x 40mm aperture
Compact and versatile transducers for high AC and DC currents from 500 to 2000A True RMS with signal conditioning. Choice of output types: 4-20 mA, 0-5 V or 0-10 V, Bandwidth: DC 20..6000 Hz
Features
Split Core
VFD and SCR waveforms current measurement
True RMS output
4-20mA current output
Busbar mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable or busbar up to 104 x 40mm
High isolation between primary and secondary circuits
Easy installation
Applications
-AC Power Supplies or Motors
True RMS sensing - the most accurate way to monitor power supply or input power
-VFD Controlled Loads
VFD output indicates how the motor and attached load are operating
-SCR Controlled Loads
Accurate measurement of phase angle fired or burst fired(time proportional) SCR's and switch mode rectifiers. Current measurement gives faster response than temperature measurement.
-Renewable Energy Installations or Backup Batteries
Continuous condition monitoring allowing automatic failure detection and prediction
-Application Domain
Energy and Automation
Specification
LEM Part Number
AHR 1500 B420
Technology
Open Loop Hall Effect
ROHS
Yes
Supply Voltage
20 - 50V
Nominal Current (RMS + DC)
1500 Amp
Maximum Measurement Current (Peak)
2500 Amp
Output
4-20mA
Isolation
5.8kV (AC, 50Hz, 1 min)
Bandwidth
20-6000Hz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
1%
Termination Style
SFKC 2.5/4-ST-5.08-RF(Phoenix Contact)
Unit Weight
650g
Factory Pack Qty
6
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM AHR 2000 B10, Hall Effect Current Sensor, 2000Amp, True RMS 0-10V output, 104 x 40mm aperture
Compact and versatile transducers for high AC and DC currents from 500 to 2000A True RMS with signal conditioning. Choice of output types: 4-20 mA, 0-5 V or 0-10 V, Bandwidth: DC 20..6000 Hz
Features
Split Core
VFD and SCR waveforms current measurement
True RMS output
0-10V voltage output
Busbar mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable or busbar up to 104 x 40mm
High isolation between primary and secondary circuits
Easy installation
Applications
-AC Power Supplies or Motors
True RMS sensing - the most accurate way to monitor power supply or input power
-VFD Controlled Loads
VFD output indicates how the motor and attached load are operating
-SCR Controlled Loads
Accurate measurement of phase angle fired or burst fired(time proportional) SCR's and switch mode rectifiers. Current measurement gives faster response than temperature measurement.
-Renewable Energy Installations or Backup Batteries
Continuous condition monitoring allowing automatic failure detection and prediction
-Application Domain
Energy and Automation
Specification
LEM Part Number
AHR 2000 B10
Technology
Open Loop Hall Effect
ROHS
Yes
Supply Voltage
20 - 50V
Nominal Current (RMS + DC)
2000 Amp
Maximum Measurement Current (Peak)
3000 Amp
Output
0-10V
Isolation
5.8kV (AC, 50Hz, 1 min)
Bandwidth
20-6000Hz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
1%
Termination Style
SFKC 2.5/4-ST-5.08-RF(Phoenix Contact)
Unit Weight
650g
Factory Pack Qty
6
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM AHR 2000 B5, Hall Effect Current Sensor, 2000Amp, True RMS 0-5V output, 104 x 40mm aperture
Compact and versatile transducers for high AC and DC currents from 500 to 2000A True RMS with signal conditioning. Choice of output types: 4-20 mA, 0-5 V or 0-10 V, Bandwidth: DC 20..6000 Hz
Features
Split Core
VFD and SCR waveforms current measurement
True RMS output
0-5V voltage output
Busbar mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable or busbar up to 104 x 40mm
High isolation between primary and secondary circuits
Easy installation
Applications
-AC Power Supplies or Motors
True RMS sensing - the most accurate way to monitor power supply or input power
-VFD Controlled Loads
VFD output indicates how the motor and attached load are operating
-SCR Controlled Loads
Accurate measurement of phase angle fired or burst fired(time proportional) SCR's and switch mode rectifiers. Current measurement gives faster response than temperature measurement.
-Renewable Energy Installations or Backup Batteries
Continuous condition monitoring allowing automatic failure detection and prediction
-Application Domain
Energy and Automation
Specification
LEM Part Number
AHR 1000 B5
Technology
Open Loop Hall Effect
ROHS
Yes
Supply Voltage
20 - 50V
Nominal Current (RMS + DC)
2000 Amp
Maximum Measurement Current (Peak)
3000 Amp
Output
0-5V
Isolation
5.8kV (AC, 50Hz, 1 min)
Bandwidth
20-6000Hz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
1%
Termination Style
SFKC 2.5/4-ST-5.08-RF(Phoenix Contact)
Unit Weight
650g
Factory Pack Qty
6
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition