LEM AP 200 B10, Split Core AC Current Sensor, selectable 100, 150, 200 Amp, Average RMS 10V/5V output, Infinite Overload Capability
Compact and versatile Split Core AC current sensor, selectable 100, 150, 200 Amp Average RMS. Selectable 0-5V, 0-10V output
Features
Split Core
Average RMS output
0-10V/0-5V voltage output
Busbar, or Din Rail mounting
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for busbar/cable up to 18.5mm x 18.5mm
High isolation between primary and secondary circuits
Easy installation
DIN Rail Mount
Applications
-Automation Systems
Analogue current reading for remote monitoring (e.g. Motor)
-Data Loggers
Self Powered. Will not drain data logger batteries
-Panel Meters
Simple connection displays power consumption
Specification
LEM Part Number
AP 200 B10
Technology
AC Current Transformer with Process Output
ROHS
Yes
Supply Voltage
24VDC @ 30mA
Nominal Current (RMS + DC)
100,150, 200 Amp Selectable
Overload
Infinite
Output
0-10V/0-5V Average RMS
Isolation
5kV (AC, 50Hz, 1 min)
Bandwidth
30-2000Hz
Mounting Style
Din Rail mount or Busbar mount
Operating Temperature Range
-40°C / 85°C
Accuracy
1%
Termination Style
Spring Terminal Block (Female Included)
Unit Weight
90g
Factory Pack Qty
6
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
Northern Design XD-R420-2, Current Transducer, True RMS, Ipn = Selectable 5,10,15,20,25,30 Amp, 4-20mA out,16-36VDC Loop powered
Features
Ipn = Selectable 5,10,15,20,25,30 Amp
True RMS Output
4-20mA Current Output
Din Rail Mounting
16-36VDC Loop Powered
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable up to ⌀ 16mm
High isolation between primary and secondary circuits
Easy installation
Applications
Current Measurement
Energy Management
Earth Leakage Measurement
Motor Control
Actuators
Lamp Failure
Specification
Northern Design Part Number
XD-R420-2
Technology
AC Current Transformer
Protection Class
IP50
Supply Voltage
16-36VDC Loop Powered (10mA)
Load Current (RMS)
Selectable 5,10,15,20,25,30 Amp
Output
4-20mA (True RMS)
Isolation
4kV (AC, 50Hz, 1 min)
Bandwidth
55 - 65Hz
Mounting Style
Din Rail Mount
Operating Temperature Range
-10°C / 65°C
Accuracy
Class 1
Termination Style
Screw
Unit Weight
180g
Factory Pack Qty
6
Â
Datasheet
Product Brochure
Product Manual
Application Notes
Northern Design XD-P-2, Current Transducer, True RMS, Ipn = Selectable 7.5,15,22.5,30Amps, Pulse output, 16-36VDC Loop powered
Features
Ipn = Selectable Selectable 7.5,15,22.5,30Amps
Average RMS Output
4-20mA Current Output
Din Rail Mounting
16-36VDC Loop Powered
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable up to ⌀ 16mm
High isolation between primary and secondary circuits
Easy installation
Applications
Current Measurement
Energy Management
Earth Leakage Measurement
Motor Control
Actuators
Lamp Failure
Specification
Northern Design Part Number
XD-P-2
Technology
AC Current Transformer
Protection Class
IP50
Supply Voltage
16-36VDC Loop Powered (10mA)
Load Current (RMS)
Selectable Selectable 7.5,15,22.5,30Amps
Output
Pulse Output
Isolation
4kV (AC, 50Hz, 1 min)
Bandwidth
55 - 65Hz
Mounting Style
Din Rail Mount
Operating Temperature Range
-10°C / 65°C
Accuracy
Class 1
Termination Style
Screw
Unit Weight
180g
Factory Pack Qty
6
Â
Datasheet
Product Brochure
Product Manual
Northern Design XD-I420-3, AC Current Transducer, Average RMS, Ipn = Selectable 50,100,150,200,300 Amp, 4-20mA out, 16-36VDC Loop powered
Features
Ipn = Selectable 50,100,150,200,300 Amp
Average RMS Output
4-20mA Current Output
Din Rail Mounting
16-36VDC Loop Powered
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable up to ⌀ 16mm
High isolation between primary and secondary circuits
Easy installation
Applications
Current Measurement
Energy Management
Earth Leakage Measurement
Motor Control
Actuators
Lamp Failure
Specification
Northern Design Part Number
XD-I420-3
Technology
AC Current Transformer
Protection Class
IP50
Supply Voltage
16-36VDC Loop Powered (10mA)
Load Current (RMS)
Selectable 50,100,150,200,300 Amp
Output
4-20mA
Isolation
4kV (AC, 50Hz, 1 min)
Bandwidth
55 - 65Hz
Mounting Style
Din Rail Mount
Operating Temperature Range
-10°C / 65°C
Accuracy
Class 1
Termination Style
Screw
Unit Weight
180g
Factory Pack Qty
6
Â
Datasheet
Product Brochure
Product Manual
Â
Northern Design XD-I420-2, AC Current Transducer, Average RMS, Ipn = Selectable 15,30,45,60,75,100 Amp, 4-20mA out, 16-36VDC Loop powered
Features
Ipn = Selectable 15,30,45,60,75,100 Amp
Average RMS Output
4-20mA Current Output
Din Rail Mounting
16-36VDC Loop Powered
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable up to ⌀ 16mm
High isolation between primary and secondary circuits
Easy installation
Applications
Current Measurement
Energy Management
Earth Leakage Measurement
Motor Control
Actuators
Lamp Failure
Specification
Northern Design Part Number
XD-I420-2
Technology
AC Current Transformer
Protection Class
IP50
Supply Voltage
16-36VDC Loop Powered (10mA)
Load Current (RMS)
Selectable 15,30,45,60,75,100 Amp
Output
4-20mA
Isolation
4kV (AC, 50Hz, 1 min)
Bandwidth
55 - 65Hz
Mounting Style
Din Rail Mount
Operating Temperature Range
-10°C / 65°C
Accuracy
Class 1
Termination Style
Screw
Unit Weight
180g
Factory Pack Qty
6
Â
Datasheet
Product Brochure
Product Manual
Â
Rishabh Rish Con M-22132, Class 0.5 Power Transducer 4 wire, 20-480V L-L, 5Amp measurement, 85-253VAC/90-320VDC Supply, 4 x Analogue -20-20mA/4-20mA/-10-10V output, USB Programming Port, Modbus RTU Comms, 750 OHM Load Resistance, without display
Measures Active Power/Phase Angle/Power Factor
Measures Apparent/Reactive/Active Power
Analogue output setting 0-20mA/4-20mA/0-10V
300mS response time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 122.5 x 66 x 106.5mm depth DIN Rail cabinet space
Specification
Rishabh Part Number
Rish Con M-22132
Functions
Active Power/Phase Angle/Power Factor Transducer 4 wire
Measurement Output
4 x 4-20mA/0-20mA/0-10V User Selectable
Relay Output
N/A
Relay Type
Voltage Free Contact, 0.5 Amp @ 250VAC
Input
20Â - 480VAC L-L 50/60Hz
Overload (Continuous)
120%
Overload (1 second)
150%
Operating Temperature
-10 - 55°C
Supply Voltage
85-253VAC/90-320VDC
Accuracy
0.2%
Response Time
300mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Mounting Size
122.5 x 66 x 106.5mm
Safety
IP40/IP20 EN60529 Protection Class II EN61010
Weight
400g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Product User Manual
Technical Support
Rish Con P setup procedure blog
Â
Rishabh Rish Con M-22122, Class 0.5 Power Transducer 4 wire, 20-480V L-L, 5Amp measurement, 85-253VAC/90-320VDC Supply, 2 x Analogue -20-20mA/4-20mA/-10-10V output, 2 Relay Outputs, USB Programming Port, Modbus RTU Comms, 750 OHM Load Resistance, without display
Measures Active Power/Phase Angle/Power Factor
Measures Apparent/Reactive/Active Power
Analogue output setting -20-20mA/4-20mA/-10-10V
2 x Relay Outputs 0.5 Amp @ 250VAC
300mS response time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 122.5 x 66 x 106.5mm depth DIN Rail cabinet space
Specification
Rishabh Part Number
Rish Con M-22121
Functions
Active Power/Phase Angle/Power Factor Transducer 4 wire
Measurement Output
2Â x 4-20mA/0-20mA/0-10V User Selectable
Minimum Load Resistance
750 Ohm
Relay Output
2Â x 0.5 Amp @ 250VAC NO Voltage Free Contacts
Relay Type
Voltage Free Contact, 0.5 Amp @ 250VAC
Input
20Â - 480VAC L-L 50/60Hz
Overload (Continuous)
120%
Overload (1 second)
150%
Operating Temperature
-10 - 55°C
Supply Voltage
85-253VAC/90-320VDC
Accuracy
0.2%
Response Time
300mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Mounting SizeÂ
122.5 x 66 x 106.5mm
Safety
IP40/IP20 EN60529 Protection Class II EN61010
Weight
400g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Product User Manual
Technical Support
Rish Con P setup procedure blog
Â
Iskra Doo UMT540-HSHFNAAAA, Multifunction Power Transducer, Class 0.5S, 4 Wire, 600V L-N, 5A AC Input 50/60Hz, 24-300VDC or 40-276VAC Aux Input, 4 Programmable analogue outputs, USB, Ethernet, RS485 Comms
(U)MT version = Ring type terminal block
Class 0.5S Active, Class 0.2 Reactive (EN 60688) , Class 0.1 on Comms
RS485 Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 140 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy Class 0.5s Active, Class 0.2 Reactive (EN 60688), Class 0.1 on Comms
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Optional Remote Display Support
Specification
Iskra Doo Part Number
UMT540-HSHFNAAAA
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
600V L-N, 5 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
N/A
Tariff Input
N/A
Output(s)
4 x Analogue
Accuracy
Class 0.2 (I,U,F,PF,θ,THD) Class 0.5s(Active), Class 0.2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Terminations
Ring Type Terminal Block
Isolation
3.5kV
Comms
USB (standard) RS232 2400-115200 b/s (RS485 Optional)
Weight
900g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Â
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Â
Datasheet
Product Datasheet
Software
MiQen Setting Software
Rishabh Rish Con V(500V)-50-H-O1A2-O2A2-Z-Z-Z, AC Voltage Transducer, 50Hz 65-500VAC Full Scale, Dual 0-20mA Output, 60-300VAC/DC Supply, without Display
Dual 0-20mA Output
250mS response time
PC 94 UL V0
Each unit needs just 43.75 x 100.9 mm depth DIN Rail cabinet space
Specification
Rishabh Part Number
Rish Con V(500V)-50-H-O1A2-O2A2-Z-Z-Z
Measurement Output
Dual 0-20mA
Input
65 - 500VAC 50/60Hz
Overlaod (Continuous)
120%
Overload (1 second)
150%
Operating Temperature
-40 - 70°C
Supply Voltage
60 - 300VAC/DC
Accuracy
0.2%
Response Time
250mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Safety
IP40/IP20 EN60529 Protection Class II EN61010
Weight
400g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Technical Support
Rish Con P setup procedure blog
Â
Iskra Doo MT550-SSHFNAASS (DIN), Multifunction Power Transducer, Class 0.1, 4 Wire, 50-500V L-N, 5A AC Input 16-400Hz, 70-300VDC or 80-276VAC Aux Input, 2 Programmable analogue outputs, 2 Pulse Outputs, USB, Ethernet, RS485 Comms
Class 0.1 Active, Class 0.2 Reactive (EN 60688)
RS485 Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 140 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy Class 0.5s Active, Class 0.2 Reactive (EN 60688), Class 0.1 on Comms
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Optional Remote Display Support
Specification
Iskra Doo Part Number
MT550-SSHFNAASS (DIN)
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
500V L-N, 5 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
N/A
Tariff Input
N/A
Output(s)
2 x Analogue
Accuracy
Class 0.2 (I,U,F,PF,θ,THD) Class 0.1(Active), Class 0.2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Terminations
EU Style Clamp Terminals
Isolation
3.5kV
Comms
USB (standard) RS232 2400-115200 b/s (RS485 Optional)
Weight
900g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
MiQen Setting Software
Iskra Doo MT440-SSUDAAAAA, Multifunction Power Transducer, Class 0.5, 4 Wire, 600V 1/5/10Amp AC Input 50/60Hz, 24-300VDC or 40-276VAC Aux Input, 4 Programmable Analogue Outputs, RS485 + USB Comms
Class 0.5 (EN 60688)
USB Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 50 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy class 0.5
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Specification
Iskra Doo Part Number
MT440-SSUDAAAAA
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
600V L-N, 1/5/10 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
N/A
Tariff Input
N/A
Output
4 x Analogue
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Comms
USB (standard) RS485 2400-115200 b/s (RS232 Optional)
Weight
370g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Â
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Â
Datasheet
Product Datasheet
Software
MiQen Setting Software
MIPACK Programmer
Iskra Doo MT406-1254 Series Single Phase AC Voltage Transducer, Fixed zero and span
Class 0.5 (EN 60688)
0-20mA analogue output for Moving Coil Voltmeter
Average RMS values of voltage
Features :
Measurement of up to 125VAC
Self powered
Accuracy class 0.5
Input frequency 50/60Hz
Specification
Iskra Doo Part Number
MT406-1254
Functions
Single Phase AC Voltage Transducer
Supply Voltage
Self Powered
Nominal Measurement Range
110VAC (0-125V Scale)
Maximum Measurement Range
132VAC
Output
0-20mA
Tariff Input
N/A
Accuracy
Class 0.5
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Comms
N/
Weight
340g
Enclosure Material
UL94
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Â
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
MiQen Setting Software
Â
Iskra Doo MT406-34 Series Single Phase AC Voltage Transducer, Fixed zero and span
Class 0.5 (EN 60688)
0-20mA analogue Output
Average RMS values of voltage
Features :
Measurement of up to 76.2VAC
Self Powered
Accuracy class 0.5
Input frequency 50/60Hz
Specification
Iskra Doo Part Number
MT406-34
Functions
Single Phase AC Voltage Transducer
Supply Voltage
Self Powered
Nominal Measurement Range
0-69.3VAC
Maximum Measurement Range
0-76.2VAC
Output
0-20mA
Tariff Input
N/A
Accuracy
Class 0.5
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Comms
N/
Weight
340g
Enclosure Material
UL94
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Â
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Â
Iskra Doo MI 454, Potentiometer and Tap Position Programmable Transducer, Class 0.5, Universal 20 - 300VDC/40 to 276VAC 40 to 70Hz, Aux Voltage 57.74V,100V,230V,400V,500VAC
Class 0.5 (EN 60688)
Programable DC Voltage Output 0-1V to 0-10V @ 20mA
Programmable DC Current Output 0-1mA to 0-5mA, 0-5mA to 0-20mA @ 15V
Features :
Measurement of up to 500VAC
Universal Supply 20 - 300VDC/40 to 276VAC 40 to 70Hz
Accuracy class 0.5
Input frequency 40-70Hz
Specification
Iskra Doo Part Number
MI454
Functions
Single Phase AC Voltage Transducer
Supply Voltage
Self Powered
Nominal Measurement Range
0-500VAC
Maximum Measurement Range
0-600VAC
Output
0-20mA/0-5mA
Tariff Input
N/A
Accuracy
Class 0.5
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Comms
N/
Weight
340g
Enclosure Material
UL94
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Â
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Â
Datasheet
Product Datasheet
Â
Iskra Doo MT540-HSHFNAAAA, Multifunction Power Transducer, Class 0.5S, 4 Wire, 600V L-N, 5A AC Input 50/60Hz, 24-300VDC or 40-276VAC Aux Input, 2 Programmable analogue outputs, USB, Ethernet, RS485 Comms
Class 0.5S Active, Class 0.2 Reactive (EN 60688) , Class 0.2 on Comms
RS485 Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 140 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy Class 0.5s Active, Class 0.2 Reactive (EN 60688), Class 0.1 on Comms
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Optional Remote Display Support
Specification
Iskra Doo Part Number
MT540-HSHFNAAAA
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
600V L-N, 5 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
N/A
Tariff Input
N/A
Output(s)
4 x Analogue
Accuracy
Class 0.2 (I,U,F,PF,θ,THD) Class 0.5s(Active), Class 0.2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Terminations
EU Style Clamp Terminals
Isolation
3.5kV
Comms
USB (standard) RS232 2400-115200 b/s (RS485 Optional)
Weight
900g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Â
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Â
Datasheet
Product Datasheet
Software
MiQen Setting Software
Iskra Doo MT440-SSUDAANNA, Multifunction Power Transducer, Class 0.5, 4 Wire, 600V L-N, 1/5/10Amp AC Input 50/60Hz, 24-300VDC or 40-276VAC Aux Input, 2 Programmable analogue outputs, RS485 & USB Comms
Class 0.5 (EN 60688)
USB Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 50 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy class 0.5
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Specification
Iskra Doo Part Number
MT440-SSUDAANNA
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
600V L-N, 1/5/10 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
N/A
Tariff Input
N/A
Output(s)
2 x Analogue
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Comms
USB (standard) RS232 2400-115200 b/s (RS485 Optional)
Weight
370g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Â
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Â
Datasheet
Product Datasheet
Software
MiQen Setting Software
MIPACK Programmer
Iskra Doo MT406-54 Series Single Phase AC Voltage Transducer, Fixed zero and span
Class 0.5 (EN 60688)
0-20mA analogue Output
Average RMS values of voltage
Features :
Measurement of up to 132VAC
Self Powered
Accuracy class 0.5
Input frequency 50/60Hz
Specification
Iskra Doo Part Number
MT406-54
Functions
Single Phase AC Voltage Transducer
Supply Voltage
Self Powered
Nominal Measurement Range
0-110VAC
Maximum Measurement Range
0-132VAC
Output
0-20mA
Tariff Input
N/A
Accuracy
Class 0.5
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Comms
N/
Weight
340g
Enclosure Material
UL94
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Â
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Â
Datasheet
Product Datasheet
Â
Iskra Doo MT406-24 Series Single Phase AC Voltage Transducer, Fixed zero and span
Class 0.5 (EN 60688)
0-20mA analogue Output
Average RMS values of voltage
Features :
Measurement of up to 76.2VAC
Self Powered
Accuracy class 0.5
Input frequency 50/60Hz
Specification
Iskra Doo Part Number
MT406-24
Functions
Single Phase AC Voltage Transducer
Supply Voltage
Self Powered
Nominal Measurement Range
0-63.5VAC
Maximum Measurement Range
0-76.2VAC
Output
0-20mA
Tariff Input
N/A
Accuracy
Class 0.5
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Comms
N/
Weight
340g
Enclosure Material
UL94
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Â
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
F923 Series AC Current Transducer with Process Outputs & High and Low Sold State Alarm
Features
Isolated measurement of AC currents using internal Hall effect transducer.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned AC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty. Otherwise 4-6 weeks
Specification
Oztherm Part Number
F923-X-XX-AC-XX
Functions
Single Phase AC Current Transducer
Supply Voltage
9-36VDC
Nominal Measurement Range
0-8 Amp (Sensor dependant)
Maximum Measurement Range
8 Amp
Alarm
C/O Relay 2Amp @ 40VDC, 2Amp @ 60VAC
Response Time
250mS
Accuracy @ 25 Deg C
Class 1
Bandwidth
DC - 1kHz
linearity
< 0.15%
Isolation
2.5kV
Comms
N/A
Weight
250g
Enclosure Size
79 x 60 x 85mm
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
Polyamide non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP40
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Rishabh Rish Con-V(500)-F-H-O1A1-O200-D-Z-Z, AC Voltage Transducer, Input Programmable True RMS 50Hz 57-500VAC Full Scale, 0-20mA, 60-300VAC Supply, with Display
Digital output setting 0-20mA/4-20mA/0-10V
Dual output version available
300mS response time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 43.75 x 100.9 mm depth DIN Rail cabinet space
Specification
Rishabh Part Number
Rish Con-V(500)-F-H-O1A1-O200-D-Z-Z
Measurement Output
4-20mA/0-20mA/0-10V User Selectable
Input
57 - 500VAC 50/60Hz
Overlaod (Continuous)
120%
Overload (1 second)
150%
Operating Temperature
-40 - 70°C
Supply Voltage
60 - 300VAC
Accuracy
0.2%
Response Time
300mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Safety
IP40/IP20 EN60529 Protection Class II EN61010
Weight
400g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Technical Support
Rish Con P setup procedure blog
Â
Iskra Doo MT406-11 Series Single Phase AC Voltage Transducer, Fixed zero and span
Class 0.5 (EN 60688)
0-1mA analogue output for Moving Coil Voltmeter
Average RMS values of voltage
Features :
Measurement of up to 69.25VAC
Self powered
Accuracy class 0.5
Input frequency 50/60Hz
Specification
Iskra Doo Part Number
MT406-11
Functions
Single Phase AC Voltage Transducer
Supply Voltage
Self Powered
Nominal Measurement Range
57.7VAC
Maximum Measurement Range
69.25VAC
Output
0-1mA
Tariff Input
N/A
Accuracy
Class 0.5
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Comms
N/
Weight
340g
Enclosure Material
UL94
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Â
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
MiQen Setting Software
Â
F923 Series DC Current Transducer with Process Outputs & High and Low Sold State Alarm
Features
Isolated measurement of DC currents using internal Hall effect transducer.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned DC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty. Otherwise 4-6 weeks
Specification
Oztherm Part Number
F923-X-XX-DC-XX
Functions
Single Phase DC Current Transducer
Supply Voltage
9-36VDC
Nominal Measurement Range
0-8 Amp (Sensor dependant)
Maximum Measurement Range
8 Amp
Alarm
C/O Relay 2Amp @ 40VDC, 2Amp @ 60VAC
Response Time
250mS
Accuracy @ 25 Deg C
Class 1
Bandwidth
DC - 1kHz
linearity
< 0.15%
Isolation
2.5kV
Comms
N/A
Weight
250g
Enclosure Size
79 x 60 x 85mm
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
Polyamide non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP40
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
F923 Series DC Current Transducer with Process Outputs & High and Low C/O Alarm
Features
Isolated measurement of DC currents using internal Hall effect transducer.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned DC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty. Otherwise 4-6 weeks
Specification
Oztherm Part Number
F923-X-XX-DC-XX
Functions
Single Phase AC Current Transducer
Supply Voltage
9-36VDC
Nominal Measurement Range
0-8 Amp (Sensor dependant)
Maximum Measurement Range
8 Amp
Alarm
C/O Relay 4Amp @ 30VDC, 0.5Amp @ 150VAC
Response Time
250mS
Accuracy @ 25 Deg C
Class 1
Bandwidth
DC - 1kHz
linearity
< 0.15%
Isolation
2.5kV
Comms
N/A
Weight
250g
Enclosure Size
79 x 60 x 85mm
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
Polyamide non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP40
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet