RCS-1800-0300 Three-Phase Flexible Current Sensor System (Rogowski Coils):
The RCS-1800 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-1800 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Suitable Alternative to Solar Edge CTRC-07500-0300
Specification
Magnelab Part Number
RCS-1800-0300
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
300 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 500 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
6 Inch
Coil Circumference
18 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
Trent 350BBF Series 690V, 350 Amp aR Semiconductor I²t Fuse BS88 Style
Features
British Standard Fuse Links Package
Wide Range of I²t
Ratings up to 1000 Amp
Busbar or Standoff Mounting
IEC Standard 60269.1 AND 4
690 V Voltage Rating complying with IEC 33
Applications
Protection of High Powered Semiconductors according to I²t
Short Circuit Protection
DC or AC Motor I²t Protection
Battery Fuse
Specification
Trent Part Number
350BBF
Fuse Type
I²t aR Class
Nominal Voltage
690VAC @ 50Hz
I²t Rating (IP < 30IN)
110000 A²/s
Nominal Current (RMS + DC)
350 Amp
Tested Breaking Capacity
200kA @ 690VAC
Dimensions
79.4 x 24 x 110mm
Hole Centers
75.2 x 93.6mm
Mounting Style
Busbar or Panel Mount with Standoff
Operating Temperature Range
-40°C / 125°C
Watt Loss
62W
Termination Style
M6
Unit Weight
400g
Factory Pack Qty
10
Datasheet
Product Datasheet
Cross Reference Chart
LEM DVL 1500 UI, Voltage Transducer 1500V Input, 4-20mA output, +/- 15V…24VDC, 8.5kV Isolation
Features
Bandwidth DC to 14kHz
Multi Range through pin selection
Closed loop transducer using Hall effect
Compact and versatile
Panel Mount
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
High accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Voltage overload capability
Low power consumption
Applications
Railway substation or locomotive
AC variable speed drives and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications
Water Treatment Electronics
Specification
LEM Part Number
DVL 1500 UI
Technology
Closed Loop Hall Effect
Aperture
No Aperture
ROHS
Yes
Supply Voltage
+/-15..24 VDC Bipolar, Isolated
Primary Nominal Voltage (RMS + DC)
+/- 1500V
Measurement Range
+/- 2250V
Output
4 - 20mA
Isolation
8.5 kV
Bandwidth
DC-14 kHz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
1%
Termination Style
M5 Screw
Unit Weight
270g
Factory Pack Quantity
4
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
Iskra Doo KNL90-00-240VAC, AC Contactor 240/400/500/690V, 3 Pole 3 x NO, Nominal Current = 90 Amps, 240VAC Coil
Capacitor duty contactors are designed to meet the requirements of capacitor duty applications. Contactors are fitted with a block of three auxiliary contacts connected in series with six quick discharge damping resistors, two per each phase. Peak current is limited to the value within the contactor making capacity.
Features :
High contact reliability at low voltages
High electrical and mechanical endurance and high switching capacity
Four and Three-pole contactors
Optional auxiliary contacts
Ratings from 6 Amp to 1000 Amp
UL, CSA Approved
Advantages :
Saves costs of expensive replacement
Long electrical life
Reduces watt losses during “ON” condition, saves energy
High safety
No risk of dangerous voltage
Less maintenance and downtime
Standard control voltages: 24 V 50/60 Hz, 240 V 50/60 Hz, 415 V 50/60 Hz
Specification
Iskra Doo Part Number
KNL90-00-240VAC
Functions
3 Pole Contactor (3 x NO)
Nominal Voltage
230/400/500/690VAC @ 50/60Hz
Current Carrying Capacity as per UL
90 Amp Continuous @ 55 Deg C
Auxiliary Contacts
Optional BFX10-40, 4 Pole Snap On Aux Contacts
Trip Delay Time
2-10ms
Electrical Life
1,200,000 Ops
Operating Temperature
-25 to 55 Deg C
Mechanical Operations
15,000,000 Ops
Control Voltage
240VAC
Power Dissipation
9.4W per pole
Approvals
UL, CSA
Standards
IEC/EN 60947-4-1, AS/NZ 61009-1
Weight
1.25kg
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
Contactor Catalogue
Iskra Contactor Catalogue
Crydom CKRD6030, Solid State Relay, Single Phase 3.5 - 32VDC Control, 30A, 48-660VAC Load, Din Rail
Features
Ratings from 10A to 30 Amp @ 48-530 VAC
SCR output for heavy industrial loads
Zero voltage or instantaneous turn-on outputs
UL/CSA/VDE Approved, CE Compliant to EN60950-1
Improved SEMS screw and washer
Redesigned housing with anti-rotation barriers
AC & DC control types
Direct bond copper substrate
EMC compliant to Level 3
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
CKRD6030
Switching Type
Zero Crossing
ROHS
Yes (Details)
Control Voltage
4 - 32VDC
Load Current
30 Amp (rms) @ 25 Deg C Ambient, 25.5 Amp (rms) @ 40 Deg C Ambient
Surge Capability
1200 Amp (peak)
Special Feature
None
Mounting Style
DIN Rail Mount
Load Voltage Range
48 - 660VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
280g
Factory Pack Qty
20
Datasheet
Product Datasheet
Alternatives
Contactor Style DR2260D35V
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
D53TP50D + HS212, Solid State Relay, and Heatsink Assembly, 3 Phase 4-32VDC Control, 20 Amp per phase @ 40 Deg C, 48-530VAC Load, LED Status Indicator
Features
Ratings from 25A to 50 Amp @ 70-530 VAC
SCR output for heavy industrial loads
Zero voltage or Instantaneous turn-on outputs
UL/CE/ROHS Approved
IP20 Cover Available
AC & DC control types
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
D53TP50D + HS212DR
Switching Type
Zero Crossing
ROHS/CE/UL
Yes
Control Voltage
4-32VDC
Load Current
3 x 20 Amp (rms) per Phase
Surge Capability
597 Amp (peak)
Special Feature
LED Status Indicator
Mounting Style
Panel Mount
Load Voltage Range
48-530VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
315g
Factory Pack Qty
10
Datasheet
D53TP Series
3 Phase SSR and Heatsink Mounted
HS212 Datasheet
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Fastron Electronics BTCD/R-M-A3-EI, PID Controller 96x96mm, 85-265VAC, Relay Output 3 Alarms, Event input (2xSV ), Multirange TC/RTD/4-20mA Input
4-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
Drip-proof / Dust-proof IP56 (front panel only)
CE Approved
Each unit needs just 80 mm depth panel space
Optional Pattern Control Feature
Specification
Fastron Part Number
BTCD/R-M-A3-EI
Control Output
Relay 3 Amp (Resistive)
Input
Multirange 4-20mA/RTD/Thermocouple (other linear inputs to be specified at time of order)
Option 1
2nd and 3rd Alarm
Option 2
Event Input (2 x SV)
Mounting Style
96 x 96mm Panel Mount
Load Voltage Range
100-240VAC
Termination Style
Screw
Weight
600g
Factory Pack Qty
1
CE
Yes
Datasheet
BTC Series Brochure
BTC Series User Manual
BTC Series RS485 Comms Manual
Fine Tuning PID Adjustments
Crydom CWA4890P, Solid State Relay, Single Phase 90-280VAC Control, 90A, 48-660VAC Load w/ Overvoltage Varistor
Features
Ratings from 25A to 125 Amp @ 48-660VAC
SCR output for heavy industrial loads
Zero voltage or instantaneous turn-on outputs
UL/CSA/VDE Approved, CE Compliant to EN60950-1
Improved SEMS screw and washer
Redesigned housing with anti-rotation barriers
AC & DC control types
Direct bond copper substrate
EMC compliant to Level 3
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
CWA4890P
Switching Type
Zero Crossing
ROHS
Yes (Details)
Control Voltage
24VAC (18-36VAC)
Load Current
90 Amp (rms)
Surge Capability
1350 Amp (peak)
Special Feature
LED Status Indicator, High Surge, MOV Overvoltage protection
Mounting Style
Panel Mount
Load Voltage Range
48-660VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
75g
Factory Pack Qty
20
Datasheet
Product Datasheet
Notifications
Please note Changes from Gen 3 to Gen 4 (current) package design here
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Crydom Series 1 HD6050-10, Solid State Relay, Single Phase 3-32VDC Control, 50A, 48-660VAC Load, Random Crossing
Features
Ratings from 25A to 125 Amp @ 24-280 VAC
SCR output for heavy industrial loads
Zero voltage or instantaneous turn-on outputs
UL/CSA/VDE Approved, CE Compliant to EN60950-1
Improved SEMS screw and washer
Redesigned housing with anti-rotation barriers
AC & DC control types
Direct bond copper substrate
EMC compliant to Level 3
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
HD6050-10
Switching Type
Random Crossing
ROHS
Yes (Details)
Control Voltage
3-32VDC
Load Current
50 Amp (rms)
Surge Capability
597 Amp (peak)
Special Feature
None
Mounting Style
Panel Mount
Load Voltage Range
48-660VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
75g
Factory Pack Qty
20
Datasheet
Product Datasheet
Notifications
Please note Changes from Gen 3 to Gen 4 (current) package design here
Equivalent
CY9008
CWD4890H
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Fastron FTM1-A80-V4-W0, Single Phase, Phase Angle/Burst Controller for Primary Control of Transformer (Phase Angle mode only), Voltage/Current/Power Limit Modes, For Single Phase Loads, 400VAC, 64 Amps @ 50 Deg C
Features
Phase Angle, Distributed Burst, and Time Proportional Burst Control Functions
Made in China, Low cost
Single Phase, Angle/Burst Controller
4-20mA/0-10V/0-5V input Proportional Control
Phase Angle or Burst switching
Digital Display and Controls
Applications
Electrical Ovens, Kilns, or Furnaces
HVAC Heaters
Controlled Power Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for HVAC or Industrial Environments
Specification
Fastron Part Number
FTM1-A80-V4-W0
Rated Operating Temperature
50°C
SCR Configuration
3 Phase AC Switch
Control Voltage
4-20mA/0-10V/0-5V/POT
Load Current
64 Amps Per Phase @ 50 Deg C
Derating
2% per 1 Deg C (approx)
Control Range
0-100%
Alarms
1 x NO Relay Contacts
Special Feature
Internal Fuse, Current Limit, Power Limit
Comms
N/A Optional
Mounting Style
Panel Mount
Switching Voltage Range
400VAC +/-10%
Supply Voltage
230VAC +/-10%
Dimensions
H:260mm W:94mm D:187mm
Soft Start
N/A
Termination Style
Screw
Unit Weight
2.5kg (4kg Packed)
Factory Pack Qty
1
Technical Docs
User Manual
Brochure
Video for How to Set Current/Voltage/Power limit
TPR-3SL040H, SCR Phase/Burst Controller FANLESS, 400VAC 3 Wire (400V L-L, 230V L-N), 3 Phase, 1-5V/4-20/0-20mA/10K POT Input, with In built Fuses, 32 Amps per Phase @ 50 Deg C
Features
Phase Angle, Distributed Burst, and Time Proportional Burst Control Functions
3 Phase, or Single Phase, Angle/Burst Controller
4-20mA/1-5V/10K POT Input Proportional Control
Fully enclosed IP20
Phase Angle or Burst switching
Aluminium/Plastic Frame
Removable Cover
Applications
Electrical Ovens, Kilns, or Furnaces
HVAC Heaters
Controlled Power Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for HVAC or Industrial Environments
Specification
Fastron Part Number
TPR-3SL040H
Rated Operating Temperature
50°C
SCR Configuration
3 Phase AC Switch
Control Voltage
4-20mA (Default), 0-5V, 10K POT)
Load Current
32 Amps Per Phase @ 50 Deg C
Derating
2% per 1 Deg C (approx)
Control Range
0-100%
Alarms
2 x NO Relay Contact
Comms
Optional RS485 Modbus RTU
Special Feature
Internal Fuse
Mounting Style
Panel Mount
Switching Voltage Range
400VAC +/-10%
Supply Voltage
100-240VAC +/-10%
Delay on Start
NA
Soft Start
Programmable from 0 to 60 seconds
Termination Style
Screw
Unit Weight
4kg (6kg Packed)
Factory Pack Qty
1
Technical Docs
User Manual