Fastron Electronics FESCT-3000-2500, 2500Amp 0.333V Class 1 Measurement Split Core CT's, 1M Flying Leads, 76x127mm Aperture
Features
Quick Release Split Core System
1m Flying Leads
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.60/3kV
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Electronics Part Number
FESCT-3000-2500
Technology
Split Core AC Current Transformer
Ratio
2500/0.333V
Aperture Size
76x127mm
VA Rating
N/A
Accuracy Class
Class 1
Output
0.333VAC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 55°C
Continuous Current (max)
2500Amp x 1.2
Termination Style
Terminals
Unit Weight
3000g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Crouzet 25622130, Style_8 Pin Socket for Din Rail or Panel Mounting, Suitable for Base of MDE or other 8 pin Timers
Specification
Crouzet Part Number
25622130
Nominal Voltage
12 → 240 VAC/DC
Style
DIN Rail or Panel Mount
Number of Pins
8
Isolation
1kV
Threshold Adjustment Range
10 → 100 % of the range
Termination Style
Screw terminals
Weight
70g
Certification
CE, cULus,CCC, ROHS, Reach, WEEE
Factory Pack Qty
1
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Datasheet
Product Datasheet
Fastron F41F-J/20P, Bridge Bar for up to 20 Pole F41F Slim Relays
Features
Rated for 6Amp @ 30VDC or 250VAC
Specification
Fastron Part Number
F41F-J/20P
Approvals
UL, CE
ROHS
Yes (Details)
Number of Poles
20
Load Current
6 Amp (rms) per Pole
Load Voltage Range
250VAC, 30VDC Load
Unit Weight
80g
Factory Pack Qty
100
Datasheet
Relay & Base Datasheet
F41F-1Z-C2-5 12-14VAC/DC Socket
Fastron Electronics AMB-A-V7-A-N, AC Voltage Panel Meter, 0-600VAC Input, 110-240VAC Supply, Large 4.1 Digit
Adjustable Zero and Span Setting
Adjustable Display Scaling
Large 4.1 Digit 20.3mm (8 Inch) LED Display
250mS Response Time
PC 94 UL V0
Each unit needs just 96 x 48mm Panel Space
90mm Depth
CE Approved
Specification
Fastron Electronics Part Number
AMB-A-V7-A-N
Transmission Output
N/A
Input
0-600VAC
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
100 - 240VAC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Display Type
4.1 Digit RED LED
Mounting Style
96 x 48mm Panel Mount
Case Material
PC - UL 94 V0
Weight
320g
Factory Pack Qty
1
Datasheet
Product Datasheet
Application Notes
Panel Meters Blog Articles
Fastron Electronics GBMA-4-DVO(0-150VDC)-ANNN, 140x420mm Digital Voltmeter, Panel Mount, 0-150V DC Input, 100-240VAC/DC supply, with IR Remote Control
Adjustable Zero and Span Setting
Adjustable Display Scaling
Remote Control Included
Wall Mount
LED Tile Display
Large 4 Digit 100mm (40 Inch) LED Display
250mS Response Time
PC 94 UL V0
100mm Depth
CE Approved
Specification
Fastron Electronics Part Number
GBMA-4-DVO(0-150VDC)-ANNN
Conditioner Output
N/A
Input
0-150VDC
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
140 x 420 mm Wall Mount
Case Material
PC - UL 94 V0
Weight
3.6kg
Factory Pack Qty
1
Datasheet
Product Datasheet
Application Notes
Panel Meters Blog Articles
Schurter 1241.1100.7098 MCS switch 18mm Square Panel Mount White
Description
Momentary action switch available with custom lettering, and in different colours
Snap in Assembly
Pin connections for Soldering
Characteristics
PES Thermoplastic Housing PBT Thermoplastic Bezel
Contacts material CuZn37 3 um Ni 2um Au; CuZn37 2.5 um Ag
Wide range of colours, lettering - Switching voltage max. 48 VDC, switching current max. 125 mA
Varnished Version Colour adjustments to customer housings possible, as standard
13/14mm Aperture Round, and Square versions available.
Specification
Schurter Part Number
1241.1100.7098
Switching Type
Momentary
Switch Size
Square 4 x 18mm (13 x 18mm total)
Switch Colour
White
Housing Colour
Black
Nominal Voltage
5-48VDC
Rated Power
0.72W
Rated Actuations
1-5 Million
Nominal Current (AC/DC)
125mA
Contact Resistance ON/OFF
<50m Ohm/ >100 M Ohm
Dimensions
ø18 x 13mm
Operating Temperature Range
-25°C / 60°C
Termination
Solder Terminals
IP Protection Rating
65 (Snap in)
Mounting
Snap in
Unit Weight
40g
Factory Pack Qty
10
Datasheet
Product Datasheet
Infineon/Siemens BSM600GA120DLC, IGBT Single, 600Amp, 1200V
Features
IGBT for Low Frequency Inverter
Pressure Contact Technology
Electrically insulated base plate
Wide Temperature Range
Medium Switching Speed
2500V Isolation
61mm Base Width
Applications
Frequency Converter
Line rectifying 50/60 Hz
Deep Cycle Applications
Controlled Rectifiers
Softstart AC motor control
Low Frequency Inverter
Drives
Specification
Infineon/Siemens Part Number
BSM600GA120DLC
Vces
1200V
Transistor Configuration
Single IGBT Module
Ic(nom) @ 60 Deg C
600 Amp
Package Size
W:61.4mm L:106.4mm D:30mm
V(isol)
2.5 kV
Vf @ 25 Deg C
1.8 - 2.3V
Tj(max)
150°C
Td(on) @ 25 Deg C
0.09uS
Td(off) @ 25 Deg C
0.54uS
I(ces) @ 25 Deg C
400nA
Rcc
N/A
Terminals
M6 Screw
Hole Centres
93 x 48mm(M6)
Gate Terminals
Spade (A 2.8 - 0.5mm)
R th(j-c)
0.09°C/W
R th(c-h)
N/A
Weight
500g
Mounting Torque
4 Nm (4 Nm Terminals)
Factory Pack Qty
10
Certification
UL Listed, ROHS
Infineon Headquarters
Germany
Datasheet
Product Datasheet
Alternatives
, Obsolete. Contact Us for Possible Replacement for alternative
SDM630Modbus-MID-V2-CL1 (SDM630-M), DIN Rail Mount kWh Meter, 3 Phase, Class 1, 100 Amp Direct Connect input, w/ 2 x pulse outputs and RS485 Comms, MID Approved
3 x 100 amp Direct Connect
RS 485 communication up to 38,400 bit/s as standard
Optional Mbus Model available
True RMS values of currents and voltages
2 x Pulse Outputs (1 Configurable)
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
Accuracy class 1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM630Modbus-MID-V2-CL1 (SDM630-M)
Functions
Three Phase Energy Meter
Supply Voltage
NA
Nominal Measurement Range
415V L-L 230V L-N, 100 Amp
Maximum Measurement Range
480V L-L 230V L-N, 100 Amp
Nominal Current Input
Direct connect 3 x 100 Amp
Pulse Output
2 x Passive, (1 x Configurable 60/100/200ms)
Tariff Input
N/A
Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Alternatives
WM3-6 230DB
Modbus Utility
EEM Meter Setting Software Utility
Magnelab DVT-1000-V05, DC Voltage Transducer, Din Rail Mount, 10-1000VDC, 5V output, 15-48VDC Supply Voltage, 10mS Response Conditioner or Transmitter
Adjustable Zero and Span Setting
10mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 5V DC output (for voltage output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Magnelab Part Number
DVT-1000-V05
Control Output
5V
Input
10 - 1000VDC
Measurement Range
120%
Overload
150% Continuous
Operating Temperature
-30 - 70°C
Operating Voltage
15 - 48VDC
Voltage Isolation (1 min)
4.5kV
Accuracy
1%
Response Time
10mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Safety
UL508C, CSA C22.2
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Fastron FRT8-M2/W240, Multifunction Timer 12-240 V AC/DC, 0.1s - 10 Days, 2 x SPDT 16 Amp C/O Contacts Replaces Elko CRM-91H,CRM-93H,CRM-9S
Features :
Multi-range (0.1s - 10days)
Multi-voltage 12 →240 V AC/DC
LED status indicator
Possibility of external load connection in parallel to the control input
Suitable replacement to Elko CRM-91H,CRM-93H,CRM-9S
Multifunction Timers Includes The Following :
A: A pulse after power-on or after the rising edge of trigger pulse S.
B: Delay after power-on or after the rising edge of trigger pulse S.
C: A pulse after power-on or after the rising edge of trigger pulse S. Retriggerable.
D: Delay after power-on or after the rising edge of trigger pulse S. Retriggerable.
E: The first edge of trigger pulse S turns relay on while the second edge starts counting down till relay off. Additional trigger S before the process is finished prolongs the on-state.
F: Each rising edge of trigger S appends additional period T to the time of on-state.
G: Pulsating operating with a starting pulse or pause which depends on the state of trigger S at power-on.
H: Bistable operating. Each rising edge of trigger S swaps the relay into the opposite state.
I: Prolonged pulse after power-on. The presence of trigger S temporarily stops counting.
J: Prolonged pause after power-on. The presence of trigger S temporarily stops counting.
Specification
Fastron Part Number
FRT 8-M2/W240
Function
Multifunction Timer
Nominal Voltage
12 → 240 V AC/DC
Digital Output
2 x C/O (SPDT) (Changeover -Single Pole), 250VAC/DC @ 16 Amp
Min Breaking Current
10mA/12VDC
Timing Ranges
Selectable 1s - 10 Days
Minimum Pulse Duration
30ms/100ms with load
Repeatability
0.5%
Reset Time
120ms
Isolation
4kV
Repetition Accuracy
0.5%
Threshold Adjustment Range
10 → 100 % of the range
Termination Style
Screw
Weight
80g
Factory Pack Qty
1
Certification
CE, RoHS
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
Fastron Monitoring/Time Relays Catalogue
For items in our catalogue which are not listed online please Contact Us for Possible Replacement
LEM AI-P1A Universal Integrator for Rogowski Coils, Multi Range Input (100 to 5000 Amp) and Output (0.333V,0.225), 1 Amp Output, Adjustable Sensitivity(22.5,70,80,85,100,120mV/kA), Din Rail Mount
The universal Rogowski coil integrator AI-P1A complements LEM’s flexible clip-around coil ART and ARU range. The design is based on digital processing to give combined dynamic range, accuracy and versatility of use. It offers a wide range of output signals both True RMS and instantaneous. AI-P1A is DIN rail mounted and can be stacked for multiphase application without spacing thanks to its low power dissipation. optional
Input signal
1 Amp output for Power Quality Measurements up to the 32nd Harmonic (1600Hz)
Accuracy Class 0.5 (IEC 61869-2) [1].
Linearity error ? 0.10 %. Protection degree IP2X.
35 mm DIN rail mounted.
Push-in terminals.
6 selectable sensitivities depending on Rogowski coil: 22.5, 70, 80, 85, 100, 120 mV/kA at 50 Hz.
12 selectable ranges: 100, 200, 300, 400, 500, 600, 800, 1000, 1500, 2000, 4000, 5000 A.
Ambient operating temperature ?25...+70 °C.
Advantages
Compact design for DIN rail assembly
High accuracy Class 0.5 (IEC 61869-2)
Setup by user via Select / Edit buttons
Clear status indication via bi-color led
Applications
MV/LV substations on LV side: Transformer Condition Monitoring
Power metering: current measurement for active power calculation
Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation
Power quality monitoring: electrical loads and distribution system equipment
Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault
Remote Terminal Units (RTU)
Phasor Measurement Units (PMU)
Standards
IEC 61010-1: 2010
UL
EMC: IEC 61326-1:2012
Options
Cross power plugin connector: side contacts to stack up to 3 Integrator modules and use only one power supply.
24VDC Power Supply Meanwell HDR-30-24
Specification
LEM Part Number
AI-P1A
Function
Integrator and True RMS Conditioner for Rogowski Coils
Measuring Range
Selectable 5000,4000,2000,1500,1000,800,600,500,400,300,200,100Amp
Sensitivity
Selectable 22.5,70,80,85,100,120mV/kA @ 50 Hz
Output
1 Amp AC
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
10-32VDC
Accuracy
0.5% from 25 to 5000 Amp
Current Consumption
350mA (max)
Dimensions
100mm x 78mm x 15mm
Mounting
Din Rail Mount
Integrator to Meter cable
User Supplied Shielded cable 6mm sqr, up to 6m long
Operating Temperature
-25°C - 70°C
Storage Temperature
-45°C to 80°C
Isolation (50Hz, 1 min)
1.5kV
True RMS Response Time
160-190ms
Termination Style
Push-in for 1.5mm sqr wire
Weight
58g
Factory Pack Qty
1
Certifications
UL, ROHS
Datasheet
Product Datasheet
Application Notes
User Notice
1) The Rogowski coil can measure any primary current as there is no saturation effect.
2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts)
3) Frequency bandwidth and phase shift modelling schematic can be provided on request.
4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5) Considering a primary conductor of at least ? 15 mm, perpendicular and in contact with the Rogowski coil.
6) Considering an external conductor of at least ? 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.