Fastron Electronics SCT-F50-1000-5A, 5 Amp, 1000Amp measurement Split Core CT's
Features
Quick Release Split Core System
Cable Mount
5 Amp Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F50-1000-5A
Technology
Split Core AC Current Transformer
Ratio
1000/5 Amp
Aperture Size
ø 50 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
5 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
1000Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
1000g
Factory Pack Qty
9
Datasheet
Product Datasheet
Stocked Split Core CT's Listing
Application Notes
Installation Guide
Types of Current Transformers - Blog
Cable Losses and CT's
High Accuracy or High Burden Requirements for CT's
Fastron Electronics SCT-Y36-400A-100mA, 400A/100mA Measurement, Class 1 Split Core CT's, 36mm Aperture, with HY2.0 Connector for Eastron Meter EasyClick System
Features
Quick Release Split Core System
Cable Mount
100mAmp Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads with HY-2.0 Connector
Applications
Eastron Modular Metering Equipment
Energy Monitoring
Load Balancing
Power Quality Measurements
Specification
Fastron Part Number
SCT-Y36-400A-100mA
Technology
Split Core AC Current Transformer
Ratio
400/100mA
Aperture Size
ø 36 mm
VA Rating
1VA
Accuracy Class
Class 1
Output
100mA (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
400Amp x 1.2
Termination Style
0.9M Flying leads with HY-2.0 Connector
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
CRJ-31 Connector User Guide
Fastron Electronics FESCT-32-400-0.333V, 400Amp measurement Split Core CT's, w/1M Flying leads, 32x32mm Aperture, 0.333v Class 1 Series Current Transformer
Features
Quick Release Split Core System
1m Flying Leads
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.60/2kV
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
FESCT-32-400-0.333V
Technology
Split Core AC Current Transformer
Ratio
400/0.333V
Aperture Size
32 x 32mm
VA Rating
N/A
Accuracy Class
Class 1
Output
0.333VAC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 55°C
Continuous Current (max)
400Amp x 1.2
Termination Style
1M Twisted Pair 0.34mm^2
Unit Weight
350g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Fastron Electronics GTD-V5-D-44, Signal Isolator/DC Voltage Transducer, 0-36VDC Input, 2 x 0-10V Output, 22-60VAC/DC
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted from 4 to 20 mA DC Loop Supply (Sensor Input) to insulated 4-20mA Standard Process Output
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
GTD-V5-D-44
Control Output
2 x 0-10V
Input
0-36VDC
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
22-60VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Fastron Electronics AM5S-C-N2-D-N, 48x24mm Digital Totaliser 7kHz, NPN 12VDC, 22-60VAC/DC supply
Large 5 Digit 0.4 Inch LED Display
250mS Response Time
PC 94 UL V0
Input signals can be NPN, PNP, or 24VDC Pulses depending on the model used
Each unit needs just 48 x 24mm Panel Space
86.2mm Depth
Specification
Fastron Electronics Part Number
AM5S-C-N2-D-N
Input
NPN 12VDC
Measurement Range
0 - 7kHz
Operating Temperature
0 - 60°C
Load Voltage
22-60VAC/DC
Termination Style
Screw
Mounting Style
48 x 24mm Panel Mount
Case Material
PC - UL 94 V0
Safety Approvals
CE
Weight
320g
Factory Pack Qty
1
Datasheet
Product Datasheet
Application Notes
Panel Meters Blog Articles
FP040080P, 400/5 Amp Split Core CT, Class 0.5 1.5VA Series Clip On Current Transformer
Features
Quick Release Split Core System
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
IEC185, BS 7626, BSEN 60044-1 and IEC 60044-1
Applications
Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
FP040080P
Technology
Split Core AC Clip On Current Transformer
Ratio
400/5
Aperture Size
50 x 80mm
VA Rating
1.5VA
Accuracy Class
Class 0.5
Output
5 Amp AC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10°C / 50°C
Continuous Current (max)
400Amp x 1.2
Termination Style
Screw
Approvals
CE
Unit Weight
1150g
Factory Pack Qty
1
Datasheet
Product Datasheet
Installation Guide
Fastron Electronics FESCT-075-1000-1-IP65, 1000Amp Measurement, 1 Amp Output Split Core CT's, Class 1, 7.5VA, 7.5VA, w/10M Flying leads, ø 55mm Aperture
Features
Quick Release Split Core System
10m Flying Leads
ø 75mm
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.60/3kV
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurement, 1 Amp Outputs
Specification
Fastron Electronics Part Number
FESCT-075-1000-1-IP65
Technology
Split Core AC Current Transformer
Ratio
1000/5A
Aperture Size
ø 75mm
VA Rating
7.5VA
Accuracy Class
Class 1
Output
1 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Dimensions
180x138x52mm
Mounting Style
Panel Mount
Operating Temperature Range
-35°C / 55°C
Continuous Current (max)
1000Amp x 1.2
Termination Style
10M Twisted Pair 0.34mm^2
Unit Weight
2000g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Fastron Electronics GTD-T/TO(0-150)/A1 PT100 to 4-20mA Signal Conditioner or Transmitter
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
GTD-T/TO(0-150)/A1(0-20mA)
Control Output
4-20mA
Input
RTD (Pt100)
Over Range
N/A
Operating Temperature
0 - 60°C
Load Voltage
100 - 240VAC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Fastron Electronics GTD-DV6-D-11, DC Voltage Transducer, 0-300VDC input, 22-60VAC/DC aux, Dual 4-20mA outputs
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
GTD-DV6-D-11
Conditioned Output
2 x 4-20mA (Average RMS)
Input
0 - 300VDC
Over Range
x 1.5
Operating Temperature
0 - 60°C
Load Voltage
22-60VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Fastron Electronics GTD-V4-A-44, Signal Conditioner/Voltage Transducer, 0-10VDC input, 100-240VAC/DC aux, Dual 0-10VDC outputs
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
GTD-V4-A-44
Conditioned Output
2 x 0-10V
Input
0-10V
Over Range
x 1.5
Operating Temperature
0 - 60°C
Load Voltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Fastron Electronics GT-II3-D-1, Resistance Transducer, 0-1kOhm input, 22-60VAC/DC aux, 4-20mA output
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
GT-II3-D-1
Control Output
4-20mA
Input
0-1 k Ohm
Over Range
x 1.5
Operating Temperature
0 - 60°C
Load Voltage
22 - 60VDC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Northern Design Cube 400-M2-C Series 3 Phase Power Meter
Optional 2 Pulse Input or Outputs
Nominal current up to 6 A (For 5A CT Input) and nominal voltage up to 240V L-N
Three Line Display
Optional RS 232/RS 485 communication up to 19,200 bit/s
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Optional THD up to 15th Harmonic
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 1
Simple Menu
Optional RS 232/RS 485 communication up to 19,200 bit/s or Ethernet communication
MODBUS and Ethernet communication protocol
240V AC power supply
Specification
Northern Design Part Number
Cube 400-M2-C
Functions
kWh Meter, Energy Meter
Supply Voltage
240VAC < 5VA
Nominal Measurement Range
415V L-L 240V L-N, 5 Amp
Maximum Measurement Range
415V L-L 280V L-N, 6 Amp
Display
Three Line LCD
Pulse Output
2 (input or output)
Accuracy
Class 1 (kW,kWh) Class 1(Active) Class 2(kVar,PF)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Ethernet
Modbus RTU Over TCP/IP 2400-19200 b/s
Weight
350g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Product Manual
Product Comms Manual
Application Notes
Dual Tariff Guide
CT Cable Losses
Meter Accuracy at Low Current
Current Input Isolation