W0642WC180, Rectifier Diode, PUK, 477 Amp, 1800V, 41/14
Features
Very low forward voltage drop
Very low leakage current
International standard package
41/14 Package
Press Mounted
Double or Single Sided Cooling
Applications
Power Supplies
Rectifier for drives applications
Uncontrolled Rectifiers
Rectifiers for UPS
Battery Chargers
Field Supply for DC Motors
Water Cooled Rectifiers
DC Substation Blocking Diode
Large Generators
Specification
Westcode Part Number
W0642WC180
Vrrm
600V
Diode Configuration
Diode Capsule (PUK)
IF(av) @ 100 Deg C
477 Amp
Package Size
ø41 x 14mm
Itsm
151 kA
VF(to)
0.99V
Tj(max)
180°C
rF
0.74mΩ
Gate Terminals
N/A
R th(j-k) (double sided cooled 180°sin)
0.09°C/W
R th(c-h) (double sided cooled)
Weight
75g
Clamping Force
3.3 - 5.5kN
Factory Pack Qty
12
Certification
ROHS
Westcode IXYS Headquarters
UK - USA
Datasheet
Product Datasheet
Alternatives
Contact Us for Possible Replacement
Heatsink
Heatsink Profiles
Semikron SKKD91/16E, Dual Diode Module, 91 Amp, 1600V
Features
Thyristor for line frequency
Solder - Solder Bonded
Electrically insulated base plate
Industrial standard package
3600V Isolation
22mm Base Width
Applications
Power Converter
Line rectifying 50/60 Hz
Controlled Rectifiers
Softstart AC motor control
AC power control
Lighting and temperature control
Specification
Semikron Part Number
SKKD91/16E
Vrrm
1600V
Diode Configuration
Dual Diode Module
IF(av) @ 112 Deg C
100 Amp
Package Size
W:22mm L:93mm D:30mm TO-240AA
Tj(max)
150°C
I(gt) @ 25 Deg C
N/A
Terminals
M5 Screw
Hole Centres
80mm (M6)
Weight
75g
Mounting Torque
4 Nm (3 Nm Terminals)
Factory Pack Qty
10
Certification
UL Listed, ROHS
Country of Origin
India
Datasheet
Product Datasheet
Alternatives
See VSKD91/16 DD89N14K or DD104N14K for Infineon Alternative
Gigavac HX460CAA, Contactor SPST-NO 1000 AMP, 1500VDC, 24VDC Coil, 38cm Flying leads, with SPDT Auxiliary Contact 5000 Cycles, IP67, IP69
Features
Hermetically Sealed (Patented) rated to 175 Deg C
UL1604 for Class I & II Div 2 and Class III for use in hazardous locations
IP67 & IP69
SAE J1171 External ignition protection
ISO8846 Protection against ignition around flammable gasses
CE Approved
High Efficiency Dual DC Coils - Very low 12,24,48VDC continuous coil power with no EMI emissions or cross-talk on your system control power
Ideal for battery powered systems or where low power is needed
PWM option provides additional drive control flexibility
Built in Coils suppression for all DC Coils
Flexible package for installation
Chassi level power terminals
Specification
Gigavac Part Number
HX460CAA
Main Contact Type
SPST-NO
Auxiliary Contact Type
SPDT 1NO+1NC
Coil Voltage
24VDC
Load Current
1000 Amp
Mechanical Life @ 0 Amp
100,000 Operations
Dielectric at Sea Level (leakage <1mA)
5.375kV rms
Control Input Terminals
38cm Flying Leads
Aux Contact Terminals
38cm Flying Leads
Special Feature
N/A
Mounting Style
Panel Mount (M6)
Load Voltage Range
1500VDC
Standards
UL1604, IP67, IP69, SAE J1171, ISO8846
Termination Style
M12
Unit Weight
4.17kg
Factory Pack Qty
1
Datasheet
Product Datasheet
VFD17AMS43ANSAA, 3 Phase Variable Frequency Drive, 460VAC, 7.5kW, 17 Amp (Normal Duty)/20.5 Amp (Heavy Duty), 460VAC L-L, 0.1-599 Hz, 250x130x219mm
Features
3 Phase VFD/VSD
4-20mA, 0-5V, 0-10V Proportional Input Control
7 x Digital Input
2 x STO Inputs
Fully enclosed IP20 (Optional IP40)
Small frame Size
Applications
Fan Motor Control
Production Lines
Transportation
Controlled Power Applications
Suitable for extreme environments such as mining
Specification
Delta Part Number
VFD17AMS43ANSAA
Rated Operation Temperature
50°C (With Derating)
Configuration
3 Phase AC Drive
Control Voltage
4-20mA, 0-20mA, 0-10V
Digital Inputs
7 x Mix / 2 x STO
Load Current
17 Amp(Normal Duty) / 20.5 Amp(Heavy Duty) Per Phase
Control Range
0.1-599 Hz
Dimensions
207x109x187mm
Mounting Style
Panel Mount
Supply Voltage Range
323-528VAC
Soft Start
0-6000s
Termination Style
Screw
Unit Weight
4.5kg
Factory Pack Qty
1
Datasheet
MS300 Brochure
User Manual
H71/110M + D53TP50D Three Phase Solid State Relay 4-32VDC Control, 3 x 13Amp, 48-530VAC Load
Ratings from 25A to 50 Amp @ 70-530 VAC
SCR output for heavy industrial loads
Zero voltage or Instantaneous turn-on outputs
UL/CE/ROHS Approved
IP20 Cover Available
AC & DC control types
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Specification
Crydom Part Number
H71/110M + D53TP50D
Switching Type
Zero Crossing
ROHS/CE/UL
Yes
Control Voltage
4-32VDC
Load Current
3 x 13 Amp (rms) per Phase @ 50 Deg C
Surge Capability
597 Amp (peak)
Special Feature
LED Status Indicator
Mounting Style
Din Rail Mount
Load Voltage Range
48-530VAC
EMC Compliant
Level 3
Dimensions
L:110mm x W:100mm x D:90mm
Termination Style
Screw
Weight
650g
Factory Pack Qty
10
Datasheet
H71 Datasheet
D53TP Series
Product Notifications
Please note Changes from Gen 3 to Gen 4 (current) package design here
Iskra Doo KNL75-11-415VAC, AC Contactor 240/400/500/690V, 3 Pole 3 x NO, with 1 x NO 1 x NC Aux Contacts, Nominal Current = 75 Amps, 415VAC Coil
Capacitor duty contactors are designed to meet the requirements of capacitor duty applications. Contactors are fitted with a block of three auxiliary contacts connected in series with six quick discharge damping resistors, two per each phase. Peak current is limited to the value within the contactor making capacity.
Features :
High contact reliability at low voltages
High electrical and mechanical endurance and high switching capacity
Four and Three-pole contactors
Optional auxiliary contacts
Ratings from 6 Amp to 1000 Amp
UL, CSA Approved
Advantages :
Saves costs of expensive replacement
Long electrical life
Reduces watt losses during “ON” condition, saves energy
High safety
No risk of dangerous voltage
Less maintenance and downtime
Standard control voltages: 24 V 50/60 Hz, 240 V 50/60 Hz, 415 V 50/60 Hz
Specification
Iskra Doo Part Number
KNL75-11-415VAC
Functions
3 Pole Contactor (3 x NO, with 1 x NO, 1 x NC Aux Contacts)
Nominal Voltage
230/400/500/690VAC @ 50/60Hz
Current Carrying Capacity as per UL
75 Amp Continuous @ 55 Deg C
Auxiliary Contacts
3 x NO, with 1 x NO, 1 x NC Aux Contacts (6 Amp) Optional NDL4-40, 4 Pole Snap On Aux Contacts
Trip Delay Time
2-10ms
Electrical Life
500,000 Ops
Operating Temperature
-25 to 55 Deg C
Mechanical Operations
10.000,000 Ops
Control Voltage
415VAC
Power Dissipation
6W per pole
Approvals
UL, CSA
Standards
IEC/EN 60947-4-1, AS/NZ 61009-1
Weight
950g
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
Contactor Catalogue
Iskra Contactor Catalogue
Shinko BCD2R1006 Series Digital Indicating Controllers
• Program control, converter function are standard features
• 5-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
• Drip-proof / Dust-proof IP66 (front panel only)
• 9-step pattern (for SV and time) is a standard feature
• UL/CSA Approved
• Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
• Each unit needs just 60 mm depth panel space
• EC Compliant (Details)
Specification
Shinko Part Number
BCD2R1006
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Input
Multirange (refer to datasheet)
Option 1
None
Option 2
RS485
Mounting Style
96 x 96mm Panel Mount
Load Voltage Range
24VAC/DC
Termination Style
Screw
Weight
170g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CE
Yes
Datasheet
BC Series Brochure
BC Series User Manual
BC Series RS485 Comms Manual
Shinko Product Guide
Fine Tuning Adjustments
Fastron TC5-H-1A-2-T/R-2 PID Controller, 100-240VAC with 2 3 Amp Relay Alarms, K,E,J Thermocouple, Pt100 or Cu20, Optional Linear Current/Voltage, 48x96mm,4-20mA Output
4-digit displays (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated -0-10V, Relay, 12VDC (SSR) and 4 to 20 mA DC outputs available
Each unit needs just 75 mm depth panel space
Now available will full Multirange input (K,E,J Thermocouple, Linear Current/Voltage and PT100/Cu20 RTD Input, 96x48mm,4-20mA Output)
Specification
Fastron Part Number
TC5-H-1A-2-T/R-2
Control Output
4-20mA
Input
Multirange Type,K,E,J, Pt100, Cu50/(Optional)Linear Current 4(0)-20mA/(Optional)Linear Voltage 0-10(5)V
Option 1
2 3 Amp Relay Alarms standard (Excludes 48x96mm with SSR/Relay output)
Mounting Style
96x48mm Panel Mount
Supply Voltage
100 - 240VAC +/-10%
Termination Style
Screw
Sampling Time
100ms
Weight
150-270g
Factory Pack Qty
10
Datasheet
TC5 Datasheet and User Manual
Iskra Doo KNL75-11-240VAC, AC Contactor 240/400/500/690V, 3 Pole 3 x NO, with 1 x NO 1 x NC Aux Contacts, Nominal Current = 75 Amps, 240VAC Coil
Capacitor duty contactors are designed to meet the requirements of capacitor duty applications. Contactors are fitted with a block of three auxiliary contacts connected in series with six quick discharge damping resistors, two per each phase. Peak current is limited to the value within the contactor making capacity.
Features :
High contact reliability at low voltages
High electrical and mechanical endurance and high switching capacity
Four and Three-pole contactors
Optional auxiliary contacts
Ratings from 6 Amp to 1000 Amp
UL, CSA Approved
Advantages :
Saves costs of expensive replacement
Long electrical life
Reduces watt losses during “ON” condition, saves energy
High safety
No risk of dangerous voltage
Less maintenance and downtime
Standard control voltages: 24 V 50/60 Hz, 240 V 50/60 Hz, 415 V 50/60 Hz
Specification
Iskra Doo Part Number
KNL75-11-240VAC
Functions
3 Pole Contactor (3 x NO, with 1 x NO, 1 x NC Aux Contacts)
Nominal Voltage
230/400/500/690VAC @ 50/60Hz
Current Carrying Capacity as per UL
75 Amp Continuous @ 55 Deg C
Auxiliary Contacts
3 x NO, with 1 x NO, 1 x NC Aux Contacts (6 Amp) Optional NDL4-40, 4 Pole Snap On Aux Contacts
Trip Delay Time
2-10ms
Electrical Life
500,000 Ops
Operating Temperature
-25 to 55 Deg C
Mechanical Operations
10.000,000 Ops
Control Voltage
240VAC
Power Dissipation
6W per pole
Approvals
UL, CSA
Standards
IEC/EN 60947-4-1, AS/NZ 61009-1
Weight
950g
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
Contactor Catalogue
Iskra Contactor Catalogue
Iskra BI432-31-230VAC, Four Pole 3 x SPST NO Configuration_SPST (1 x NC) Bistable Switch/Latching Relay with Manual Control, 440VAC, 32 Amp 230VAC Coil Voltage (Resistive)
Features
32 Amp (rms) @ 440VAC/18 Amp @ 24VDC/10 Amp @ 48VDC/4 Amp @ 60VDC/1.2 Amp @ 110VDC/0.3 Amp @ 220VDC
DIN Rail Mount
Changeover Contact
Zero Power Consumption in "ON State"
Slim package
CE Compliant to IEC 60664
IP20
Specification
Fastron Part Number
BI432-31-230VAC
Switch/Latching Relay Type
3 x SPST NO Configuration_SPST (1 x NC) 440VAC/220VDC
Approvals
CE
Coil Voltage
230VAC
Load Current (RMS/DC)
32 Amp (rms) @ 440VAC/18 Amp @ 24VDC/10 Amp @ 48VDC/4 Amp @ 60VDC/1.2 Amp @ 110VDC/0.3 Amp @ 220VDC
Special Feature
With Manual Control
Mounting Style
DIN Rail Mount
Load Voltage Range
32 Amp (rms) @ 440VAC/18 Amp @ 24VDC/10 Amp @ 48VDC/4 Amp @ 60VDC/1.2 Amp @ 110VDC/0.3 Amp @ 220VDC
Isolation
4kV
Termination Style
Screw
Unit Weight
195g
Factory Pack Qty
20
Datasheet
Relay Datasheet
Iskra Doo KC40-12-230-50, Capacitor Duty Contactor 240/480/600VAC @ 20, 40, 50 kVar, 100,000 Operations, AC-6B
Capacitor duty contactors are designed to meet the requirements of capacitor duty applications. Contactors are fitted with a block of three auxiliary contacts connected in series with six quick discharge damping resistors, two per each phase. Peak current is limited to the value within the contactor making capacity.
Features :
Capacitor Duty
Discharge Resistors
Three-pole contactors
Seven ratings from 12,5 kVAr to 60 kVAr
IEC 60947-4-1 for AC-6b utilization category
UL Approved
Advantages :
Conforms to utilization category AC-6b
Saves costs of expensive replacement
Long electrical life
Reduces watt losses during “ON” condition, saves energy
High safety
No risk of dangerous voltage
Switching of capacitor bank in parallel without de-rating
Less maintenance and downtime
Standard control voltages: 24 V 50/60 Hz, 220 V 50/60 Hz, 230 V 50/60 Hz, 415 V 50/60 Hz
Specification
Iskra Doo Part Number
KC40-12-230-50
Functions
3 Pole Capacitor Duty Contactor
Nominal Voltage
230/480/600VAC @ 50Hz
Current Carrying Capacity as per UL
20kVar/Amp @230VAC, 40kVar/Amp@480VAC, 50kVar/Amp@600VAC, AC-6B
Auxiliary Contacts
1 x NO and 2 x NC
Trip Delay Time
2-10ms
Electrical Life
100,000 Ops
Operating Temperature
-25 to 40 Deg C
Mechanical Operations
1,000,000 Ops
Control Voltage
230VAC
Power Dissipation
4.2W
Approvals
UL
Standards
IEC/EN 60947-4-1, AS/NZ 61009-1, AC-6B
Weight
200g
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog