Fastron Electronics SCT-F24-100, 100/5 Amp Class 1 Series Current Transformer
Features
Quick Release Split Core System
Cable Mount
5 Amp Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F24-100-5A
Technology
Split Core AC Current Transformer
Ratio
100/5 Amp
Aperture Size
ø 24 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
5 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
100Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Fastron Electronics FESCT-51-600-0.333V, 600Amp measurement Split Core CT's, w/1M Flying leads, 51x51mm Aperture Class 1 Series Current Transformer
Features
Quick Release Split Core System
1m Flying Leads
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.60/3kV
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Electronics Part Number
FESCT-51-600-0.333V
Technology
Split Core AC Current Transformer
Ratio
600/0.333V
Aperture Size
51 x 51mm
VA Rating
N/A
Accuracy Class
Class 1
Output
0.333VAC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 55°C
Continuous Current (max)
600Amp x 1.2
Termination Style
1M Twisted Pair 0.34mm^2
Unit Weight
950g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Schurter 4747.0000, Distribution Unit with IEC Appliance Inlet C14/M to 4 x C14/F Outlet, Snap-in Mounting, Front Side, Quick connect terminals 4.8 x 0.8 mm, 2mm panel Thickness
Features
1 x C14 Male in 4 x C14 Female out, Ganged Distribution Outlet
C14 Socket acc to IEC 60320-1
70 °C pin Temperature
Suitable for use in equipment according to IEC/UL 60950
Characteristics
UL 60320-1, CSA C22.2 no. 60320-1 (for hot conditions) pin-temperature 70 °C, 10A, Protection Class I
Types for enhanced glow wire test requirements acc. IEC 60695-2- 12 and -13 for the use in unattended household equipment acc. IEC 60335-1
Specification
Schurter Part Number
4747.0000
Rated Voltage
250V
Rated Current
10A (CE) 15A (UL/CSA)
No of Outlets
4
Operating Temperature
-25°C to 120°C
Filter Type
N/A
Fuse Holder
N/A
Line Switch
N/A
Mounting
Loose
Material
Thermoplastic, black, UL 94V-0
Termination Style
1 x C14 Male Inlet, 4 x Female C14 Outlet
Weight
550g
Factory Pack Qty
1
Protection Class
From front side IP30 acc. to IEC 60529
Isolation
2kV (L-N, L/N-E)
VDE/UL/CSA/CE/ROHS
Yes
Datasheet
Product Datasheet
Crydom CKRD6030, Solid State Relay, Single Phase 3.5 - 32VDC Control, 30A, 48-660VAC Load, Din Rail
Features
Ratings from 10A to 30 Amp @ 48-530 VAC
SCR output for heavy industrial loads
Zero voltage or instantaneous turn-on outputs
UL/CSA/VDE Approved, CE Compliant to EN60950-1
Improved SEMS screw and washer
Redesigned housing with anti-rotation barriers
AC & DC control types
Direct bond copper substrate
EMC compliant to Level 3
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
CKRD6030
Switching Type
Zero Crossing
ROHS
Yes (Details)
Control Voltage
4 - 32VDC
Load Current
30 Amp (rms) @ 25 Deg C Ambient, 25.5 Amp (rms) @ 40 Deg C Ambient
Surge Capability
1200 Amp (peak)
Special Feature
None
Mounting Style
DIN Rail Mount
Load Voltage Range
48 - 660VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
280g
Factory Pack Qty
20
Datasheet
Product Datasheet
Alternatives
Contactor Style DR2260D35V
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Fastron Electronics FESCT-19-300-0.333V, 300Amp measurement Split Core CT's, w/1M Flying leads, 19x19mm Aperture, 0.333v Class 1 Series Current Transformer
Features
Quick Release Split Core System
1m Flying Leads
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.60/3kV
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
FESSCT-19-300-0.333V
Technology
Split Core AC Current Transformer
Ratio
300/0.333V
Aperture Size
19 x 19mm
VA Rating
N/A
Accuracy Class
Class 1
Output
0.333VAC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 55°C
Continuous Current (max)
300Amp x 1.2
Termination Style
1M Twisted Pair 0.34mm^2
Unit Weight
350g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
TSG-V (ZKG-2000)High quality and high accuracy voltage regulator /Intelligent voltage regulator for SCR or SSR Control (choose one model)
Technical data:
Output impulse: Breadth value ≥ 3v, width ≥ 50us; S (when the load resistance is 20ohm)
Voltage setting range: 0-200v(or the voltage range you want)
Working environment: Temperature 0-50 degrees celcius, relative humidity does not exceed 85%, non-corrosive environment.
Power supply: AC 220v+/-15%, 50Hz+/-1Hz; About 3va
Size: TSG-V 48x48x88mm TSA-V96*96*100mm TSD-V72*72*100mm
TSG-2V 48*48*88(two voltage regulator in one unit)
Voltage setting range: 0-200v(or the voltage range you want)
Datasheet
Wiring Diagram
User Manual
TSG-V Manual
Required Accessories
Solid State relay and Heatsink is required sized large enough for the maximum continuous current of the load to be voltage regulated.
See here for complete list of possible combinations
Iskra Doo KNL18-10-240VAC Contactor
Capacitor duty contactors are designed to meet the requirements of capacitor duty applications. Contactors are fitted with a block of three auxiliary contacts connected in series with six quick discharge damping resistors, two per each phase. Peak current is limited to the value within the contactor making capacity.
Features :
High contact reliability at low voltages
High electrical and mechanical endurance and high switching capacity
Four and Three-pole contactors
Optional auxiliary contacts
Ratings from 6 Amp to 1000 Amp
UL, CSA Approved
Advantages :
Saves costs of expensive replacement
Long electrical life
Reduces watt losses during “ON” condition, saves energy
High safety
No risk of dangerous voltage
Less maintenance and downtime
Standard control voltages: 24 V 50/60 Hz, 240 V 50/60 Hz, 415 V 50/60 Hz
Specification
Iskra Doo Part Number
KNL18-10-240VAC
Functions
4 Pole Contactor
Nominal Voltage
230/400/500/690VAC @ 50/60Hz
Current Carrying Capacity as per UL
18 Amp Continuous @ 55 Deg C
Overload Capability
144(10s), 170(5s), 200(1s), 500(0.001s)
Auxiliary Contacts
4 x NO
Trip Delay Time
2-10ms
Electrical Life
200,000 Ops
Operating Temperature
-25 to 40 Deg C
Mechanical Operations
10.000,000 Ops
Control Voltage
240VAC
Power Dissipation
0.36W
Approvals
UL, CSA
Standards
IEC/EN 60947-4-1, AS/NZ 61009-1
Weight
200g
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
Contactor Catalogue
Iskra Contactor Catalogue
Iskra Doo KNL38-00-240VAC, AC Contactor 240/400/500/690V, Overload 304(10s), 320(5s), 350(1s), 900(0.001s) (each pole), 240VAC Control Voltage, 3 Pole 3 x NO, Nominal Current = 38 Amps
Capacitor duty contactors are designed to meet the requirements of capacitor duty applications. Contactors are fitted with a block of three auxiliary contacts connected in series with six quick discharge damping resistors, two per each phase. Peak current is limited to the value within the contactor making capacity.
Features :
High contact reliability at low voltages
High electrical and mechanical endurance and high switching capacity
Four and Three-pole contactors
Optional auxiliary contacts
Ratings from 6 Amp to 1000 Amp
UL, CSA Approved
Advantages :
Saves costs of expensive replacement
Long electrical life
Reduces watt losses during “ON” condition, saves energy
High safety
No risk of dangerous voltage
Less maintenance and downtime
Standard control voltages: 24 V 50/60 Hz, 240 V 50/60 Hz, 415 V 50/60 Hz
Specification
Iskra Doo Part Number
KNL38-00-240VAC
Functions
3 Pole Contactor (3 x NO)
Nominal Voltage
230/400/500/690VAC @ 50/60Hz
Current Carrying Capacity as per UL
38 Amp Continuous @ 55 Deg C
Overload Capability
304(10s), 320(5s), 350(1s), 900(0.001s)
Auxiliary Contacts
Optional Snap On 4 Pole NPL3
Trip Delay Time
2-10ms
Electrical Life
200,000 Ops
Operating Temperature
-25 to 55 Deg C
Mechanical Operations
10.000,000 Ops
Control Voltage
240VAC
Power Dissipation
2.3W
Approvals
UL, CSA
Standards
IEC/EN 60947-4-1, AS/NZ 61009-1
Weight
200g
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
Contactor Catalogue
Iskra Contactor Catalogue
Iskra Doo KNL90-00-240VAC, AC Contactor 240/400/500/690V, 3 Pole 3 x NO, Nominal Current = 90 Amps, 240VAC Coil
Capacitor duty contactors are designed to meet the requirements of capacitor duty applications. Contactors are fitted with a block of three auxiliary contacts connected in series with six quick discharge damping resistors, two per each phase. Peak current is limited to the value within the contactor making capacity.
Features :
High contact reliability at low voltages
High electrical and mechanical endurance and high switching capacity
Four and Three-pole contactors
Optional auxiliary contacts
Ratings from 6 Amp to 1000 Amp
UL, CSA Approved
Advantages :
Saves costs of expensive replacement
Long electrical life
Reduces watt losses during “ON” condition, saves energy
High safety
No risk of dangerous voltage
Less maintenance and downtime
Standard control voltages: 24 V 50/60 Hz, 240 V 50/60 Hz, 415 V 50/60 Hz
Specification
Iskra Doo Part Number
KNL90-00-240VAC
Functions
3 Pole Contactor (3 x NO)
Nominal Voltage
230/400/500/690VAC @ 50/60Hz
Current Carrying Capacity as per UL
90 Amp Continuous @ 55 Deg C
Auxiliary Contacts
Optional BFX10-40, 4 Pole Snap On Aux Contacts
Trip Delay Time
2-10ms
Electrical Life
1,200,000 Ops
Operating Temperature
-25 to 55 Deg C
Mechanical Operations
15,000,000 Ops
Control Voltage
240VAC
Power Dissipation
9.4W per pole
Approvals
UL, CSA
Standards
IEC/EN 60947-4-1, AS/NZ 61009-1
Weight
1.25kg
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
Contactor Catalogue