Risbabh EM94-Z-V2-L-D, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 61-200VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,12-60V DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V2-L-D
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
61-200VDC
Maximum Measurement Range
61-200VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Trent 500BBF Series 690V, 500 Amp Semiconductor I²t Fuse, aR BS88 Style
Features
British Standard Fuse Links Package
Wide Range of I²t
Ratings up to 1000 Amp
Busbar or Standoff Mounting
IEC Standard 60269.1 AND 4
690 V Voltage Rating complying with IEC 33
Applications
Protection of High Powered Semiconductors according to I²t
Short Circuit Protection
DC or AC Motor I²t Protection
Battery Fuse
Specification
Trent Part Number
500BBF
Fuse Type
I²t aR Class
Nominal Voltage
690VAC @ 50Hz
I²t Rating (IP < 30IN)
277000 A²/s
Nominal Current (RMS + DC)
500 Amp
Tested Breaking Capacity
200kA @ 690VAC
Dimensions
79.4 x 24 x 110mm
Hole Centers
75.2 x 93.6mm
Mounting Style
Busbar or Panel Mount with Standoff
Operating Temperature Range
-40°C / 125°C
Watt Loss
69W
Termination Style
M6
Unit Weight
400g
Factory Pack Qty
10
Datasheet
Product Datasheet
Cross Reference Chart
Rishabh Rish Rish SIGMA 75 CTR1+1/1.CL0.5.5VA Summation Current Transformer for 1 Amp CTs
Features
DIN Rail Mounting Clip Included
Built In Sealable Terminal Covers
Mounting Feet Supplied
Narrow Width (30mm)
Self Powered
Rated System Voltage 0.72/3kV
IEC185, BS 7626, BSEN 60044-1 and IEC 60044-1
Applications
Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Rishabh Part Number
Rish SIGMA 75 CTR1+1/1.CL0.5.5VA
Technology
AC Current Transformer
Ratio
1+1/1
VA Rating
5VA Class 0.5
Accuracy Class
Class 0.5
Output
1 Amp AC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Din Rail Mount
Operating Temperature Range
-30°C / 85°C
Continuous Current (max)
1.6 Amp
Termination Style
Screw
Unit Weight
500g
Factory Pack Qty
5
Datasheet
Product Datasheet
Gigavac P105BDA, MiniTactor Contactor SPST-NO, 50 AMP, 1200VDC, 12VDC Coil, M3 Coil Screw Terminals, M4 Power Terminals
Features
Perfect for Photovoltaic/Battery Systems
Hermetically Sealed (Patented) rated to 175 Deg C
High Efficiency Dual DC Coils - 12,24,48VDC options
Ideal for battery powered systems or where low power is needed
Built in Coils suppression for all DC Coils
Small and lightweight
Flexible package for installation
Chassi level power terminals
Specification
Gigavac Part Number
P105BDA
Main Contact Type
SPST-NO
Auxiliary Contact Type
N/A
Coil Voltage
12VDC
Load Current
50 Amp
Mechanical Life @ 0 Amp
100,000 Operations
Dielectric at Sea Level
4.3kV rms
Control Input Terminals
M3 Screw
Special Feature
N/A
Mounting Style
Panel Mount (M4)
Load Voltage Range
1200VDC
Standards
UL508, NEC 690.11 and 690.12 DC
Termination Style
M4 Screw
Unit Weight
135g
Factory Pack Qty
1
Datasheet
Product Datasheet
Gigavac GX14FC, Contactor SPST-NO, 350+ AMP, 12-800VDC, 48VDC Coil, 122cm Flying leads, IP67, IP69K
Features
Hermetically Sealed (Patented) rated to 175 Deg C
UL1604 for Class I & II Div 2 and Class III for use in hazardous locations
IP67 & IP69K
SAE J1171 External ignition protection
ISO8846 Protection against ignition around flammable gasses
CE Approved
High Efficiency Dual DC Coils - Very low 12,24,48VDC continuous coil power with no EMI emissions or cross-talk on your system control power
Ideal for battery powered systems or where low power is needed
PWM option provides additional drive control flexibility
Built in Coils suppression for all DC Coils
Flexible package for installation
Chassi level power terminals
Salt Fog MIL-STD-810
Specification
Gigavac Part Number
GX14FC
Main Contact Type
SPST-NO
Auxiliary Contact Type
None
Coil Voltage
48VDC
Load Current
350+ Amp
Mechanical Life @ 0 Amp
1,000,000 Operations
Dielectric at Sea Level (leakage <1mA)
2.2kV rms
Control Input Terminals
38cm Flying Leads
Aux Contact Terminals
38cm Flying Leads
Special Feature
Hermetically Seal rated to 175 Deg C
Mounting Style
Panel Mount (M5)
Load Voltage Range
12-800VDC
Standards
UL1604, IP67, IP69K, SAE J1171, ISO8846
Termination Style
M8
Unit Weight
440g
Factory Pack Qty
1
Datasheet
Product Datasheet
Gigavac P115BDA, MiniTactor Contactor, 1000VDC, 50A @ 25°C, 25A @ 85°C, SPST-NO, 12V 170mA DC Coil Contactor
Features
Hermetically Sealed (Patented) rated to 175 Deg C
High Efficiency Dual DC Coils - 12,24,48VDC options
Ideal for battery powered systems or where low power is needed
Built in Coils suppression for all DC Coils
Small and lightweight
Flexible package for installation
Specification
Gigavac Part Number
P115BDA
Main Contact Type
SPST-NO
Auxiliary Contact Type
N/A
Coil Voltage
12VDC
Load Current
50A @ 25°C, 25A @ 85°C
Mechanical Life @ 0 Amp
100,000 Operations
Impulse Withstand
6kV rms
Control Input Terminals
M3 Screw
Special Feature
N/A
Mounting Style
Panel Mount (M4)
Load Voltage Range
1000VDC
Standards
UL508, NEC 690.11 and 690.12 DC
Termination Style
M4 Screw
Unit Weight
135g
Factory Pack Qty
1
Datasheet
Product Datasheet
FT500160P, 5000/5 Amp Split Core CT, Class 1 15VA Series Current Transformer
Features
Quick Release Split Core System
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
IEC185, BS 7626, BSEN 60044-1 and IEC 60044-1
Applications
Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Electronics Part Number
FT500160P
Technology
Split Core AC Current Transformer
Ratio
5000/5
Aperture Size
80 x 160mm
VA Rating
15VA
Accuracy Class
Class 0.5
Output
5 Amp AC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10°C / 50°C
Continuous Current (max)
4000Amp x 1.2
Termination Style
Screw
Approvals
UL, CE
Unit Weight
1150g
Factory Pack Qty
1
Datasheet
Product Datasheet
Installation Guide
Crydom DR48D06, Solid State Relay, 4-32VDC control, 6 Amp 48-600V AC Output, Slimline, Din Rail Mount, LED status Indicator
Features
Ratings from 6A to 12 Amp @ 48 - 600VAC
DIN Rail Mount
SCR output for reliable AC switching
Ultra slim package
UL/CSA/VDE Approved, CE Compliant to EN60950-1
EMC compliant to Level 3
Epoxy free design
Spec
Crydom Part Number
DR48D06
Switching Type
Zero Crossing
ROHS
Yes (Details)
Control Voltage
4-32VDC
Load Current
6 Amp (rms)
Surge Capability (10ms)
410 Amp (peak)
Special Feature
LED Status Indicator
Mounting Style
DIN Rail Mount
Load Voltage Range
48 - 600VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
38g
Factory Pack Qty
20
Datasheet
Product Datasheet
Equivalent
DRA1-CMX60D10
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Fastron Electronics DEVD200E1DA4, Contactor SPST-NO Non Polar, 200 AMP, 12-800VDC, 12-36VDC Coil, SPST-NO Auxiliary Contact
Features
Hermetically Sealed with inert gas
CE, CCC Approved
Ideal for battery powered systems or where low power is needed
PWM option provides additional drive control flexibility
Built in Coils suppression for all DC Coils
Side mounted version available
Specification
Fastron Part Number
DEVD200E1DA4
Main Contact Type
SPST-NO (silver plated copper)
Auxiliary Contact Type
SPST-NO
Coil Voltage
12-36VDC
Load Current
200 Amp
Mechanical Life @ 0 Amp
200,000 Operations
Dielectric at Sea Level (leakage <1mA)
2.5kV rms
Control Input Terminals
Lead Wire Connection
Special Feature
N/A
Mounting Style
Panel Mount (M5)
Load Voltage Range
12 - 800VDC
Standards
CE, CCC
Termination Style
M8
Unit Weight
550g
Factory Pack Qty
1
Datasheet
Product Datasheet
Risbabh EM94-Z-V2-M-M, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 61-200VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,10-60V AC/DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
4 x DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
10-60VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V2-M-M
Functions
kWh Meter, Energy Meter
Supply Voltage
10-60VAC/DC
Nominal Measurement Range
61-200VDC
Maximum Measurement Range
61-200VDC
Display
4 Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Crydom HS501DR + A2450G, Panel or Din Rail Mount Solid State Relay 90-280VAC Control Input, LED Status, 24-280VAC Output, 10 Amps
Features
Ratings from 25A to 125 Amp @24-280 VAC
SCR output for heavy industrial loads
Zero voltage or instantaneous turn-on outputs
UL/CE/ROHS Compliant
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Spec
Part Number
HS501DR + A2450G
Switching Type
Zero Crossing
ROHS/CE/UL
Yes
Control Voltage
90-280VAC
Load Current
10 Amp (rms) @ 40 Deg C
Surge Capability
597 Amp (peak)
Special Feature
LED Status Indicator
Mounting Style
Din Rail or Panel Mount
Load Voltage Range
24-280VAC
Max Non Repetitive Peak Voltage
600 Vp
Termination Style
Screw Terminals
Dimensions
L:79.9mm x W:45mm x D:40.3mm
Unit Weight
296g
Factory Pack Qty
20
Datasheet
HS501DR
A2450-G
Notifications
Please note Changes from Gen 3 to Gen 4 (current) package design here
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies