TCD-M-1-PT HEATING Temp Controller, 72x72mm 230VAC, C/O Relay output, PT100 RTD Input. Encoder Control,amp; Digital Display, 0-999 Deg C
Pushbutton Encoder Setpoint
3-digit display (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated ON/OFF Relay, output, Optional cooling or time proprtional versions output available
Each unit needs just 75 mm depth panel space
Specification
Fastron Part Number
TCD-M-1-PT
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Input
Pt100 RTD
Control Mode
Heating ON/OFF Control
Control Range
0- 999 Deg C
Mounting Style
72x72mm Panel Mount
Supply Voltage
230VAC
Termination Style
Screw
Sampling Time
50ms
Weight
270g
Factory Pack Qty
1
Datasheet
TCD/TCR/FC5 Datasheet
TCD/TCR User Manual
TCD-H-1-K HEATING Temp Controller, 48x96mm 230VAC, C/O Relay output, Type K Input. Encoder Control,amp; Digital Display, 0-999 Deg C
Pushbutton Encoder Setpoint
3-digit display (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated ON/OFF Relay, output, Optional cooling or time proprtional versions output available
Each unit needs just 75 mm depth panel space
Specification
Fastron Part Number
TCD-H-1-K
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Input
Type K Thermocouple
Control Mode
Heating ON/OFF Control
Control Range
0- 999 Deg C
Mounting Style
48x96mm Panel Mount
Supply Voltage
230VAC
Termination Style
Screw
Sampling Time
50ms
Weight
270g
Factory Pack Qty
1
Datasheet
TCD/TCR/FC5 Datasheet
TCD/TCR User Manual
DR6760D30P, Solid State Relay and Heatsink Assembly, 3 Phase, 2 Leg Control, 4-32VDC Control, Random Crossing, 30 Amp per phase @ 40 Deg C, 48-600VAC Load, LED Status Indicator, Overvoltage Protection
Features
Ratings from 25A to 60 Amp @ 70-530 VAC
Motor Control
SCR output for heavy industrial loads
Zero voltage or Instantaneous turn-on outputs
UL/CE/ROHS Approved
IP20 Cover Available
AC & DC control types
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
DR6760DR30P
Switching Type
Random Crossing
ROHS/CE/UL
Yes
Control Voltage
4-32VDC
Load Current
3 x 30 Amp (rms) per Phase @ 30 DeG C
Surge Capability
716 Amp (peak)
Special Feature
LED Status Indicator, Overvoltage Protection
Mounting Style
Din Rail Mount
Load Voltage Range
48-600VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
961g
Factory Pack Qty
10
Datasheet
DR6760D30P
3 Phase SSR and Heatsink Mounted
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Infineon T298N08TOF Thyristor(SCR) Capsule
Features
Very low forward voltage drop
Very low leakage current
International standard package
41/14 Package
Press Mounted
Double or Single Sided Cooling
Applications
Power Supplies
Rectifier for drives applications
Controlled Rectifiers
AC Switch
Battery Chargers
Phase Controllers
Water Cooled AC switches
Power Factor Correction
Specification
Infineon Part Number
T298N08TOF
Vrrm
800V
SCR Configuration
Thyristor(SCR) Capsule PUK
IF(av) @ 85 Deg C
298 Amp
Package Size
ø41 x 14mm
Itsm
4.9 kA
VF(to)
.85V
Tj(max)
125°C
rF
0.9mΩ
Gate Terminals
Faston 4.8 x 0.8mm & 2.8 x 0.8mm
R th(j-c) (double sided cooled 180°sin)
0.088°C/W
R th(c-h) (double sided cooled)
0.015°C/W
Weight
300g
Clamping Force
3 - 6kN
Factory Pack Qty
12
Certification
ROHS
Infineon Headquarters
Germany
Datasheet
Product Datasheet
Alternatives
, Obsolete, See
T430N16TOF
Heatsink
Heatsink Profiles
TA800E-LR24, Red LED Bead Replacements for 24AC/DC TRIB, TRI Series Indicators
LED Will activate while the contacts are connected. Widely Used for Rugged Industrial Applications Including Critical Machinery requiring safe operation by the user.
Features :
240VAC or 24AC/DC (400VAC Special Orders)
AC & DC Sensing (Type A)
1 Pole Momentary
LED Illumination
Rated for 6 Amp @ 240VAC, or 0.3 Amp @ 240VDC
Ø 22.5mm Cutout
Standards :
IP40
IEC60947-5-1
CE
Specification
TRENT Part Number
TA800E-LR24
Functions
LED Indicator Bulb Replacement
Nominal Voltage
24AC/DC @ 50/60Hz
Impulse Voltage Wear Resistance
6kV
Illumination Type
Red LED
Approvals
CE
Weight
Factory Pack Qty
1
TRENT(Fastron) Head Office
Australia
Datasheet
Product Datasheet
Northern Design Power Rail PR350-M2-C-0.333V, kWh Meter, 3 Phase, DIN Rail, 240VAC aux, Class 1, 0.333V input, w/ pulse output and RS485 Comms, Power quality measurements
0.333V CT Input
Optional RS 485 communication up to 19,200 bit/s
True RMS values of currents and voltages
Power Quality Measurements
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, Hours Run, Peak Demand etc to the 30th Harmonic) from the measured signals.
Features :
Accuracy class 1
Measurement of Active and Reactive Power
Optional MODBUS RS 485 communication up to 19,200 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Northern Design Part Number
Power Rail PR350-M2-C-0.333V
Functions
Three Phase Energy Meter
Supply Voltage
230V L-N, 5 Amp +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 5 Amp +/-15%
Nominal Current Input
0.333 Volt AC
Pulse Output
3 x NO Voltage Free Contacts 100mA @ 100VAC/DC
Tariff Input
N/A (Optional)
Accuracy
Class 1 (I,U,F,PF,) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
106mm x 90mm x 58mm (6 modules wide)
Isolation
3.5kV
RS485
1200-19200 b/s
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 6 Modules
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Product Manual
Product Comms Manual
Option Links
Application Notes
CT Cable Losses
Meter Accuracy at Low Current
Current Input Isolation
Magnelab HCT-0024-250, Split Core DC Hall Effect Current Sensor, 250 Amp, +/-4V Output, Split Core 24mm Aperture, X = 1%
Features
Open loop transducer using Hall effect
Compact and versatile
Panel mounting-Horizontal or Vertical
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
Very good accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Current overload capability
Low power consumption
Applications
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications.
Specification
Magnelab Part Number
HCT-0024-250
Technology
Split Core Open Loop Hall Effect
Aperture
ø24mm
ROHS
Yes
Supply Voltage
+/-15 VDC Bipolar, Isolated
Load Current (RMS + DC)
250 Amp
Measurement Range
+/-375 Amp
Output
+/-4 V
Isolation
4 kV
Bandwidth
DC
Mounting Style
Panel Mount
Operating Temperature Range
-25°C / 75°C
Accuracy
1%
Termination Style
Flying Lead
Unit Weight
400g
Factory Pack Quantity
10
Datasheet
Product Datasheet
Crydom ED24C5, EMR plug in Solid State Relay, 18-32VDC control, 5 Amp 24-280VAC output
Features
Ratings 5 Amp @ 24-280VAC
Plug in EMR relay style
Motor controller rated
SCR output for reliable AC switching
Multiple modules can be wired in parallel for higher currents
UL/CSA/VDE Approved, CE Compliant to EN60950-1
EMC compliant to Level 3
Epoxy free design
Spec
Crydom Part Number
ED24C5
Switching Type
AC Load
ROHS
Yes (Details)
Control Voltage
18-32VDC
Load Current
5 Amp DC
Surge Capability (10ms)
60 Amp DC
Special Feature
Plug in EMR style
Mounting Style
EMR Base
Load Voltage Range
24-280VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
38g
Factory Pack Qty
10
Datasheet
Product Datasheet
Socket
DRSED
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Crydom CWU4890P, Solid State Relay, Single Phase 20-48VDC or 20-280VAC Control, 90A, 48-530VAC Load, High Surge Rating w/status LED + Overvoltage Protection
Features
Ratings from 25A to 125 Amp @48-600VAC
SCR output for heavy industrial loads
Zero voltage or instantaneous turn-on outputs
UL/CSA/VDE Approved, CE Compliant to EN60950-1
Improved SEMS screw and washer
Redesigned housing with anti-rotation barriers
AC & DC control types
Direct bond copper substrate
EMC compliant to Level 3
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
CWU4890P
Switching Type
Zero Crossing
ROHS
Yes (Details)
Control Voltage
20-48VDC or 20-280VAC
Load Current
90 Amp (rms)
Surge Capability
1290 Amp (peak)
Special Feature
LED Status Indicator, High Surge, Internal Over Voltage Protection
Mounting Style
Panel Mount
Load Voltage Range
48-660VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
75g
Factory Pack Qty
20
Datasheet
Product Datasheet
Notifications
Please note Changes from Gen 3 to Gen 4 (current) package design here
Equivalent
See CWA2450P, CWD2450P, CWA4890P CWD4890H for stocked equivalent (no overvoltage protection).
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Fastron Electronics SCT-F24-100-33.33mA, 100Amp measurement, 33.33mA Output Split Core CT, Suitable for Porsche E-Performance Chargers
Features
Quick Release Split Core System
Cable Mount
33.33mA Amp Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F24-100-33.33mA
Technology
Split Core AC Current Transformer
Ratio
100A/33.33mA
Aperture Size
ø 24 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
33.33mA Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
100Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Iskra Doo MCR 32 UNI, Current Monitoring Relay AC 2-20 Amp, Adjustable Range, Universal 24-240VAC 24VDC Aux Supply, 1 x 8 AMP SPST CO Relay
MCR 32 Series serves to monitor AC currents up to 20 Amp, and provides Relay alarm output with adjustable delay time 0.5 - 10s. Can replace Crouzet 84871122
Features :
Current transformer is a part of the product. Inside this transformer there is a wire which senses the volume of fl owing current
Non Invasive measurement
Galvanically separates monitored circuit
Universal supply AC 24 - 240 V and DC 24 V Supply is galvanically separated from measuring current
Current withstand up to 100 A
Output contact: 1x changeover/SPST 8 A Clamp terminals 1-phase, 1-MODULE, DIN rail mounting
Applications :
Heating bars in sliding rails
Heating cables
Indication of current flow
Controlling of 1-phase motor consumption
Specification
Iskra Doo Part Number
MCR 32 UNI
Voltage Range
AC 24 - 240 V, DC 24 V (AC 50 - 60 Hz)
Operating Range
-15 %; +10 %
Current Range
1 - 20 A (AC 50 Hz)
Current Trip Adjustment
2,4,6,8,10,12,14,16,18,20 Amp Setpoints
Settign Accuracy
5 %
Burden
max. 1.5 VA
Repeatability
1 %
Temperature Drift
0.1%/°C
Peak Overload (10s)
100 Amp
Time delay T1
max. 500 ms
Time delay T2
N/A
Output
SPDT Relay 8 Amp
Number of contacts
1x changeover/ SPDT (AgNi / Silver Alloy)
Rating
8 A / AC1
Breaking capacity
2500 VA / AC1, 240 W / DC
Inrush current
10 A
Switching voltage
250 V AC1 / 24 V DC
Min. breaking capacity DC
500 mW
Indication of state
red LED
Mechanical life
1 x 107
Electrical life (AC1)
1 x 105
Other information
Operating temperature
-20 ... +55 °C
Storage temperature
-30 ... +70 °C
Electrical strength
4 kV (supply - output)
Operating position
any
Mounting
DIN rail EN 60715
Protection degree
IP 40 from front panel / IP 10 terminals
Overvoltage cathegory
III.
Pollution degree
2
Max. cable size (mm )2
solid wire max. 2x2.5 or 1x4 ; with sleeve max. 1x2.5 or 2x1.5
Dimensions
90 x 17,6 x 64 mm
Weight
69 g
Standards
EN 60255-6, EN 61010-1
Datasheet
Product Datasheet
Application Notes
Monitoring relay MCR-32 serves to monitor current level in single phase AC circuits. Due to its fl uent adjustment of release current, it is predestined for applications with necessity of current flow indication, and can be used as precedence relay. Output relay is off in normal state. In case the set current level is exceeded, it switches. Multivoltage supply is an advantage.