RCS-1800-1000 Three-Phase Flexible Current Sensor System (Rogowski Coils):
The RCS-1800 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-1800 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Suitable Alternative to Solar Edge CTRC-07500-1000
Specification
Magnelab Part Number
RCS-1800-1000
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
1000 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 1000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
6 Inch
Coil Circumference
18 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
Eastron SDM630MCT-2L-TCP, Dual 3 Phase DIN Rail Mount kWh Meter with Easyclick, 2 x 3 Phase or 6 x Single Phase, 240VAC aux, Class 1, 100mA RJ12 CT Connect, w/RS485 Modbus RTU Comms
100mA RJ12 CT 2 x 3 Phase Connect
100mA RJ12 6 x Single Phase RJ12 CT with adapter
RS 485 communication up to 38,400 bit/s as standard
True RMS values of currents and voltages
Easyclick CT system reduces installation costs
Dual Metering System Reduces Cost and saves space
The meter is intended for measuring, and monitoring 2 x three phase or 6 x single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
System Accuracy Class B/Class1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM630MCT-2L-TCP
Functions
Dual Three Phase Energy Meter/ 6 x Single Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
100mA via RJ12 Easyclick CT's
Pulse Output
N/A
Tariff Input
N/A
Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
600g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Suitable RJ12 CT's
Three Phase J12 Connected CT's
Split Core Single Phase CT's for RJ12 Connected Meters
Modbus Utility
EEM Meter Setting Software Utility
Eastron Europe SDM72D-M-2-MID, DIN Rail Mount kWh Meter, 3 Phase, with Resettable Energy Register, 500VAC L-L, Class 1, 100 Amp Direct Connect input, w/ 1 x fixed pulse output and RS485 Comms, MID Approved. Built for EV Chargers, (Superseeds SDM72D-M V2)
3 x 100 amp Direct Connect
RS 485 communication up to 38,400 bit/s as standard
True RMS values of currents and voltages
1 x Pulse Outputs (fixed)
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
Accuracy class 1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM72D-M-2-MID (Superseeds SDM72D-M V2)
Functions
Three Phase Energy Meter
Supply Voltage
N/A
Nominal Measurement Range
415V L-L 230V L-N, 100 Amp
Maximum Measurement Range
500V L-L 230V L-N, 100 Amp
Nominal Current Input
Direct connect 3 x 100 Amp
Pulse Output
1 x Passive (fixed)
Tariff Input
N/A
Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Alternatives
WM3-6 230DB
Modbus Utility
EEM Meter Setting Software Utility
GIC Z2221N0G2FT00, Totalizer/Counter or HOUR METER with Green Backlit Display 85-265VAC, Relay Output
IP40
Direct Voltage Inputs
7 Digit Display (8mm)
85-265VAC Aux Supply
48 x 24mm Cutout
Reset On Panel or via Rear Terminals
Datasheet
Product Datasheet
Fastron Electronics SCT-F10-20-0.2V, 200mV, 20Amp measurement Split Core CT's Class 1 with 0.5M flying leads
Features
Quick Release Split Core System
Cable Mount
200mV Output
Self Powered
Rated System Voltage 0.60/3kV
0.5M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F10-20-0.2V
Technology
Split Core AC Current Transformer
Ratio
20/200mV
Aperture Size
ø 10 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
200mV (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
20Amp x 1.2
Termination Style
0.5M Flying Leads
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Fastron Electronics SCT-F24-200-5A, 200/5 Amp Class 1 Series Current Transformer
Features
Quick Release Split Core System
Cable Mount
5 Amp Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F24-200-5A
Technology
Split Core AC Current Transformer
Ratio
200/5 Amp
Aperture Size
ø 24 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
5 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
200Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Northern Design Multicube Modular Digital Output Module
Up to 12 Pulse or Alarm outputs. Requires multicube modular master unit
Minimum 2 x 3 Phase Circuits with measurement module
Alternative master with logger
Optional pulse output modules
Requires Multicube Modular Master or Multicube Master with Logger
Optional 12 way pulse/alarm digital output modules
Nominal current up to 0.383V (For 0.333V CT Input) and nominal voltage up to 240V L-N 415V L-L
Graphic Display
Optional RS485 or Ethernet communication up to 19,200 bit/s
True RMS measurement of currents and voltages
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, reactive power, power factor, harmonics, etc.) from the measured signals.
Features :
Dual 3 phase Measurement Module
2 x 3 Phase or 6x Single Phase Circuits
Accuracy class 1
Simple Menu
Optional MODBUS RTU RS485 communication up to 19,200 bit/s or Ethernet communication
5 Year Warranty
240V AC power supply
Specification
Northern Design Part Number
Multicube Modular Master
Functions
kWh Meter, Energy Meter, Power Quality
Supply Voltage
240VAC < 15VA
Nominal Measurement Range
415V L-L 240V L-N, 0.333V
Maximum Measurement Range
480V L-L 280V L-N, 0.383V
Display
Graphic LCD
Pulse Output
12 (Optional)
Accuracy
Class 1 (kW,kWh) Class 1(Active), Class 2 Reactive
Ethernet
Optional
Real Time Clock
1min/month (30ppm)
Isolation
2.11kV
RS232/RS485
N/A (Optional 2400-19200 b/s)
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
ABS with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
164 x 96mm x 29mm
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product brochure
User manual
Wiring Diagram
Suitable 0.333V CT's
Split Core CT's
Eastron SDM630MCT-RC, DIN Rail Mount kWh Meter, 3 Phase, 240VAC aux, Class 0.5, 85mV/kA Rogowski Coil Connect, w/ 2 x pulse outputs and RS485 Modbus RTU Comms. COILS NOT INCLUDED
85mV/kA Rogowski Coil Connect
RS 485 communication up to 38,400 bit/s as standard
Optional Mbus Model available
True RMS values of currents and voltages
1 x Configurable Pule Output (via Display Menu or Modbus)
1 x Fixed Pulse Output (1000imp/kwh)
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
Accuracy class 0.5
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Part Number
SDM630MCT-RC
Functions
Three Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
85mV/kA Rogowski Coil Connect
Pulse Output
2 x Passive, (1 x Configurable 60/100/200ms)
Tariff Input
N/A
Accuracy
Class 0.5 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Setup Video - CT Ratio Unlock
Alternatives
WM3-6 230DB
Modbus Utility
EEM Meter Setting Software Utility
Fastron Electronics SCT-F24-25, 0.333v, 25Amp Measurement, Class 1 Split Core CT's
Features
Quick Release Split Core System
Cable Mount
0.333v Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F24-25
Technology
Split Core AC Current Transformer
Ratio
25/0.333v
Aperture Size
ø 24 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
0.333v (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
25Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Secure Elite E500C-5202, Panel Mount Network Recorder with Harmonics (15th) & PQ Parameters, Class 0.5S, 50..500VAC 50/60Hz, RS485 Modbus RTU, 35..300V DC/85..300VAC Aux, 16MB Dual Logger , TFT Touch Screen, 10 Years Warranty
Automatic range of nominal current up to 6 A (Includes 5A/1A CT Input) and nominal voltage up to 500 V L-L, 300V L-N
Configurable 2 x Tariff Inputs or 2 x Pulse Outputs, or Alarm Outputs
Dual Loggers, configurable for Instant or accumulated energy
Configurable 2 x Tariff Inputs or 2 x Pulse Outputs, or Alarm Outputs
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
RS 485 communication up to 38400 bit/s as standard
Optional Protocol Modules Modbus TCP, BACNet IP, Profinet, SCADA EC61850
Optional Modules for Analogue outputs and Relay Alarms
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values and accumulated energy. Includes Harmonics to the 15th
Accuracy class 0.5S
Dual Internal Loggers
Measurement of 20 minimal and maximal values in different time periods
RS 232/RS 485 communication up to 38400 bit/s or Ethernet communication
MODBUS communication protocol
Optional Protocol Modules Modbus TCP, BACNet IP, Profinet, SCADA EC61850
Configurable 2 x Tariff Inputs or 2 x Pulse Outputs, or Alarm Outputs
Universal or AC/DC power supply
Graphic Colour TFT 320 x 240 pixels (53x70mm)
Automatic range of nominal current up to 6 A and nominal voltage up to 500 V
Multilingual support
User-friendly Free ECon Configuration software
Specification
Secure Part Number
E500C-5202
Functions
Power Quality Meter(15th Hamonic), Energy Meter, Network Recorder
Supply Voltage
Universal 35..300V DC, 85..300VAC
Nominal Measurement Range
240V L-N, 1/5 Amp, 415V L-L 1/5 Amp
Maximum Measurement Range
300V L-N, 1/5 Amp, 500V L-L 1/5 Amp
Alarm
Optional Module 2 Relay/Pulse Outputs
Tariff/Digital Inputs
TOU Tarriff Clock
Accuracy
Class 0.5S (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Analogue Output
Optional Module 2 x Programmable Analogue Outputs
Internal Memory
2 x 8MB
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS232/RS485
N/A Optional
CT Termination
Ring Terminals
Weight
600g
Certification
CE, CSA, ROHS
Warranty
10 Years from dispatch from Secure Warehouse
Factory Pack Qty
1
EU Directives
Degree on electrical equipment designed for use within certain voltage limits URLRS 53/00 (Directive 73/23/EEC on low voltage): SIST EN 61010-1:2002
Safety Requirement for electrical equipment for measurement, control and laboratory use, part1 : general requirement
Decree on electromagnetic Compatibility (EMC) URLRS 61/00 (Directive 89/336/EEC on electromagnetic compatibility): SIST EN 61036 item 4.5: 1998 Meters for active energy (class 1 and 2)
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP52 (IP00 for terminals) in compliance with SIST EN 60529:1997
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Cross Reference
The Following meters are close equivalents to Elite 500 Series. For further details please contact Fastron Sales Team
Elite 500_400_300_100 series competition replacement for
Schneider
Siemens
Accuenergy (RS485 +DNP3 default)
Socomec
Selec
PM 5000 series
PAC 2000 series
ACCUVIM-CL + DNP3.0
DIRIS A-20
Selec MFM376
PM 5100
PAC 3200
ACCUVIM-CL + DNP3.0
DIRIS A-20
MFM384, CL-1, RS485
PM 5300
ACCUVIM-IIR
DIRIS A-20
MFM383A
PM 5500
PAC 4200
ACCUVIM-IIR(+ BACnet)
DIRIS A-20
MFM384. RS485
PM 6463
Siemens 7KMPAC4200
ACCUVIM-IIR (+ Profibus)
DIRIS A-30/ DIRIS - A60 (PQ Feature)
MFM384-C-CE-CL05, RS485
PM 5650
ACCUVIM-IIR (+ IEC 61850)
DIRIS A-30 + Profibus
MFM384-C-CE-CL05, RS485
PM 5760
ACCUVIM-EL
DIRIS A-30 +Ethernet
MFM384-C-CE-CL05, RS485
PM5330
ACCUVIM-EL (+ BACnet)
DIRIS A-30/ DIRIS A-60
PM 5560
ACCUVIM-EL (+ Profibus)
DIRIS A-30/ DIRIS A-60
DM6200H
ACCUVIM-EL (+ IEC 61850)
PM2220
ACCUVIM-II R +Ethernet
PM2230 / DM2120 (LED)
PM 5350
Eastron Europe SDM72CT-D, DIN Rail Mount kWh Meter, 3 Phase, with Resettable Energy Register, 500VAC L-L, Class 1, 1/5 Amp CT Connect input, w/ 1 x fixed pulse output and RS485 Comms, MID Approved. Built for EV Chargers
Features
3 x 1/5 Amp CT Input
RS 485 communication up to 38,400 bit/s as standard
True RMS values of currents and voltages. Note only kWH is shown on display
1 x Pulse Outputs (fixed)
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
Accuracy class 1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM72CT-D
Functions
Three Phase Energy Meter
Supply Voltage
N/A
Nominal Measurement Range
415V L-L 230V L-N, 5000 Amp
Maximum Measurement Range
500V L-L 230V L-N, 5000 Amp
Nominal Current Input
CT Connect 3 x 5/1 Amp
Pulse Output
1 x Passive (fixed)
Tariff Input
N/A
Accuracy
Class 1 (kWh Only)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
Alternatives
SDM630MCT
SDM72CT-M (with additional measurement parameters)
Modbus Utility
EEM Meter Setting Software Utility
LEM ART-B22-D70-SP3 + AI-PMUL Single Phase Rogowski Coil Set, Class 1, User Selectable 0.333v, 0.166v, True RMS 4-20mA, 0-20mA, 0-10V, 0-5V Outputs, Sensitivity, and Measurement Range, 7cm Diameter
The universal Rogowski coil integrator AI-PMUL complements LEM’s flexible clip-around coil ART and ARU range. The design is based on digital processing to give combined dynamic range, accuracy and versatility of use. It offers a wide range of output signals both RMS and instantaneous. AI-PMUL is DIN rail mounted and can be stacked for multiphase application without spacing thanks to its low power dissipation.
Input signal
Accuracy Class 1 (IEC 61869-2) [1].
Linearity error ≤ 0.10 %. Protection degree IP2X.
35 mm DIN rail mounted.
Push-in terminals.
4 selectable true RMS output signals: 0…20 mA, 4…20 mA, 0…5 V, 0…10 V.
2 selectable instantaneous output signals: 225 mV, 333 mV.
6 selectable sensitivities depending on Rogowski coil: 22.5, 70, 80, 85, 100, 120 mV/kA at 50 Hz.
12 selectable ranges: 100, 200, 300, 400, 500, 600, 800, 1000, 1500, 2000, 4000, 5000 A.
Ambient operating temperature −25...+70 °C.
Advantages
Compact design for DIN rail assembly
High accuracy Class 1 (IEC 61869-2)
Setup by user via Select / Edit buttons
Clear status indication via bi-color led
Applications
MV/LV substations on LV side: Transformer Condition Monitoring
Power metering: current measurement for active power calculation
Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation
Power quality monitoring: electrical loads and distribution system equipment
Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault
Remote Terminal Units (RTU)
Phasor Measurement Units (PMU)
Standards
IEC 61010-1: 2010
UL
EMC: IEC 61326-1:2012
Included Options
Cross Power Plug-in: side contacts to stack up to 3 Integrator modules and use only one power supply.
Specification
LEM Part Number
ART-B22-D70-SP3 + AI-PMUL
Function
Single Phase AC Current Measurement
Measuring Range
Selectable 5000,4000,2000,1500,1000,800,600,500,400,300,200,100Amp
Sensitivity
Selectable 22.5,70,80,85,100,120mV/kA @ 50 Hz
Output
Selectable; Signal Conditioned True RMS 0-20mA, True RMS 4-20mA, True RMS 5V, True RMS 10V or 225mV, 333mV Direct Output (1 Amp output coming soon)
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
10-32VDC
Accuracy
1% from 25 to 5000 Amp
Current Consumption
100mA (max)
Dimensions
100mm x 78mm x 15mm (Integrator), 7cm Diameter (Coils)
Mounting
Din Rail Mount
Integrator to Coil cable
3M Twisted and Screened
Integrator to Meter cable
User Supplied Shielded cable 1.5mm sqr, up to 6m long
Operating Temperature
-25°C - 70°C
Storage Temperature
-45°C to 80°C
Isolation (50Hz, 1 min)
1.5kV
True RMS Response Time
160-190ms
Termination Style
Push-in for 1.5mm sqr wire
Weight
58g
Factory Pack Qty
1
Certifications
UL, ROHS
Datasheet
AI-PMUL Datasheet
ART Series Datasheet
Applicaton Notes
User Notice
1) The Rogowski coil can measure any primary current as there is no saturation effect.
2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts)
3) Frequency bandwidth and phase shift modelling schematic can be provided on request.
4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5) Considering a primary conductor of at least ⌀ 15 mm, perpendicular and in contact with the Rogowski coil.
6) Considering an external conductor of at least ⌀ 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.