Trent 15AF Series 690V, 15 Amp aR Semiconductor I²t Fuse BS88 Style
Features
British Standard Fuse Links Package
Wide Range of I²t
Ratings up to 1000 Amp
Busbar or Standoff Mounting
IEC Standard 60269.1 AND 4
690 V Voltage Rating complying with IEC 33
Applications
Protection of High Powered Semiconductors according to I²t
Short Circuit Protection
DC or AC Motor I²t Protection
Battery Fuse
Specification
Trent Part Number
15AF
Fuse Type
I²t AR Class
Nominal Voltage
690VAC @ 50Hz
I²t Rating (IP < 30IN)
55 A²/s
I²t Rating (IP > 30IN)
95 A²/s
Nominal Current (RMS + DC)
15 Amp
Tested Breaking Capacity
200kA @ 690VAC
Dimensions
17 x 49mm
Hole Centers
60.9 - 65.6mm
Mounting Style
Busbar or Panel Mount with Standoff
Operating Temperature Range
-40°C / 125°C
Watt Loss
4.8W
Termination Style
M6
Unit Weight
61g
Factory Pack Qty
10
Datasheet
Product Datasheet
Cross Reference Chart
Fastron Electronics AMB-D-V6-D-N, 96x48mm DC Voltmeter, Panel Mount, 0-300V DC Input, 24-60VDC supply, Previously AMB-D-V6-24VDC, Large 4.1 Digit
Adjustable Zero and Span Setting
Adjustable Display Scaling
Large 4.1 Digit 20.3mm (8 Inch) LED Display
250mS Response Time
PC 94 UL V0
Each unit needs just 96 x 48mm Panel Space
90mm Depth
CE Approved
Specification
Fastron Electronics Part Number
AMB-D-V6-D-N
Conditioner Output
N/A
Input
300VDC
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
22-60VDC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Display Type
4.1 Digit RED LED
Mounting Style
96 x 48mm Panel Mount
Case Material
PC - UL 94 V0
Weight
320g
Factory Pack Qty
1
Datasheet
Product Datasheet
Application Notes
Panel Meters Blog Articles
LEM ATO 5 B420 D10/SP4, AC Current Transformer, 20-30VDC loop powered, 125 Amp Average RMS 4-20mA output, X = 1.5%
Features
125 Amp AC Current Measurement
Signal Conditioned output
Split Core
4-20mA Current Output
Cable or Din Rail Mounting
20-28VDC Powered
Isolated plastic case recognised according to UL94-V0
UL508 Rated
Advantages
Large aperture for cable up to ? 10mm
High isolation between primary and secondary circuits
Easy installation
Applications
Hybrid Inverter
Power Metering
Power Quality Analysis
Distributed Measurement Systems
Current Measurement
Energy Management
Motor Control
Condition Monitoring
Specification
LEM Part Number
ATO-5-B420-D10-SP4
Technology
AC Current Transformer
Protection Class
IP50
Supply Voltage
20-30VDC Loop Powered (10mA)
Load Current (RMS)
125 Amp
Output
4-20mA (Average RMS)
Isolation
4.3kV (AC, 50Hz, 1 min)
Bandwidth
50 - 60Hz
Mounting Style
Din Rail Mount or Cable Mount
Operating Temperature Range
-10°C / 55°C
Accuracy
1.5%
Termination Style
4M Output Cable
Unit Weight
140g
Factory Pack Qty
6
Datasheet
Product Datasheet
Crydom DR2260D20V, Solid State Contactor SSR, Single Phase 4-32VDC Control, 20A, 48-600VAC Load, Din Rail Mount w/status LED
Features
Ratings from 20 Amp up to 30 Amp @ 200 VDC
Mosfet output for heavy industrial loads
UL/CSA/VDE Approved, CE Compliant to EN60950-1
Din Rail Mount with bonded Heat sink
Direct bond copper substrate
EMC compliant to Level 3
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
DR2260D20V
Switching Type
DC Load
ROHS
Yes (Details)
Control Voltage
4 - 32VDC
Load Current (single unit)
20 Amp (rms) @ 45 Deg C Ambient, 18 Amp (rms) @ 50 Deg C Ambient
Load Current (multiple units)
16.5 Amp (rms) @ 40 Deg C Ambient, 13 Amp (rms) @ 50 Deg C Ambient
Surge Capability
286 Amp RMS
Special Feature
None
Mounting Style
DIN Rail Mount
Load Voltage Range
48 - 600VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
298g
Factory Pack Qty
20
Datasheet
Product Datasheet
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Crydom DR2260D30V, Solid State Contactor SSR, Single Phase 4-32VDC Control, 30A, 48-600VAC Load, Din Rail Mount w/status LED
Features
Ratings from 20A to 35 Amp @ 48-660 VAC
Contactor Style for retrofit
SCR output for heavy industrial loads
Zero voltage or instantaneous turn-on outputs
UL/CSA/VDE Approved, CE Compliant to EN60950-1
Improved SEMS screw and washer
Redesigned housing with anti-rotation barriers
AC & DC control types
Direct bond copper substrate
EMC compliant to Level 3
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
DR2260D30V
Switching Type
Zero Crossing
ROHS
Yes (Details)
Control Voltage
4 - 32VDC
Load Current (single unit)
30 Amp (rms) @ 40 Deg C Ambient, 26 Amp (rms) @ 50 Deg C Ambient
Load Current (multiple units)
23 Amp (rms) @ 40 Deg C Ambient, 18.5 Amp (rms) @ 50 Deg C Ambient
Surge Capability
716 Amp (peak)
Special Feature
Contactor Style Terminals
Mounting Style
DIN Rail Mount
Load Voltage Range
48 - 660VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
298g
Factory Pack Qty
20
Datasheet
Product Datasheet
Alternatives
SSR Style CKRD4830
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Iskra Two Pole DTS 2 UNI V2, Dual Digital Time Switch with 2 independant Daily Weekly, Monthly, and Yearly program, Universal 12-240VAC/DC Power Supply/Control, 2 x 16 Amp SPST CO Relay
DTS 2 UNI V2 24-240 V AC/DC - 2 Relay 16A :
Multi-range (1 Min - Yearly)
Multi-voltage 12 →240 V AC/DC
LED status indicator
Possibility of external load connection in parallel to the control input
Specification
Iskra Part Number
DTS 2 V2 UNI
Function
Yearly Time Switch
Nominal Voltage
24 → 240 V AC/DC
Digital Output
2 x C/O (SPST) (Changeover -Single Pole), 250VAC/DC @ 16 Amp
Min Breaking Current
10mA/12VDC
Timing Ranges
Minutes, Hours, Days, Weeks, Months
Minimum Pulse Duration
30ms/100ms with load
Repeatability
0.5%
Reset Time
120ms
Isolation
4kV
Repetition Accuracy
0.5%
Threshold Adjustment Range
10 → 100 % of the range
Termination Style
Screw
Weight
80g
Factory Pack Qty
1
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
User Manual
Trent F170M1317 Series 690V Semiconductor I^2t (aR) Fuse Square Body DIN 43 653 Style, 100 Amp, 690VAC, Panel Mount 200kA, Size 000 (78mm Hole Centers)
Features
Square Body DIN 43 653
Wide Range of I^2t
Ratings up to 400 Amp
Busbar or Standoff Mounting
IEC Standard 60269.1 AND 4
690 V Voltage Rating complying with IEC 33
Applications
Protection of High Powered Semiconductors according to I??t
Short Circuit Protection
DC or AC Motor I^2t Protection
Battery Fuse
Specification
Trent Part Number
F170M1317
Fuse Type
I^2t AR Class
Nominal Voltage
690VAC @ 50Hz
I??t Rating (660V)
4650 A^2/s
Nominal Current (RMS DC)
100 Amp
Tested Breaking Capacity
200kA @ 690VAC
Dimensions
40 x 100 x 20mm (Size 000)
Hole Centers
78mm
Mounting Style
Busbar or Panel Mount with Standoff
Operating Temperature Range
-40DegC / 125DegC
Watt Loss
24W
Termination Style
M8
Unit Weight
134g
Factory Pack Qty
10
Datasheet
Product Datasheet
Trent F170M1320 Series 690V Semiconductor I^2t (aR) Fuse Square Body DIN 43 653 Style, 200 Amp, 690VAC, Panel Mount 200kA, Size 000 (78mm Hole Centers)
Features
Square Body DIN 43 653
Wide Range of I^2t
Ratings up to 400 Amp
Busbar or Standoff Mounting
IEC Standard 60269.1 AND 4
690 V Voltage Rating complying with IEC 33
Applications
Protection of High Powered Semiconductors according to I??t
Short Circuit Protection
DC or AC Motor I^2t Protection
Battery Fuse
Specification
Trent Part Number
F170M1320
Fuse Type
I^2t AR Class
Nominal Voltage
690VAC @ 50Hz
I??t Rating (660V)
28000 A^2/s
Nominal Current (RMS DC)
200 Amp
Tested Breaking Capacity
200kA @ 690VAC
Dimensions
40 x 100 x 20mm (Size 000)
Hole Centers
78mm
Mounting Style
Busbar or Panel Mount with Standoff
Operating Temperature Range
-40DegC / 125DegC
Watt Loss
37W
Termination Style
M8
Unit Weight
134g
Factory Pack Qty
10
Datasheet
Product Datasheet
Trent I^2t (aR) Blade Style Semiconductor Fuse, 80 Amp, 690VAC, Square Body, Size_Body Size 1*/80, DIN 43 653, 200kA (78mm Hole Centers) F170M3011
Features
Square Body, Size_Body Size 1*/80, DIN 43 653
Wide Range of I^2t
Ratings up to 2000 Amp
Busbar or Fuse Holder Mounted
IEC Standard 60269.1 AND 4
690 V Voltage Rating complying with IEC 33
Applications
Protection of High Powered Semiconductors according to I??t
Short Circuit Protection
DC or AC Motor I??t Protection
Battery Fuse
Specification
Trent Part Number
F170M3011
Fuse Type
I^2t AR Class
Nominal Voltage
690VAC @ 50Hz
I^2t Rating (660V)
1250A^2/s
Nominal Current (RMS DC)
80 Amp
Tested Breaking Capacity
200kA (78mm Hole Centers) @ 690VAC
Dimensions
45 x 104 x 45mm
Hole Centers
78mm
Mounting Style
Busbar or Panel Mount with Standoff
Operating Temperature Range
-40DegC / 125DegC
Watt Loss
18W
Termination Style
M10
Unit Weight
350g
Factory Pack Qty
10
Datasheet
Product Datasheet
Trent I^2t (aR) Blade Style Semiconductor Fuse, 350 Amp, 690VAC, Square Body, Size 1, 200kA (78mm Hole Centers) F170M4011
Features
Square Body, Size 1
Wide Range of I^2t
Ratings up to 2000 Amp
Busbar or Fuse Holder Mounted
IEC Standard 60269.1 AND 4
690 V Voltage Rating complying with IEC 33
ApplI^2tions
Protection of High Powered Semiconductors according to I^2t
Short Circuit Protection
DC or AC Motor I^2t Protection
Battery Fuse
Specification
Trent Part Number
F170M4011
Fuse Type
I^2t AR Class
Nominal Voltage
690VAC @ 50Hz
I^2t Rating (660V)
59000A^2/s
Nominal Current (RMS DC)
350 Amp
Tested Breaking Capacity
200kA (78mm Hole Centers) @ 690VAC
Dimensions
53 x 104 x 53mm
Hole Centers
78mm
Mounting Style
Busbar or Panel Mount with Standoff
Operating Temperature Range
-40DegC / 125DegC
Watts Dissipation
60W
Termination Style
M10
Unit Weight
350g
Factory Pack Qty
10
Datasheet
Product Datasheet