Trent 200BBF Series 690V, 200 Amp aR Semiconductor I²t Fuse BS88 Style 200kA Breaking
Features
British Standard Fuse Links Package
Wide Range of I²t
Ratings up to 1000 Amp
Busbar or Standoff Mounting
IEC Standard 60269.1 AND 4
690 V Voltage Rating complying with IEC 33
Applications
Protection of High Powered Semiconductors according to I²t
Short Circuit Protection
DC or AC Motor I²t Protection
Battery Fuse
Specification
Trent Part Number
200BBF
Fuse Type
I²t aR Class
Nominal Voltage
690VAC @ 50Hz
I²t Rating
Nominal Current (RMS + DC)
200 Amp
Tested Breaking Capacity
200kA @ 690VAC
Dimensions
79.4 x 24 x 110mm
Hole Centers
75.2 x 93.6mm
Mounting Style
Busbar or Panel Mount with Standoff
Operating Temperature Range
-40°C / 125°C
Watt Loss
62W
Termination Style
M6
Unit Weight
400g
Factory Pack Qty
10
Datasheet
Product Datasheet
Cross Reference Chart
Magnelab MCT-0016-020, 20 Amp, Loop Powered AC Current Transducer, Average RMS, 4-20mA Output, Accuracy +/-2% (Ripple)
Features
Average RMS Output
Split Core
4-20mA Current Output
Cable Mounting
20-30VDC Loop Powered
Isolated plastic case recognised according to UL94-V0
UL, CE, ROHS Approved
Advantages
Large aperture for cable up to ⌀ 24mm
High isolation between primary and secondary circuits
Easy installation
Applications
Current Measurement
Energy Management
Motor Control
Actuators
Lamp Failure
Specification
Magnelab Part Number
MCT-0016-020
Technology
AC Current Transducer
Protection Class
IP50
Supply Voltage
20-30VDC Loop Powered (10mA)
Load Current (RMS)
20 Amp
Output
4-20mA (Average RMS)
Isolation
3.5kV (AC, 50Hz, 1 min)
Bandwidth
50 - 60Hz
Mounting Style
Din Rail Mount
Operating Temperature Range
-10°C / 65°C
Accuracy
+/-2% Ripple on output
Termination Style
Screw
Aperture
16mm
Approvals
UL, CE, ROHS
Unit Weight
170g
Factory Pack Qty
6
Datasheet
Product Datasheet
Shinko PCA1R10010 Series Digital Indicating Controllers
Program control, Fixed Point Control function are standard features
5-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
Time Signal Output
Drip-proof / Dust-proof IP66 (front panel only)
16-step, 16 Patterns with Interlinking pattern is a standard feature
UL/CSA Approved
Each unit needs just 60 mm depth panel space
EC Compliant (Details)
Applications
Kiln Controller
Timed Heatsink Process
Food Industry
Oven Controller
Furnace Controller
Specification
Shinko Part Number
PCA1R10010
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Number of Steps
16
Number of Patterns
16
Interlinkable
Yes
Input
Multirange (refer to datasheet)
Option 1
4-20mA Retransmission Output
Option 2
None
Mounting Style
96 x 96mm Panel Mount
Load Voltage Range
24VAC/DC
Termination Style
Screw
Weight
270g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CE
Yes
Datasheet
PCA Series Brochure
PCA Series User Manual
Shinko Product Guide
Fine Tuning Adjustments
LEM DK 100 B420, Split Core Hall Effect Current Transducer, 20, 50, 100A DC, 4-20mA unipolar output, 20-50VDC supply
Compact and versatile Split Core DC current sensor, selectable 50, 75, 100 Amp DC. Choice of output types: 0-20mA, 4-20 mA, 0-5 V or 0-10 V
Features
Split Core
DC Unipolar Measurement
4-20mA analogue output
Busbar, or panel mounting
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for busbar/cable up to 21.7mm sqr
High isolation between primary and secondary circuits
Easy installation
DIN Rail Kit available
Applications
-Automation Systems
Analogue current reading for remote monitoring (e.g. Motor)
-Data Loggers
Self Powered. Will not drain data logger batteries
-Panel Meters
Simple connection displays power consumption
Specification
LEM Part Number
DK 100 B420
Technology
DC Current Transformer with Process Output
ROHS
Yes
Supply Voltage
20-20VDC
Nominal Current (RMS + DC)
50,75,100 Amp Selectable
Response Time
< 100ms
Output
4-20mA Analogue
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
DC
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 85°C
Accuracy
2%
Termination Style
2 x UNC8 Cylindric Head
Unit Weight
120g
Factory Pack Qty
6
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
Gigavac GX16CEB, Contactor SPST-NO, 600+ AMP, 12-800VDC, 24VDC Coil, 8 Pin Deutch Connector, SPST-NO Auxiliary Contact, IP67, IP69K
Features
Hermetically Sealed (Patented) rated to 175 Deg C
UL1604 for Class I & II Div 2 and Class III for use in hazardous locations
IP67 & IP69K
SAE J1171 External ignition protection
ISO8846 Protection against ignition around flammable gasses
CE Approved
High Efficiency Dual DC Coils - Very low 12,24,48VDC continuous coil power with no EMI emissions or cross-talk on your system control power
Ideal for battery powered systems or where low power is needed
Built in Coils suppression for all DC Coils
Flexible package for installation
Chassi level power terminals
Salt Fog MIL-STD-810
Specification
Gigavac Part Number
GX16CEB
Main Contact Type
SPST-NO
Auxiliary Contact Type
SPST-NO
Coil Voltage
24VDC
Load Current
600+ Amp
Mechanical Life @ 0 Amp
1,000,000 Operations
Dielectric at Sea Level (leakage <1mA)
2.2kV rms
Control Input Terminals
8 Pin Deutch Connector
Aux Contact Terminals
8 Pin Deutch Connector
Special Feature
Hermetically Seal rated to 175 Deg C
Mounting Style
Panel Mount (M5)
Load Voltage Range
12-800VDC
Standards
UL1604, IP67, IP69K, SAE J1171, ISO8846
Termination Style
M12
Unit Weight
900g
Factory Pack Qty
1
Datasheet
Product Datasheet
BH-50-2-24, Split Core Hall Effect DC Current Transducer, +/-50 Amp DC, 4-20mA Bipolar output, 31mm aperture, 24VDC supply
Compact and versatile Split Core DC current sensor, +/-50 Amp DC, 4-20mA Bipolar Output
Features
⌀31mm Aperture
Split Core
DC Bipolar Measurement
4-20mA analogue output
Busbar, or DIN Rail Mounting
Isolated plastic case recognised according to UL94-V0
Advantages
High isolation between primary and secondary circuits
Easy installation
DIN Rail Mount
Applications
-Automation Systems
Analogue current reading for remote monitoring (e.g. Motor)
-Data Loggers
Self Powered. Will not drain data logger batteries
-Panel Meters
Simple connection displays power consumption
Specification
Fastron Part Number
BH-50-2-24
Technology
DC Hall Effect Current Transducer with Process Output
ROHS
Yes
Supply Voltage
24VDC
Nominal Current (DC)
+/-50 Amp DC
Response Time
< 200mS
Output
Bipolar 4-20mA Analogue
Isolation
2.5kV (AC, 50Hz, 1 min)
Bandwidth
DC
Mounting Style
DIN Rail Mount
Operating Temperature Range
-40°C / 85°C
Accuracy
1%
Termination Style
Elevator Screw
Unit Weight
120g
Factory Pack Qty
6
Datasheet
Product Datasheet
Iskra Doo KNL38G-00 + NPLG, AC Contactor 240/400/500/690V, Overload 304(10s), 320(5s), 350(1s), 900(0.001s) (each pole), 24VDC Control Voltage, 3 Pole 3 x NO, Nominal Current = 38 Amps
Capacitor duty contactors are designed to meet the requirements of capacitor duty applications. Contactors are fitted with a block of three auxiliary contacts connected in series with six quick discharge damping resistors, two per each phase. Peak current is limited to the value within the contactor making capacity.
Features :
High contact reliability at low voltages
High electrical and mechanical endurance and high switching capacity
Four and Three-pole contactors
Optional auxiliary contacts
Ratings from 6 Amp to 1000 Amp
UL, CSA Approved
Advantages :
Saves costs of expensive replacement
Long electrical life
Reduces watt losses during “ON” condition, saves energy
High safety
No risk of dangerous voltage
Less maintenance and downtime
Standard control voltages: 24 V 50/60 Hz, 240 V 50/60 Hz, 415 V 50/60 Hz
Specification
Iskra Doo Part Number
KNL38G-00 + NPLG
Functions
3 Pole Contactor with (3 x NO) with 1 x NO Aux Contacts
Nominal Voltage
230/400/500/690VAC @ 50/60Hz
Current Carrying Capacity as per UL
38 Amp Continuous @ 55 Deg C
Overload Capability
304(10s), 320(5s), 350(1s), 900(0.001s)
Auxiliary Contacts
1 x NO (+Optional Snap On 4 Pole NPL3)
Trip Delay Time
2-10ms
Electrical Life
200,000 Ops
Operating Temperature
-25 to 55 Deg C
Mechanical Operations
10.000,000 Ops
Control Voltage
24VDC
Power Dissipation
2.3W
Approvals
UL, CSA
Standards
IEC/EN 60947-4-1, AS/NZ 61009-1
Weight
200g
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
Contactor Catalogue
Iskra Contactor Catalogue
Crydom CKRD2430P, Solid State Relay, Single Phase 4-32VDC Control, 30A, 24-280VAC Load, w/Varistor, Din Rail
Features
• Ratings from 10A to 30 Amp @ 24-280 VAC
• SCR output for heavy industrial loads
• Zero voltage or instantaneous turn-on outputs
• UL/CSA/VDE Approved, CE Compliant to EN60950-1
• Improved SEMS screw and washer
• Redesigned housing with anti-rotation barriers
• AC & DC control types
• Direct bond copper substrate
• EMC compliant to Level 3
• Direct power lead frame
• Epoxy free design
Spec
Crydom Part Number
CKRD2430P
Switching Type
Zero Crossing
ROHS
Yes (Details)
Control Voltage
4-32VDC
Load Current
30 Amp (rms) @ 25 Deg C Ambient, 25.5 Amp (rms) @ 40 Deg C Ambient
Surge Capability
1200 Amp (peak)
Special Feature
Varistor for Overvoltage Protection
Mounting Style
DIN Rail Mount
Load Voltage Range
24-280VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
280g
Factory Pack Qty
20
Datasheet
Product Datasheet
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Crydom HS211 + D2425T, Panel or slide on Din Rail Solid State Relay, 3-32VDC Control Input, 24-280VAC Output, 23 Amps
Features
Ratings from 25A to 125 Amp @24-280 VAC
SCR output for heavy industrial loads
Zero voltage or instantaneous turn-on outputs
UL/CE/ROHS Compliant
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Panel Mount
Din Rail Mount
Spec
Part Number
HS211 + D2425T
Switching Type
Zero Crossing
ROHS/CE/UL
Yes
Control Voltage
3-32VDC
Load Current
25 Amp (rms) @ 40 Deg C
Surge Capability
239 Amp (peak)
Special Feature
Gen 3 Optocoupler
Mounting Style
Din Rail or Panel Mount
Load Voltage Range
24-280VAC
Max Non Repetitive Peak Voltage
600 Vp
Termination Style
Screw Terminals
Dimensions
L:81mm x W:45mm x D:73.4mm
Unit Weight
296g
Factory Pack Qty
20
Datasheet
HS211
D2425T
Notifications
Please note Changes from Gen 3 to Gen 4 (current) package design here
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
RCT-1200 Single Phase Flexible Current Sensor System:
The RCS-1200 Single Phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-1200 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Specification
Magnelab Part Number
RCT-1200-3000
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
3000 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 3000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
4 Inch
Coil Circumference
12 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
Magnelab HCT-0036-500, Split Core DC Hall Effect Current Sensor, 500 Amp, +/-4V Output, Split Core 36mm Aperture, X = 1%
Features
Open loop transducer using Hall effect
Compact and versatile
Panel mounting-Horizontal or Vertical
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
Very good accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Current overload capability
Low power consumption
Applications
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications.
Specification
Magnelab Part Number
HCT-0036-500
Technology
Split Core Open Loop Hall Effect
Aperture
ø36mm
ROHS
Yes
Supply Voltage
+/-15 VDC Bipolar, Isolated
Load Current (RMS + DC)
500 Amp
Measurement Range
+/-750 Amp
Output
+/-4 V
Isolation
4 kV
Bandwidth
DC
Mounting Style
Panel Mount
Operating Temperature Range
-25°C / 75°C
Accuracy
1%
Termination Style
Flying Lead
Unit Weight
400g
Factory Pack Quantity
10
Datasheet
Product Datasheet
FPT-135 1500/5A 5P35 5VA Protection Class CT, 1500/5A, Class 5P35 5VA, 135 x 81mm Aperture
Features
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Applications
Protection Relays
Safety Equipment
Fault Monitoring
??
Specification
Fastron Electronics Part Number
FPT-135 1500/5A 5P35 5VA
Technology
Protection Class Current Transformer
Ratio
1500/5
Aperture Size
81 x 135mm
VA Rating
5VA
Accuracy Class
Class 5P35
Output
5 Amp AC (?%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10??C / 50??C
Continuous Current (max)
1500Amp x 1.3
Termination Style
Screw
Stanbards
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Unit Weight
7kg
Factory Pack Qty
1
??
Datasheet
Product Installation Guide and Datasheet
??