RCS-1800-1500 Three-Phase Flexible Current Sensor System (Rogowski Coils):
The RCS-1800 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-1800 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Suitable Alternative to Solar Edge CTRC-07500-1500
Specification
Magnelab Part Number
RCS-1800-1500
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
1500 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 1500 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
6 Inch
Coil Circumference
18 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
RCS-2400-1500 Three-Phase Flexible Current Sensor System(Rogowski Coils):
The RCS-2400 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-2400 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Specification
Magnelab Part Number
RCS-2400-1500
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
1500 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 1500 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
8 Inch
Coil Circumference
24 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
RCS-3600-2000 Three-Phase Flexible Current Sensor System (Rogowski Coils):
The RCS-3600 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-3600 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Specification
Magnelab Part Number
RCS-3600-2000
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
2000 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 2000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
12 Inch
Coil Circumference
36 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
RCS-3600-2500 Three-Phase Flexible Current Sensor System (Rogowski Coils):
The RCS-3600 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-3600 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Specification
Magnelab Part Number
RCS-3600-2500
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
2500 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 2500 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
12 Inch
Coil Circumference
36 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
Infineon DDB6U134N16RR 3 Phase Diode Rectifier Bridge, 134 Amp, 1600V, 42 x 94mm Package
Features
Package with DCB ceramic base plate
Isolation voltage 3600 V∼
Planar glass passivated chips
Low forward voltage drop
Leads suitable for PC board soldering
UL registered, E 148688
Applications
Heat and temperature control for industrial furnaces and chemical processes
Lighting control
Motor control
Power converter
Advantages
Easy to mount with two screws
Space and weight savings
Improved temperature and power cycling capability
High power density
Specification
Infineon Part Number
DDB6U134N16RR
AC Line voltage
533V
Device Configuration
Three Phase Rectifier Bridge
DC Output @ 100 Deg C
134 Amp
Package Size
W:45mm L:107.5mm D:20.5mm
Itsm
650 A
VF(to)
0.75V
Tj(max)
150°C
rF
Not Published
Terminals
Press Fit
Hole Centres
93mm (M5)
Gate Terminals
N/A
R th(j-c)
0.7°C/W
R th(c-h)
0.25°C/W
Weight
185g
Isolation
3kV
Factory Pack Qty
10
Certification
UL Listed
Infineon Headquarters
Germany
Datasheet
Product Datasheet
Infineon T880N18TOF Thyristor(SCR) Capsule
Features
Very low forward voltage drop
Very low leakage current
International standard package
58/14 Package
Press Mounted
Double or Single Sided Cooling
Applications
Power Supplies
Rectifier for drives applications
Controlled Rectifiers
AC Switch
Battery Chargers
Phase Controllers
Water Cooled AC switches
Power Factor Correction
Specification
Infineon Part Number
T880N18TOF
Vrrm
1800V
SCR Configuration
Thyristor(SCR) Capsule PUK
IF(av) @ 85 Deg C
880 Amp
Package Size
ø58 x 14mm
Itsm
17.5 kA
VF(to)
.85V
Tj(max)
125°C
rF
0.27mΩ
Gate Terminals
Faston 4.8 x 0.8mm & 2.8 x 0.8mm
R th(j-c) (double sided cooled 180°sin)
0.032°C/W
R th(c-h) (double sided cooled)
0.005°C/W
Weight
300g
Clamping Force
10.5 - 21kN
Factory Pack Qty
12
Certification
ROHS
Infineon Headquarters
Germany
Datasheet
Product Datasheet
Alternatives
Contact Us for Possible Replacement
Heatsink
Heatsink Profiles
LEM DHAB S/118 Series O/L Automotive AC/DC Current Transducer, Multirange
Features
Open Loop Transducer using Hall Effect
Low Voltage Application
Unipolar +5V Power Supply
Primary Current Measuring Range up to +/-30A, and +/-350A for Channel 2
Maximum RMS primary admissable current: defined by busbar to have T° < +150°C
Operating Temperature Range: -40°C < T° < +125°C
Output Voltage: Full ratio-metric (in sensitivity and offset)
Dual Channel Sensor for Wider Measurement Range and Redundancy
Advantages
Good Accuracy for High and Low Current Range
Good Linearity
Low Thermal Offset Drift
Low Thermal Sensitivity Drift
Hermetic Package
Automotive Applications
Battery Pack Monitoring
Hybrid Vehicles
EV and Utility Vehicles
Specification
LEM Part Number
DHAB S/118
Technology
Multirange Open Loop Hall Effect
ROHS
Yes
Supply Voltage
5 VDC
Load Current Channel 1 (RMS)
+/-30 Amp
Load Current Channel 2 (RMS)
+/-350 Amp
Output
0.25 - 4.75V (2.5Vref)
Isolation
2.5kV (AC, 50Hz, 1 min)
Bandwidth(-3dB)
DC - 1.1kHz
Mounting Style
Panel Mount/Cable Mount
Aperture
⌀22.5mm
Operating Temperature Range
-40°C - 70°C
CH1 Accuracy @ 25 Deg C
0.15%(0A),0.45%(20A),0.7%(30A)
CH2 Accuracy @ 25 Deg C
1%(0A),3.5%(175A),5%(350A)
Termination Style
TYCO 1-1456426-5
Unit Weight
100g
Factory Pack Qty
6
Datasheet
Product Datasheet
Vishay VSKD91/16, Dual Diode Module, 91 Amp, 1600V
Features
Thyristor for line frequency
Solder - Solder Bonded
Electrically insulated base plate
Industrial standard package
3600V Isolation
22mm Base Width
Applications
Power Converter
Line rectifying 50/60 Hz
Controlled Rectifiers
Softstart AC motor control
AC power control
Lighting and temperature control
Specification
Vishay Part Number
VSKD91/16
Vrrm
1600V
Diode Configuration
Dual Diode Module
IF(av) @ 112 Deg C
100 Amp
Package Size
W:22mm L:93mm D:30mm TO-240AA
Itsm
2.02 kA
VF(to)
0.89V
Tj(max)
150°C
rF
2.05mΩ
I(gt) @ 25 Deg C
N/A
Terminals
M5 Screw
Hole Centres
80mm (M6)
Gate Terminals
N/A
R th(j-c)
0.22°C/W
R th(c-h)
0.1°C/W
Weight
75g
Mounting Torque
4 Nm (3 Nm Terminals)
Factory Pack Qty
10
Certification
UL Listed, ROHS
Country of Origin
India
Datasheet
Product Datasheet
Alternatives
See DD89N14K or DD104N14K for Infineon Alternative
Fastron Electronics GT-DVO(0-100V)D-1, DC Voltage Transducer, 0-100VDC input, 22-60VAC/DC aux, 4-20mA output
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
GTD-DVO(0-100V)D-1
Control Output
4-20mA
Input
0 - 100VDC
Over Range
x 1.5
Operating Temperature
0 - 60°C
Load Voltage
22 - 60VDC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Fastron Electronics AM5H-A-DV5-D-NAN, 96x48mm Digital Voltmeter 0-36VDC with 4-20mA output, 20-60VDC supply, 5 Digit
Adjustable Zero and Span Setting
Adjustable Display Scaling
Large 5 Digit 20.3mm (8 Inch) LED Display
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 96 x 48mm Panel Space
90mm Depth
Specification
Fastron Electronics Part Number
AM5H-A-DV5-D-NAN
Conditioner Output
4-20mA
Input
0 - 36VDC
Over Range
x 1.5
Operating Temperature
0 - 60°C
Load Voltage
20-60VDC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Display Type
5 Digit RED LED
Termination Style
Screw
Mounting Style
96 x 48mm Panel Mount
Case Material
PC - UL 94 V0
Weight
320g
Factory Pack Qty
1
Datasheet
Product Datasheet
User Manual
Application Notes
Panel Meters Blog Articles
MS Power MSD85N16MB Series Stud Mount Rectifier Diode
Features
Full blocking capability over wide temperature range
Hermetic metal case with glass insulator
Threaded stud
Applications
Power Supplies
Uncontrolled Rectifiers
Oil Cooled Circuits
Battery Chargers
Specification
MS Power Part Number
MSD85N16MB
Vrrm
1600V
Diode Configuration
Cathode Stud
IF(av) @ 100 Deg C
95 Amp
IF(av) @ 125 Deg C
70 Amp
Itsm
1.15 kA
VF(to)
0.85V
Tj(max)
180°C
rF
3mΩ
Termination Style (Tail)
Solder Tab
Termination Style (Stud)
3/8" -24UNF2A
Tail Length to Stud
158mm
R th(j-c)
0.55°C/W
R th(c-h)
0.20°C/W
Weight
40g
Mounting Torque
4 Nm
Factory Pack Qty
10
Country Of Origin
China
MS Power Headquarters
Germany
Datasheet
Product Datasheet