LEM AHR 1500 B420, AHR 1500 B420, Hall Effect Current Sensor, 1500Amp, True RMS 4-20mA output, 104 x 40mm aperture
Compact and versatile transducers for high AC and DC currents from 500 to 2000A True RMS with signal conditioning. Choice of output types: 4-20 mA, 0-5 V or 0-10 V, Bandwidth: DC 20..6000 Hz
Features
Split Core
VFD and SCR waveforms current measurement
True RMS output
4-20mA current output
Busbar mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable or busbar up to 104 x 40mm
High isolation between primary and secondary circuits
Easy installation
Applications
-AC Power Supplies or Motors
True RMS sensing - the most accurate way to monitor power supply or input power
-VFD Controlled Loads
VFD output indicates how the motor and attached load are operating
-SCR Controlled Loads
Accurate measurement of phase angle fired or burst fired(time proportional) SCR's and switch mode rectifiers. Current measurement gives faster response than temperature measurement.
-Renewable Energy Installations or Backup Batteries
Continuous condition monitoring allowing automatic failure detection and prediction
-Application Domain
Energy and Automation
Specification
LEM Part Number
AHR 1500 B420
Technology
Open Loop Hall Effect
ROHS
Yes
Supply Voltage
20 - 50V
Nominal Current (RMS + DC)
1500 Amp
Maximum Measurement Current (Peak)
2500 Amp
Output
4-20mA
Isolation
5.8kV (AC, 50Hz, 1 min)
Bandwidth
20-6000Hz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
1%
Termination Style
SFKC 2.5/4-ST-5.08-RF(Phoenix Contact)
Unit Weight
650g
Factory Pack Qty
6
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM AHR 800 B10, Hall Effect Current Sensor, 800Amp, True RMS 0-10V output, 104 x 40mm aperture
Compact and versatile transducers for high AC and DC currents from 500 to 2000A True RMS with signal conditioning. Choice of output types: 4-20 mA, 0-5 V or 0-10 V, Bandwidth: DC 20..6000 Hz
Features
Split Core
VFD and SCR waveforms current measurement
True RMS output
0-10V voltage output
Busbar mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable or busbar up to 104 x 40mm
High isolation between primary and secondary circuits
Easy installation
Applications
-AC Power Supplies or Motors
True RMS sensing - the most accurate way to monitor power supply or input power
-VFD Controlled Loads
VFD output indicates how the motor and attached load are operating
-SCR Controlled Loads
Accurate measurement of phase angle fired or burst fired(time proportional) SCR's and switch mode rectifiers. Current measurement gives faster response than temperature measurement.
-Renewable Energy Installations or Backup Batteries
Continuous condition monitoring allowing automatic failure detection and prediction
-Application Domain
Energy and Automation
Specification
LEM Part Number
AHR 800 B10
Technology
Open Loop Hall Effect
ROHS
Yes
Supply Voltage
20 - 50V
Nominal Current (RMS + DC)
800 Amp
Maximum Measurement Current (Peak)
2500 Amp
Output
0-10V
Isolation
5.8kV (AC, 50Hz, 1 min)
Bandwidth
20-6000Hz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
1%
Termination Style
SFKC 2.5/4-ST-5.08-RF(Phoenix Contact)
Unit Weight
650g
Factory Pack Qty
6
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM AK Series Average RMS Solid Core AC Current Sensor with Process Outputs
Compact and versatile Solid Core AC current sensor, selectable 2 or 5 Amp Average RMS. Choice of output types: 4-20 mA, 0-5 V or 0-10 V
Features
Solid Core
Average RMS output
4-20mA current output
Busbar, or panel mounting
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable up to ?19mm
High isolation between primary and secondary circuits
Easy installation
DIN Rail Kit available
Applications
-Automation Systems
Analogue current reading for remote monitoring (e.g. Motor)
-Data Loggers
Self Powered. Will not drain data logger batteries
-Panel Meters
Simple connection displays power consumption
Specification
LEM Part Number
AK 5 C420L,
Technology
AC Current Transformer with Process Output
ROHS
Yes
Supply Voltage
24VDC Loop Powered
Nominal Current (RMS + DC)
2, 5 Amp Selectable
Maximum Measurement Current (Peak)
3.4, 10.1 Amp
Output
4-20mA Average RMS
Aperture
?19mm
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 85°C
Accuracy
1%
Termination Style
2 x UNC8 Cylindric Head
Unit Weight
120g
Factory Pack Qty
6
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM AP 100 B420L, Split Core AC Current Sensor, selectable 50, 75,100 Amp, Average RMS 4-20mA output, Infinite Overload Capability
Compact and versatile Split Core AC current sensor, selectable 50, 75, 100Amp Average RMS 4-20mA output
Features
Split Core
Average RMS output
4-20mA process output
Busbar, or Din Rail mounting
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for busbar/cable up to 18.5mm x 18.5mm
High isolation between primary and secondary circuits
Easy installation
DIN Rail Mount
Applications
-Automation Systems
Analogue current reading for remote monitoring (e.g. Motor)
-Data Loggers
Self Powered. Will not drain data logger batteries
-Panel Meters
Simple connection displays power consumption
Specification
LEM Part Number
AP 100 B420L
Technology
AC Current Transformer with Process Output
ROHS
Yes
Supply Voltage
24VDC @ 30mA
Nominal Current (RMS + DC)
50, 75, 100 Amp Selectable
Overload
Infinite
Output
4-20mA Average RMS
Isolation
5kV (AC, 50Hz, 1 min)
Bandwidth
30-2000Hz
Mounting Style
Din Rail mount or Busbar mount
Operating Temperature Range
-40°C / 85°C
Accuracy
1%
Termination Style
Spring Terminal Block (Female Included)
Unit Weight
90g
Factory Pack Qty
6
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM AP 400 B420L, Split Core AC Current Sensor, selectable 200, 300, 400 Amp, Average RMS 4-20mA output, Infinite Overload Capability
Compact and versatile Split Core AC current sensor, selectable 200, 300, 400 Amp Average RMS 4-20mA output
Features
Split Core
Average RMS output
4-20mA current output
Busbar, or Din Rail mounting
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for busbar/cable up to 18.5mm x 18.5mm
High isolation between primary and secondary circuits
Easy installation
DIN Rail Mount
Applications
-Automation Systems
Analogue current reading for remote monitoring (e.g. Motor)
-Data Loggers
Self Powered. Will not drain data logger batteries
-Panel Meters
Simple connection displays power consumption
Specification
LEM Part Number
AP 400 B420L
Technology
AC Current Transformer with Process Output
ROHS
Yes
Supply Voltage
24VDC @ 30mA
Nominal Current (RMS + DC)
200,300,400 Amp Selectable
Overload
Infinite
Output
4-20mA Average RMS
Isolation
5kV (AC, 50Hz, 1 min)
Bandwidth
30-2000Hz
Mounting Style
Din Rail mount or Busbar mount
Operating Temperature Range
-40°C / 85°C
Accuracy
1%
Termination Style
Spring Terminal Block (Female Included)
Unit Weight
90g
Factory Pack Qty
6
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM APR 100 B420L, Split Core AC Current Sensor, selectable 50, 75, 100 Amp, True RMS 4-20mA output, Infinite Overload Capability
Compact and versatile Split Core AC current sensor, selectable 50, 75, 100 Amp True RMS 4-20mA output
Features
Split Core
True RMS output
4-20mA current output
Busbar, or Din Rail mounting
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for busbar/cable up to 18.5mm x 18.5mm
High isolation between primary and secondary circuits
Easy installation
DIN Rail Mount
Applications
-Automation Systems
Analogue current reading for remote monitoring (e.g. Motor)
-Data Loggers
Self Powered. Will not drain data logger batteries
-Panel Meters
Simple connection displays power consumption
Specification
LEM Part Number
APR 100 B420L
Technology
AC Current Transformer with Process Output
ROHS
Yes
Supply Voltage
24VDC @ 30mA
Nominal Current (RMS + DC)
50,75,100 Amp Selectable
Overload
Infinite
Output
4-20mA True RMS
Isolation
5kV (AC, 50Hz, 1 min)
Bandwidth
30-2000Hz
Mounting Style
Din Rail mount or Busbar mount
Operating Temperature Range
-40°C / 85°C
Accuracy
1%
Termination Style
Spring Terminal Block (Female Included)
Unit Weight
90g
Factory Pack Qty
6
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM DHR 1000 C10, Hall Effect Current Sensor, 1000Amp RMS ,10V output, 32mm aperture
Compact and versatile transducers for high AC and DC currents from 100 to 1000A True RMS with signal conditioning. Choice of output types: 4-20 mA, 0-5 V or 0-10 V, Bandwidth: DC 20..6000 Hz
Features
VFD and SCR waveforms current measurement
True RMS output
4-20mA current output
Panel mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable up to ?32mm
High isolation between primary and secondary circuits
Easy installation
Applications
-VFD Controlled Loads
VFD output indicates how the motor and attached load are operating
-SCR Controlled Loads
Accurate measurement of phase angle fired or burst fired(time proportional) SCR's. Current measurement gives faster response than temperature measurement
-Application Domain
Energy and Automation
Specification
LEM Part Number
DHR 1000 C10
Technology
Open Loop Hall Effect
ROHS
Yes
Supply Voltage
20 - 50V
Load Current (RMS + DC)
1000 Amp
Output
0-10V
Isolation
4kV (AC, 50Hz, 1 min)
Bandwidth
20-6000Hz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
Level 3
Termination Style
SFKC 2.5/4-ST-5.08-RF(Phoenix Contact)
Unit Weight
260g
Factory Pack Qty
6
Datasheet
Product Datasheet
LEM DHR 600 C420, Hall Effect Current Sensor, 600Amp RMS , 4-20mA output, 32mm aperture
Compact and versatile transducers for high AC and DC currents from 100 to 1000A True RMS with signal conditioning. Choice of output types: 4-20 mA, 0-5 V or 0-10 V, Bandwidth: DC 20..6000 Hz
Features
VFD and SCR waveforms current measurement
True RMS output
4-20mA current output
Panel mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable up to ?32mm
High isolation between primary and secondary circuits
Easy installation
Applications
-VFD Controlled Loads
VFD output indicates how the motor and attached load are operating
-SCR Controlled Loads
Accurate measurement of phase angle fired or burst fired(time proportional) SCR's. Current measurement gives faster response than temperature measurement
-Application Domain
Energy and Automation
Specification
LEM Part Number
DHR 600 C420
Technology
Open Loop Hall Effect
ROHS
Yes
Supply Voltage
20 - 50V
Load Current (RMS + DC)
600 Amp
Output
4-20mA
Isolation
4kV (AC, 50Hz, 1 min)
Bandwidth
20-6000Hz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 70°C
Accuracy
Level 3
Termination Style
SFKC 2.5/4-ST-5.08-RF(Phoenix Contact)
Unit Weight
260g
Factory Pack Qty
6
Datasheet
Product Datasheet
GO 30-SMS/SP3, O/L Hall Effect Current Sensor with evaluation PCB, 30 Amp
Features
Hall effect measuring principle
Galvanic separation between primary and secondary circuit
Insulated test voltage 3000 V RMS
Low power consumption
Extremely low profile
Single power supply +5 V
Double overcurrent detection
Fixed offset & sensitivity
Response time 2 µs.
Advantages
Small size and space saving
High immunity to external interference
High insulation capability Industrial.
Low electrical resistance (0.75 mΩ)
No magnetic hysteresis
Robust against external fields and cross-talk.
Applications
Appliances
Small drives
HVAC
Solar
E-Bikes
Standards
IEC 62109-1: 2010
IEC 60950-1: 2005
IEC 61800-5-1: 2007
UL 1577: 2014.
Application Domains
Industrial
Specification
LEM Part Number
GO 30-SMS/SP3
Technology
Open Loop Hall Effect
ROHS
Yes
Supply Voltage
3.3 VDC
Load Current (RMS + DC)
30 Amp
Overload Capability
+/-200 Amp
Output
2.5 Vref
Isolation
2.5 kV
Bandwidth
DC-300 kHz
Mounting Style
Surface Mount - SOIC 8 Pin
Operating Temperature Range
-40°C / 125°C
Accuracy
2%
Termination Style
N/A
Unit Weight
10g
Factory Pack Quantity
150
Datasheet
Product Datasheet
LEM HAT 1000-S O/L Hall Effect Current Transducer, 1000 Amp, +/-15V Supply, 40.5 x 30.5 Square Aperture, +/-4V Output
Features
Bandwidth DC to 5kHz
Open loop transducer using Hall effect
Compact and versatile
Panel mounting-Horizontal or Vertical
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
Very good accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Current overload capability
Low power consumption
Wide dynamic range, nominal 100 to 1500 A in one package.
Up to 2500 A measurement range
Applications
AC variable speed drives and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications.
Specification
LEM Part Number
HAT 1000-S
Technology
Open Loop Hall Effect
Aperture
40.5 x 30.5mm Square
ROHS
Yes
Supply Voltage
+/-15 VDC Bipolar, Isolated
Load Current (RMS + DC)
1000 Amp
Measurement Range
+/-2500 Amp
Output
+/-4 V
Isolation
4.9 kV
Bandwidth
DC-25 kHz
Mounting Style
Panel Mount
Operating Temperature Range
-10°C / 80°C
Accuracy
1%
Termination Style
Molex 5045-04A
Unit Weight
300g
Factory Pack Quantity
10
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM HAT 1200-S O/L Hall Effect Current Transducer, 1200 Amp, +/-15V Supply, 40.5 x 30.5 Square Aperture, +/-4V Output
Features
Bandwidth DC to 5kHz
Open loop transducer using Hall effect
Compact and versatile
Panel mounting-Horizontal or Vertical
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
Very good accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Current overload capability
Low power consumption
Wide dynamic range, nominal 100 to 1500 A in one package.
Up to 2500 A measurement range
Applications
AC variable speed drives and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications.
Specification
LEM Part Number
HAT 1200-S
Technology
Open Loop Hall Effect
Aperture
40.5 x 30.5mm Square
ROHS
Yes
Supply Voltage
+/-15 VDC Bipolar, Isolated
Load Current (RMS + DC)
1200 Amp
Measurement Range
+/-2500 Amp
Output
+/-4 V
Isolation
4.9 kV
Bandwidth
DC-25 kHz
Mounting Style
Panel Mount
Operating Temperature Range
-10°C / 80°C
Accuracy
1%
Termination Style
Molex 5045-04A
Unit Weight
300g
Factory Pack Quantity
10
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM HAT 800-S O/L Hall Effect Current Transducer, 800 Amp, +/-15V Supply, 40.5 x 30.5 Square Aperture, +/-4V Output
Features
Bandwidth DC to 5kHz
Open loop transducer using Hall effect
Compact and versatile
Panel mounting-Horizontal or Vertical
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
Very good accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Current overload capability
Low power consumption
Wide dynamic range, nominal 100 to 1500 A in one package.
Up to 2500 A measurement range
Applications
AC variable speed drives and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications.
Specification
LEM Part Number
HAT 800-S
Technology
Open Loop Hall Effect
Aperture
40.5 x 30.5mm Square
ROHS
Yes
Supply Voltage
+/-15 VDC Bipolar, Isolated
Load Current (RMS + DC)
800 Amp
Measurement Range
+/-2400 Amp
Output
+/-4 V
Isolation
4.9 kV
Bandwidth
DC-25 kHz
Mounting Style
Panel Mount
Operating Temperature Range
-10°C / 80°C
Accuracy
1%
Termination Style
Molex 5045-04A
Unit Weight
300g
Factory Pack Quantity
10
Datasheet