Eastron Europe SDM120CTModbus-MID-100mV, DIN Rail Mount kWh Meter, Single Phase, 240VAC aux, Class 1/Class B, 100mV CT Connect, w/ 2 x pulse outputs and RS485 Comms, MID Approved. *Best accuracy for low current measurements
100mV CT Connect
1 x Configurable Pule Output (via Modbus)
1 x Fixed Pulse Output (1000imp/kwh)
RS 485 communication up to 38,400 bit/s as standard
Optional Mbus Model available
True RMS values of currents and voltages
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
Accuracy Class 1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM120CTModbus-MID-100mV
Functions
Single Phase Energy Meter
Supply Voltage
230V L-N, 5 Amp +/-15% < 5VA
Nominal Measurement Range
230V L-L 230V L-N, 45 Amp
Maximum Measurement Range
276V L-L 230V L-N, 45 Amp
Nominal Current Input
100mV Amp CT
Pulse Output
1 x 1000imp/kwh, 1 x Configurable 60/100(default)/200ms
Primary CT Ratio
5,10,20,30,40,50,75,100,125,150,200,250,300,400,600 Amp
Accuracy
Class 1/ Class B (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
24mm x 100mm x 66mm (1 module wide)
Isolation
4kV
RS485
2400-38400 b/s
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 6 Modules
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
User Manual
Modbus Protocol
Setup Video
Modbus Utility
EEM Meter Setting Software Utility
Fastron Electronics AM5S-R-VEH-D-R1, 48x24mm Frequncy/RPM Counter 0.1-100kHz, 12-24VAC/DC Pulse Input, 22-60VDC supply
Large 5 Digit 0.4 Inch LED Display
250mS Response Time
PC 94 UL V0
Input signals can be NPN, PNP, or 24VDC Pulses depending on the model used
Each unit needs just 48 x 24mm Panel Space
86.2mm Depth
Specification
Fastron Electronics Part Number
AM5S-R-VEH-D-R1
Input
10.8 - 24VDC
Measurement Range
0.1Hz - 100kHz
Operating Temperature
0 - 60°C
Load Voltage
22-60VAC/DC
Termination Style
Screw
Mounting Style
48 x 24mm Panel Mount
Case Material
PC - UL 94 V0
Safety Approvals
CE
Weight
320g
Factory Pack Qty
1
Datasheet
Product Datasheet
Application Notes
Panel Meters Blog Articles
Crydom A2450G, Solid State Relay, Single Phase 90-280VAC Control, 50A, 24-280VAC Load, w/status LED
Features
• Ratings from 25A to 125 Amp @ 24-280 VAC
• SCR output for heavy industrial loads
• Zero voltage or instantaneous turn-on outputs
• UL/CSA/VDE Approved, CE Compliant to EN60950-1
• Improved SEMS screw and washer
• Redesigned housing with anti-rotation barriers
• AC & DC control types
• Direct bond copper substrate
• EMC compliant to Level 3
• Direct power lead frame
• Epoxy free design
Spec
Crydom Part Number
A2450G
Switching Type
Zero Crossing
ROHS
Yes (Details)
Control Voltage
90 - 280VAC
Load Current
50 Amp (rms)
Surge Capability
597 Amp (peak)
Special Feature
LED Status Indicator
Mounting Style
Panel Mount
Load Voltage Range
24-280VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
75g
Factory Pack Qty
20
Datasheet
Product Datasheet
Please note Changes from Gen 3 to Gen 4 (current) package design here
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Crydom ED24C5, EMR plug in Solid State Relay, 18-32VDC control, 5 Amp 24-280VAC output
Features
Ratings 5 Amp @ 24-280VAC
Plug in EMR relay style
Motor controller rated
SCR output for reliable AC switching
Multiple modules can be wired in parallel for higher currents
UL/CSA/VDE Approved, CE Compliant to EN60950-1
EMC compliant to Level 3
Epoxy free design
Spec
Crydom Part Number
ED24C5
Switching Type
AC Load
ROHS
Yes (Details)
Control Voltage
18-32VDC
Load Current
5 Amp DC
Surge Capability (10ms)
60 Amp DC
Special Feature
Plug in EMR style
Mounting Style
EMR Base
Load Voltage Range
24-280VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
38g
Factory Pack Qty
10
Datasheet
Product Datasheet
Socket
DRSED
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Fastron FDV-1000-V10-24, DC Voltage Transducer, Din Rail Mount, 0-1000VDC, 0-10V output, 24VDC Supply Voltage, 150mS Response
150mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 5V DC output (for voltage output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Part Number
FDV-1000-V10-24
Analogue Output
0-10V
Input
0 - 1000VDC
Measurement Range
120%
Overload
150% Continuous
Operating Temperature
-30 - 70°C
Operating Voltage
24VDC +/-15%
Voltage Isolation (1 min)
2.5kV
Accuracy
1%
Response Time
150mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Safety
CE, UL94V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Fastron FDV-100-V10-24, DC Voltage Transducer, Din Rail Mount, 0-100VDC, 0-10V output, 24VDC Supply Voltage, 150mS Response
150mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 5V DC output (for voltage output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Part Number
FDV-100-V10-24
Analogue Output
0-10V
Input
0 - 100VDC
Measurement Range
120%
Overload
150% Continuous
Operating Temperature
-30 - 70°C
Operating Voltage
24VDC +/-15%
Voltage Isolation (1 min)
2.5kV
Accuracy
1%
Response Time
150mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Safety
CE, UL94V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Crydom CKRA2430P, Solid State Relay, Single Phase 90-280VAC Control, 30A, 24-280VAC Load, w/ over voltage suppressor, Din Rail
Features
• Ratings from 10A to 30 Amp @ 24-280 VAC
• SCR output for heavy industrial loads
• Zero voltage or instantaneous turn-on outputs
• UL/CSA/VDE Approved, CE Compliant to EN60950-1
• Improved SEMS screw and washer
• Redesigned housing with anti-rotation barriers
• AC & DC control types
• Direct bond copper substrate
• EMC compliant to Level 3
• Direct power lead frame
• Epoxy free design
Spec
Crydom Part Number
CKRA2430P
Switching Type
Zero Crossing
ROHS
Yes (Details)
Control Voltage
90 - 280VAC
Load Current
30 Amp (rms)
Surge Capability
1200 Amp (peak)
Special Feature
Varistor for Overvoltage Protection
Mounting Style
DIN Rail Mount
Load Voltage Range
24-280VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
280g
Factory Pack Qty
20
Datasheet
Product Datasheet
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Fastron Electronics SCT-F24-100-40mA, 40mA, 100Amp measurement Split Core CT's, Class 1 Series Current Transformer
Features
Quick Release Split Core System
Cable Mount
40mA Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F24-100-40mA
Technology
Split Core AC Current Transformer
Ratio
100/.40 Amp
Aperture Size
ø 24 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
40mAmp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
100Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Fastron Electronics SCT-F50-600-5A, 5 Amp, 600Amp measurement Split Core CT's
Features
Quick Release Split Core System
Cable Mount
5 Amp Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F50-600-5A
Technology
Split Core AC Current Transformer
Ratio
600/5 Amp
Aperture Size
ø 50 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
5 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
600Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
1000g
Factory Pack Qty
9
Datasheet
Product Datasheet
Stocked Split Core CT's Listing
Application Notes
Installation Guide
Types of Current Transformers - Blog
Cable Losses and CT's
High Accuracy or High Burden Requirements for CT's