Fastron S-FTY220D80P, Single Phase Proportional Phase Control Module, 4-20mA,0-10V,0-5V,10K POT Input, 220VAC, 80 Amp Per Phase, Also referred to as Single Phase Voltage Regulator
4-20mA,0-10V, 0-5V or 10K POT Proportional Phase Control Input
Ratings from 25A to 120 Amp @ 180-280 VAC
SCR output for heavy industrial loads
Instantaneous turn-on output
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Specification
Trent part Number
S-FTY220D80P
Switching Type
Phase Angle (Random Crossing)
Control Voltage
4-20mA,0-10V,0-5V,10K POT Proportional Input
Load Current
80 Amp (rms) @ 40 Deg C
Surge Capability
690Amp (peak)
Special Feature
Single Phase Proportional Controller + SSR/3 Phase Voltage Regulator
Mounting Style
Panel Mount
Load Voltage Range
170-220VAC +15% (253VAC Max)
Max Non Repetitive Peak Voltage
600 Vp
Termination Style
Barrier Strip Screw
Dimensions
105 x 80 x 55mm
Unit Weight
400g
Factory Pack Qty
20
Datasheet
FTY Series Voltage Regulators
Crydom DR2260A35U, Solid State Relay 4-32VDC Control, 35A, 48-600VAC Load, Din Rail Mount, w/status LED
Features
Ratings from 20 Amp up to 35 Amp @ 600 VAC
Mosfet output for heavy industrial loads
UL/CSA/VDE Approved, CE Compliant to EN60950-1
Din Rail Mount with bonded Heat sink
Direct bond copper substrate
EMC compliant to Level 3
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
DR2260D35U
Switching Type
Zero Crossing
ROHS
Yes (Details)
Control Voltage
4 - 32VDC
Load Current (single unit)
35 Amp (rms) @ 45 Deg C Ambient, 28 Amp (rms) @ 50 Deg C Ambient
Load Current (multiple units)
25 Amp (rms) @ 40 Deg C Ambient, 20 Amp (rms) @ 50 Deg C Ambient
Surge Capability
1290 Amp RMS
Special Feature
None
Mounting Style
DIN Rail Mount
Load Voltage Range
48-600VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
298g
Factory Pack Qty
20
Â
Datasheet
Product Datasheet
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
TRV-22D-R-400, 22mm LED Voltmeter RED 20-500VAC, Plastic, IP40, IEC60947-5-1
LED indicator Series will activate while the contacts are connected to the rated voltage. Widely Used for Rugged Industrial Applications Including Critical Machinery requiring safe operation and visual Indication by the user.
Features :
400VAC Supply
20-500VAC Measurement
LED Illumination
Ø 22.5mm Cutout
Long Life
LED Replacement Beads Available
RED, GREEN, AMBER, BLUE, or Clear\White Colour
Standards :
IP40
IEC60947-5-1
CE
Specification
TRENT Part Number
TRV-22D-R-400
Functions
LED Voltmeter
Measurement Range
20-500VAC
Nominal Voltage
400VAC @ 50/60Hz
Impulse Voltage Wear Resistance
6kV
Illumination Type
Blue LED
Short Circuit Protection (Fuse)
Recommend 10A gG Fuse
Mechanical Compression Force at Closing
20N
Mechanical Compression Force at Closing
8N
Humidity
35-85%
Approvals
CE
Standards
IP65, IEC60947-5-1
Weight
Enclosure Material
UL94V0
Factory Pack Qty
1
TRENT(Fastron) Head Office
Australia
Datasheet
Product Datasheet
Fastron FC5-L-W-2-G-4 PID Controller, 24VDC with 2 Alarms, K,E,J,N,T,S,R,B Thermocouple, Linear Current/Voltage and PT100/Cu20 RTD Input, 96x96mm, Dual Relay and SSR Output
4-digit displays (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated -0-10V, Relay, 12VDC (SSR) and 4 to 20 mA DC outputs available
Each unit needs just 75 mm depth panel space
Specification
Fastron Part Number
FFC5-L-W-2-G-4
Control Output
Relay and SSR (Dual Ouptut)
Input
Multirange Type K, J, E,S,T,R, Pt100, Cu50/Linear Current 4(0)-20mA/Linear Voltage 0-10(5)V
Option 1
2 Alarms
Mounting Style
96x96mm Panel Mount
Supply Voltage
24VDC+/-15%
Termination Style
Screw
Sampling Time
100ms
Weight
150-270g
Factory Pack Qty
10
Â
Datasheet & User Manual
Datasheet
User Manual
FC5 Communication Protocol
Rishabh Rish SIGMA 75 CTR5+5+5+5/5.CL1.15VA Summation Current Transformer
Features
DIN Rail Mounting Clip Included
Built In Sealable Terminal Covers
Mounting Feet Supplied
Narrow Width (30mm)
Self Powered
Rated System Voltage 0.72/3kV
IEC185, BS 7626, BSEN 60044-1 and IEC 60044-1
Applications
Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Rishabh Part Number
Rish SIGMA 75 CTR5+5+5+5/5.CL1.15VA
Technology
AC Current Transformer
Ratio
5+5+5+5/5
VA Rating
15VA Class 1
Accuracy Class
Class 1
Output
5 Amp AC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Din Rail Mount
Operating Temperature Range
-30°C / 85°C
Continuous Current (max)
8 Amp
Termination Style
Screw
Unit Weight
500g
Factory Pack Qty
5
Â
Datasheet
Product Datasheet
E62.P17-153C60, 15uF, Heavy Duty AC Film Capacitor ø95 x 176mm, M6x12 terminals with Bushing. C2 Design, 2000VAC/3400VDC
Characteristics and utility
15uF 2000VAC/3400VDC
Metalized Polypropylene Film
Connector type - M6 x 12mm Studs
M12 Stud mounting
Standards
IEC 60831-1/2
EN 60831-1/2
Specification
Electronicon Part Number
E62.P17-153620
Technology
Metalized Polypropylene Film Capacitor
Dimensions
ø95 x 176mm
Mounting
M12 Stud
Standards
IEC 60831-1/2, EN 60831-1/2
Voltage
2000VAC/3400VDC
Operating Temperature Range
-40 to 85 °C
Capacitance
15uF
Tolerance On Capacitance
+10 / -10%
Lifetime
200,000 Hours @ 85 °C (Statistical Life)
Termination Style
M6 x 12 studs
Unit Weight
1.3kg
Factory Pack Quantity
21 (MOQ = 105)
Â
Datasheet
Product Datasheet
276.036-505710/221K02, Power Factor Correction Capacitor, Single Phase, 4.1 KVAR, 57uF, 480V, 50HZ, 65 x 148mm, DRY TYPE, Requires Discharge Resistor
Characteristics and utility
4.1 kVar @ 480V @ 50 Hz, 57.0uF
Discharge resistors required (sold seperately)
Reactive power factor correction
Dry Type (Resin Filled)
Connector type - single sided terminal
Indoor mounting
Safety
Overpressure disconnection system
Protection by internal fuses
Construction and materials
Low losses metallized self-healing polypropylene film, high density, high temperature and greater dielectric resistance Volt/µ
Polyurethane self-extinguishing resin V0, developed under standard UL 94 by RTR EnergÃa
Aluminium case with bottom fixing M12x16
Standards
IEC 60831-1/2
EN 60831-1/2
Specification
Electronicon Part Number
276.036-505710/221K02
Technology
Dry Type (Resin Filled), Low Loss, Self Healing
Dimensions
65 x 148mm
Standards
IEC 60831-1/2, EN 60831-1/2
Voltage
480V @ 50Hz
Kvar
4.1 Kvar
Capacitance
124.2uF
Tolerance On Capacitance
-5% + 10%
Imax
22 Amp
Overpressure Disconnection System
YES
Self Extinguishing Resin
YES
Internal Fuses
YES
DWCAP system (Patented) internal windings Displacement
YES
Mounting
M12 x 16mm (Indoor)
Operating Temperature Range
50°C Max, 30°C Mean(1 year), 40°C Mean(24 hrs)
Lifetime
120,000 Hours
Termination Style
Filter Type Terminal
Unit Weight
1.2kg
Factory Pack Quantity
25
Â
Datasheet
Product Datasheet
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Rishabh Rish Xmer 140-100H (45) 3000/5 Class 0.5 Series Current Transformer
Features
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
IEC185, BS 7626, BSEN 60044-1 and IEC 60044-1
Applications
Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Rishabh Part Number
Rish Xmer 140-100H (45) 3000/5 Class 0.5
Technology
AC Current Transformer
Ratio
3000/5
Aperture Size
⌀ 86mm or 101 x 31mm Busbar
VA Rating
60VA
Accuracy Class
Class 0.5
Output
5 Amp AC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-30°C / 85°C
Continuous Current (max)
3000Amp x 1.2
Termination Style
Screw
Unit Weight
1.2kg
Factory Pack Qty
9
Datasheet
Product Datasheet
Fastron Electronics GT-DVO(0-30V)D-1, Signal Isolator/DC Voltage Transducer, 0-30VDC input, 22-60VAC/DC aux, 4-20mA output
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
GT-DVO(0-30V)D-1
Control Output
4-20mA
Input
0-30V
Over Range
x 1.5
Operating Temperature
0 - 60°C
Load Voltage
22-60VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Fastron Electronics FATL500D420T, AC Current Transducer, 500Amp Measurement, 36mm Split Core, 4-20mA Average RMS Output, Accuracy = 1%, Terminal Version
Features
Quick Release 36mm Split Core System
Cale Mount
4-20mA Output
24VDc Aux
Rated System Voltage 0.60/2.5kV
0.5M Flying Leads
Applications
Control Systems
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Fastron Part Number
FATL500D420T
Technology
36mm Split Core AC Current Transformer
Ratio
500/4-20mA
Aperture Size
ø 36 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
4-20mA (+20%)
Isolation
2.5kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
500Amp x 1.2
Termination Style
Screw Terminals
Unit Weight
250g
Factory Pack Qty
9
Â
Datasheet
Product Datasheet
Application Notes
Installation Guide
Iskra Doo MT440-SSUDAAMNA, Multifunction Power Transducer, Class 0.5, 4 Wire, 600V L-N, 1/5/10Amp AC Input 50/60Hz, 24-300VDC or 40-276VAC Aux Input, 2 Programmable analogue outputs, 1 relay output, RS485 & USB Comms
Class 0.5 (EN 60688)
USB Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 50 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy class 0.5
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Specification
Iskra Doo Part Number
MT440-SSUDAAMNA
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
600V L-N, 1/5/10 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
1 x Relay Output
Tariff Input
N/A
Output(s)
2 x Analogue
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Comms
USB (standard) RS232 2400-115200 b/s (RS485 Optional)
Weight
370g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Â
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Â
Datasheet
Product Datasheet
Software
MiQen Setting Software
MIPACK Programmer
Iskra Two Pole DTS 2 UNI V2, Dual Digital Time Switch with 2 independant Daily Weekly, Monthly, and Yearly program, Universal 12-240VAC/DC Power Supply/Control, 2 x 16 Amp SPST CO Relay
DTSÂ 2 UNI V2 24-240 V AC/DC - 2 Relay 16A :
Multi-range (1 Min - Yearly)
Multi-voltage 12 →240 V AC/DC
LED status indicator
Possibility of external load connection in parallel to the control input
Specification
Iskra Part Number
DTSÂ 2 V2 UNI
Function
Yearly Time Switch
Nominal Voltage
24 → 240 V AC/DC
Digital Output
2 x C/O (SPST) (Changeover -Single Pole), 250VAC/DC @ 16 Amp
Min Breaking Current
10mA/12VDC
Timing Ranges
Minutes, Hours, Days, Weeks, Months
Minimum Pulse Duration
30ms/100ms with load
Repeatability
0.5%
Reset Time
120ms
Isolation
4kV
Repetition Accuracy
0.5%
Threshold Adjustment Range
10 → 100 % of the range
Termination Style
Screw
Weight
80g
Factory Pack Qty
1
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Â
Datasheet
User Manual
Â
Â