Hobut CTSC CLIP 200/5 Series Current Transformer
Features
Low Price Point
Split Core
1m Flying Leads
Self Powered
Rated System Voltage 0.72/3kV
IEC185, BS 7626, BSEN 60044-1 and IEC 60044-1
Flame Retardent UL94V0
Applications
Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Site Measurements
Specification
Hobut Part Number
CTSC CLIP 200/5
Technology
Split Core AC Current Transformer
Ratio
200/5
Aperture Size
⌀ 40mm
VA Rating
2.5VA
Accuracy Class
Class 1
Output
5 Amp AC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount
Operating Temperature Range
-30°C / 80°C
Continuous Current (max)
200Amp x 1.2
Termination Style
Screw
Unit Weight
800g
Factory Pack Qty
9
Datasheet
Product Datasheet
LEM HTA 300-S Series Open Loop AC/DC Hall Effect Sensor
Features
Bandwidth DC to 50kHz
Open loop transducer using Hall effect
Compact and versatile
Panel mounting-Horizontal or Vertical
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
Very good accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Current overload capability
Low power consumption
Wide dynamic range, 100 to 1000 A in one package.
Applications
AC variable speed drives and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications.
Specification
LEM Part Number
HTA 300-S
Technology
Open Loop Hall Effect
Aperture
ø32mm
ROHS
Yes
Supply Voltage
+/-15 VDC Bipolar, Isolated
Load Current (RMS + DC)
300 Amp
Measurement Range
+/-900 Amp
Output
+/-4 V
Isolation
4 kV
Bandwidth
DC-50 kHz
Mounting Style
Panel Mount
Operating Temperature Range
-10°C / 80°C
Accuracy
1%
Termination Style
Molex 5045-04A
Unit Weight
230g
Factory Pack Quantity
10
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
LEM AT 10 B420L, AC Current Transformer, 20-30VDC loop powered, 10 Amp Average RMS 4-20mA output
Features
Average RMS Output
Split Core
4-20mA Current Output
Cable Mounting
20-30VDC Loop Powered
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable up to ? 16mm
High isolation between primary and secondary circuits
Easy installation
Applications
Current Measurement
Energy Management
Motor Control
Actuators
Lamp Failure
Specification
LEM Part Number
AT 10 B420L
Technology
AC Current Transformer
Protection Class
IP50
Supply Voltage
20-30VDC Loop Powered (10mA)
Load Current (RMS)
10 Amp
Maximum Measurement Current (RMS)
12 Amp
Output
4-20mA (Average RMS)
Isolation
3.5kV (AC, 50Hz, 1 min)
Bandwidth
55 - 65Hz
Mounting Style
Din Rail Mount
Operating Temperature Range
-10°C / 65°C
Accuracy
1.5%
Approvals
? 16mm
Termination Style
Screw
Approvals
CE,UL,ROHS
Unit Weight
90g
Factory Pack Qty
6
Datasheet
Product Datasheet
FN600-5T0370G/0450P, 3 Phase 3 Wire, Variable Frequency Drive, 0.1 - 600 Hz, 37/45kW 75 Amp (Normal Duty)/91 Amp (Heavy Duty), 320-480VAC L-L, RS485 Comms
Features
3 Phase 3 Wire VFD/VSD
2 x 4-20mA, 0-10V Proportional Input Control
8Â x Digital Inputs
1 High Speed Digital Input
4 x Open Collector Outputs
1 x High Speed Open Collector Outputs
1 x C/O Relay Output
RS485
Fully enclosed IP20 (Optional IP40)
Small frame Size
Applications
Fan Motor Control
Production Lines
Transportation
Controlled Power Applications
Suitable for extreme environments such as mining
Specification
Fastron Part Number
FN600-5T0370G/0450P
Rated Operation Temperature
50°C (With Derating)
Configuration
3 Phase 3 Wire AC Variable Frequency Drive / Variable Frequnecy Drive
Control Voltage
4-20mA, 0-10V
Inputs
7 x DI / 1 x High Speed DI, 2 x Analogue
Load Current
60 Amp(Normal Duty) /Â 75 Amp(Heavy Duty)Â Per Phase
Control Range
0.1-600 Hz
Dimensions
450x280x240mm
Comms
RS485
Mounting Style
Panel Mount
Supply Voltage Range
320-480VAC L-L
Soft Start
0-6000s
Termination Style
Screw
Unit Weight
20kg
Factory Pack Qty
1
Datasheet
User Manual
Â
LEM ART-B22-D125-SP3 + AI-P1A - 3 Pcs, 3 Phase Rogowski Coil Set, Class 1, 1 Amp AC, Sensitivity, and Measurement Range, 12.5cm Diameter, 3M integrator Cable
The universal Rogowski coil integrator AI-P1A complements LEM’s flexible clip-around coil ART and ARU range. The design is based on digital processing to give combined dynamic range, accuracy and versatility of use. It offers a wide range of output signals both RMS and instantaneous. AI-P1A is DIN rail mounted and can be stacked for multiphase application without spacing thanks to its low power dissipation.
Input signal
Accuracy Class 1 (IEC 61869-2) [1].
Linearity error ≤ 0.10 %. Protection degree IP2X.
35 mm DIN rail mounted.
Push-in terminals.
1 Amp instantaneous output.
6 selectable sensitivities depending on Rogowski coil: 22.5, 70, 80, 85, 100, 120 mV/kA at 50 Hz.
12 selectable ranges: 100, 200, 300, 400, 500, 600, 800, 1000, 1500, 2000, 4000, 5000 A.
Ambient operating temperature −25...+70 °C.
Advantages
Compact design for DIN rail assembly
High accuracy Class 1 (IEC 61869-2)
Setup by user via Select / Edit buttons
Clear status indication via bi-color led
Applications
MV/LV substations on LV side: Transformer Condition Monitoring
Power metering: current measurement for active power calculation
Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation
Power quality monitoring: electrical loads and distribution system equipment
Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault
Remote Terminal Units (RTU)
Phasor Measurement Units (PMU)
Standards
IEC 61010-1: 2010
UL
EMC: IEC 61326-1:2012
Options
Cross Power Plug-in: side contacts to stack up to 3 Integrator modules and use only one power supply.
Specification
LEM Part Number
ART-B22-D125-SP3 + AI-P1A - 3 Pcs
Function
3 Phase AC Current Measurement
Measuring Range
Selectable 5000,4000,2000,1500,1000,800,600,500,400,300,200,100Amp
Sensitivity
Selectable 22.5,70,80,85,100,120mV/kA @ 50 Hz
Output
1 Amp Instantaneous
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
10-32VDC
Accuracy
1% from 25 to 5000 Amp
Current Consumption
100mA (max)
Dimensions
100mm x 78mm x 15mm (Integrator), 12.5cm Diameter (Coils)
Mounting
Din Rail Mount
Integrator to Coil cable
3M Twisted and Screened
Integrator to Meter cable
User Supplied Shielded cable 1.5mm sqr, up to 6m long
Operating Temperature
-25°C - 70°C
Storage Temperature
-45°C to 80°C
Isolation (50Hz, 1 min)
1.5kV
True RMS Response Time
160-190ms
Termination Style
Push-in for 1.5mm sqr wire
Weight
1125g
Factory Pack Qty
1
Certifications
Â
UL, ROHS
Datasheet
AI-P1A Datasheet
ART Series Datasheet
Application Notes
User Notice
1) The Rogowski coil can measure any primary current as there is no saturation effect.
2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts)
3) Frequency bandwidth and phase shift modelling schematic can be provided on request.
4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5) Considering a primary conductor of at least ⌀ 15 mm, perpendicular and in contact with the Rogowski coil.
6) Considering an external conductor of at least ⌀ 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.
Â
RCS-1200-1500 Three-Phase Flexible Current Sensor System (Rogowski Coils):
The RCS-1200 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-1200 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Specification
Magnelab Part Number
RCS-1200-1500
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
1500 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 1500 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
4 Inch
Coil Circumference
12 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
Crydom D1D40K, Solid State Relay, DC 3-32VDC control, 40A, 100VDC Load, Gen 3 retrofit type
Features
Ratings from 7A to 100 Amp @ 100-500VDC
Mosfet output for reliable DC switching
Multiple modules can be wired in parallel for higher currents
UL/CSA/VDE Approved, CE Compliant to EN60950-1
Improved SEMS screw and washer
Redesigned housing with anti-rotation barriers
Direct bond copper substrate
EMC compliant to Level 3
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
D1D40K
Switching Type
DC Load
ROHS
Yes (Details)
Control Voltage
3.5-32VDC
Load Current
40 Amp DC
Surge Capability (10ms)
106 Amp DC
Special Feature
Gen 3 Terminals for retrofit
Mounting Style
Panel Mount
Load Voltage Range
0 - 100VDC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
75g
Factory Pack Qty
20
Datasheet
Product Datasheet
Notifications
Please note Changes from Gen 3 to Gen 4 (current) package design here
Equivalent
See alternative D1D40K with raised terminals for alternative or D1D80 for higher current alternative
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
4400.0015 T11-211-8, Thermal Circuit Breaker (CBE) for Electrical Appliance, 240VAC/48VDC, 8 Amp, 2kA, Threaded neck type, Reset Type, Quick Connect Terminals
Thermal Circuit Breakers are used for over-current (overload and short-circuit) protection of electrical appliances, and as a disconnector in case of equipment failure/malfunction
Description
Threaded neck type
Thermal circuit breaker
1-pole - Power tools
Reset type
Quick connect terminals 6.3 x 0.8 mm
Features :
< 3mS Trip Delay Time
1 Pole Disconnect
2kA Short Circuit Rating
Suitable for 500VDC Isolation
Applications:
Power Tools
Household Equipment
Power Supplies and Chargers
Industrial Appliances
Standards :
IEC 60934
2 x Ir: 500 Cycles
500VDC Insulation Resistance
1.5kV (50Hz) Dielectric Strength
Overload @ 6 x Ir Cos φ 0.6 IEC: min 40 trip
@ 1.5 x Ir, cos φ 0.75 Allowable UL / CSA: min. 50 trips
Specification
Schurter Part Number
4400.0015 T11-211-8
Functions
1 Pole Thermal Circuit Breaker, Reset Type
Nominal Voltage
240VAC @ 50Hz or 48VDC
Nominal Current Range
8 Amp RMS
Trip Delay Time
< 3ms
Rated Frequency
50/60 Hz
Operating Temperature
-5 to 60 Deg C
Insulation Resistance
500VDC
Dielectric Strength
1.5kV (50Hz)
Short Circuit Current
2kA
Approvals
UL, CSA
Standards
IEC 6094
Weight
10g
Enclosure Material
UL94
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Â
4400.0271 T11-211-6.5, Thermal 4400.0405, TZZ01 IP54 Dust Cover for T11 CBE Series
Thermal Circuit Breakers are used for over-current (overload and short-circuit) protection of electrical appliances, and as a disconnector in case of equipment failure/malfunction
Description
Threaded neck type
IP54 Dust Cover for T11 Series
Datasheet
Product Datasheet
Â
Eastron SDM630MCT-RC, DIN Rail Mount kWh Meter, 3 Phase, 240VAC aux, Class 0.5, 85mV/kA Rogowski Coil Connect, w/ 2 x pulse outputs and RS485 Modbus RTU Comms. COILS NOT INCLUDED
85mV/kA Rogowski Coil Connect
RS 485 communication up to 38,400 bit/s as standard
Optional Mbus Model available
True RMS values of currents and voltages
1 x Configurable Pule Output (via Display Menu or Modbus)
1 x Fixed Pulse Output (1000imp/kwh)
Â
The meter is intended for measuring, and monitoring single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Â
Features :
Accuracy class 0.5
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Part Number
SDM630MCT-RC
Functions
Three Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
85mV/kA Rogowski Coil Connect
Pulse Output
2 x Passive, (1 x Configurable 60/100/200ms)
Tariff Input
N/A
Accuracy
Class 0.5 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Â
Documents
Product Datasheet
User Manual
Modbus Protocol
Setup Video - CT Ratio Unlock
Alternatives
WM3-6 230DB
Modbus Utility
EEM Meter Setting Software Utility