Electronicon 275.196-505500/221K02, Power Factor Correction Capacitor, 3 Phase, 136 x 230mm, Feed Through Terminals, Dry Type (Gas Filled), 660VAC, 3 x 55.2uF, REQUIRES EXTERNAL DISCHARGE RESISTORS
Characteristics and utility
25kVar @ 690V @ 50 Hz
33.3kVAr @ 800V @ 50Hz
Three phase capacitor DUAL WINDING internally delta connected
External Discharge Resistors Required
Reactive power factor correction
Dry type
Feed Through Terminals Capagrip L (3 x 56 Amp Max)
Indoor mounting
Triple safety
Overpressure disconnection system
Protection by internal fuses
Self Healing
Construction and materials
Low losses metallized self-healing polypropylene film, high density, high temperature and greater dielectric resistance Volt/µ
UL 94 V0 Resin
Aluminium case with bottom fixing M12x16
Standards
IEC 60831-1/2
EN 60831-1/2
Specification
Vishay Part Number
275.196-505500/221K02
Technology
Gas Filled, Low Loss, Self Healing
Dimensions
136 x 230mm
Standards
IEC 60831-1/2, EN 60831-1/2
Voltage
800V @ 50Hz
Kvar
25 Kvar
Capacitance
3 x 55.2uF (12.5KVAR @ 415VAC 50Hz) (25KVAR @ 690VAC 50Hz) (33,3KVAR @ 800V 50Hz)
Tolerance On Capacitance
-5% + 10% (others on request)
Current (Imax)
3 x 36 Amp
Overpressure Disconnection System
YES
Self Extinguishing Resin
YES
Internal Fuses
YES
Self Healing
YES
Mounting
M12 x 16mm (Indoor)
Operating Temperature Range
50°C Max, 30°C Mean(1 year), 40°C Mean(24 hrs)
Lifetime
120,000 Hours
Termination Style
Capacgrip L (Feed Through 3 x 56 Amp)
Unit Weight
2.9kg
Factory Pack Quantity
25
Â
Datasheet
Product Datasheet
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Electronicon 275.545-602900/221K02, 7.5kvar 525V 50Hz, Power Factor Correction Capacitor, 3 Phase, 75 x 164(+25 +5/-2)mm Gas Filled, 3 x 29uF, Internal Discharge Resistors
Characteristics and utility
7.5kVar @ 525V @ 50 Hz 10.0kvar 10kvar
Three phase capacitor DUAL WINDING internally delta connected
Discharge resistors Incorporated
Reactive power factor correction
Gas Filled Lightweight Construction
Connector type - single sided terminal
Indoor mounting
Triple safety
Overpressure disconnection system
Protection by internal fuses
Self Healing
Construction and materials
Low losses metallized self-healing polypropylene film, high density, high temperature and greater dielectric resistance Volt/µ
Aluminium case with bottom fixing M12x16
Standards
IEC 60831-1/2
EN 60831-1/2
Specification
Electronicon Part Number
275.545-602900/221K02
Technology
Gas Filled, Low Loss, Self Healing
Dimensions
75 x 164(+25)mm
Standards
IEC 60831-1/2, EN 60831-1/2
Voltage
525V @ 50Hz
Kvar
7.5 Kvar
Capacitance
3 x 29uF
Tolerance On Capacitance
-5% + 10% (others on request)
Current (In)
3 x 12 Amp
Overpressure Disconnection System
YES
Self Extinguishing Resin
YES
Internal Fuses
YES
Self Healing
YES
Mounting
M12 x 16mm (Indoor)
Operating Temperature Range
50°C Max, 30°C Mean(1 year), 40°C Mean(24 hrs)
Lifetime
120,000 Hours
Termination Style
Filter Type Terminal
Approvals
UL 810, CSA C22.2 No.90
Unit Weight
1.6kg
Factory Pack Quantity
30
Â
Datasheet
Product Datasheet
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Electronicon 275.545-701900/221K02, 5kvar 525V 50Hz, Power Factor Correction Capacitor, 3 Phase, 75 x 164(+25 +5/-2)mm Gas Filled, 3 x 19uF, Internal Discharge Resistors
Characteristics and utility
5kVar @ 525V @ 50 Hz 10.0kvar 10kvar
Three phase capacitor DUAL WINDING internally delta connected
Discharge resistors Incorporated
Reactive power factor correction
Gas Filled Lightweight Construction
Connector type - single sided terminal
Indoor mounting
Triple safety
Overpressure disconnection system
Protection by internal fuses
Self Healing
Construction and materials
Low losses metallized self-healing polypropylene film, high density, high temperature and greater dielectric resistance Volt/µ
Aluminium case with bottom fixing M12x16
Standards
IEC 60831-1/2
EN 60831-1/2
Specification
Electronicon Part Number
275.545-701900/221K02
Technology
Gas Filled, Low Loss, Self Healing
Dimensions
75 x 164(+25)mm
Standards
IEC 60831-1/2, EN 60831-1/2
Voltage
525V @ 50Hz
Kvar
5 Kvar
Capacitance
3 x 19uF
Tolerance On Capacitance
-5% + 10% (others on request)
Current (In)
3 x 9 Amp
Overpressure Disconnection System
YES
Self Extinguishing Resin
YES
Internal Fuses
YES
Self Healing
YES
Mounting
M12 x 16mm (Indoor)
Operating Temperature Range
50°C Max, 30°C Mean(1 year), 40°C Mean(24 hrs)
Lifetime
120,000 Hours
Termination Style
Filter Type Terminal
Approvals
UL 810, CSA C22.2 No.90
Unit Weight
1.6kg
Factory Pack Quantity
30
Â
Datasheet
Product Datasheet
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Electronicon 275.545-503300/221K02, 7.5kvar 480V 50Hz, Power Factor Correction Capacitor, 3 Phase, 75 x 164(+25 +5/-2)mm Gas Filled, 3 x 33uF, Internal Discharge Resistors, Close Replacement to Ducati Modulo XD 416464080
Characteristics and utility
7.5kVar @ 480V @ 50 Hz 10.0kvar 10kvar
Three phase capacitor DUAL WINDING internally delta connected
Discharge resistors Incorporated
Reactive power factor correction
Gas Filled Lightweight Construction
Connector type - single sided terminal
Indoor mounting
Triple safety
Overpressure disconnection system
Protection by internal fuses
Self Healing
Construction and materials
Low losses metallized self-healing polypropylene film, high density, high temperature and greater dielectric resistance Volt/µ
Aluminium case with bottom fixing M12x16
Standards
IEC 60831-1/2
EN 60831-1/2
Specification
Electronicon Part Number
275.545-503300/221K02
Technology
Gas Filled, Low Loss, Self Healing
Dimensions
75 x 164(+25)mm
Standards
IEC 60831-1/2, EN 60831-1/2
Voltage
480V @ 50Hz
Kvar
7.5 Kvar
Capacitance
3 x 33uF
Tolerance On Capacitance
-5% + 10% (others on request)
Current (In)
3 x 17 Amp
Overpressure Disconnection System
YES
Self Extinguishing Resin
YES
Internal Fuses
YES
Self Healing
YES
Mounting
M12 x 16mm (Indoor)
Operating Temperature Range
50°C Max, 30°C Mean(1 year), 40°C Mean(24 hrs)
Lifetime
120,000 Hours
Termination Style
Filter Type Terminal
Approvals
UL 810, CSA C22.2 No.90
Unit Weight
1.6kg
Factory Pack Quantity
30
Â
Datasheet
Product Datasheet
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
ACXP06R-MB (BLR-CX Plus 06R-MB), CX-Plus Power Factor Regulator, 6 Step, 1 Phase Measurement, 3 Phase Control, 110-480V 50/60HZ, Step Time Recording, Alarm Recording, RS485 Modbus
Single CT Sensing
Isolated Switching of Power Factor Correction Contactors
Cos Ï• Setting 0.85 to 0.95 CAP
Auto CT Secondary Selection
Backlit LCD Display
Various Program Combinations
IP41
Up to 6 steps
Measurement System - Automatic/Manual
90-550VAC Aux/Measurement Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
Â
Specification
Beluk Part Number
ACXP06R-MB (BLR-CX Plus 06R-MB) /Â 3ACXP06R-BEL-G-MB
Function
Reactive Power Correction
Nominal Voltage (Un)
110-480VAC Line to Line
Supply Voltage
90-300VAC (L-N), 15VA 45-65Hz
Relay Rating
250VAC/10Amp
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature/Fan Alarm
1 x Relay as above
Re-connection Delay Time
50 - 1200s User Adjustable
Desired Power Factor
0.80 IND - 0.80 CAP
Number of Output Relays
12/13 (If no fan output used)
Smallest Capacitor Current
10mA
CT Input Range
0 - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
RS485 Modbus
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP50 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
User Manual
Modbus user Manual
Comparison of CX and CX Plus Controllers
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)
ACXP06R-MB (BLR-CX Plus 12R-MB), CX-Plus Power Factor Regulator, 12/13 Step, 1 Phase Measurement, 3 Phase Control, 110-480V 50/60HZ, Modbus RTU Comms, Step Time Recording, Alarm Recording, RS485 Modbus
Single CT Sensing
Isolated Switching of Power Factor Correction Contactors
Cos Ï• Setting 0.85 to 0.95 CAP
Auto CT Secondary Selection
Backlit LCD Display
Various Program Combinations
IP41
Up to 13 steps
Measurement System - Automatic/Manual
90-550VAC Aux/Measurement Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
Â
Specification
Beluk Part Number
ACXP12R-MB (BLR-CX Plus 12R-MB) / Â 3ACXP12R-BEL-G-MB
Function
Reactive Power Correction
Nominal Voltage (Un)
110-480VAC Line to Line
Supply Voltage
90-300VAC (L-N), 15VA 45-65Hz
Relay Rating
250VAC/10Amp
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature/Fan Alarm
1 x Relay as above (Can be used as 13th Step)
Re-connection Delay Time
50 - 1200s User Adjustable
Desired Power Factor
0.80 IND - 0.80 CAP
Number of Output Relays
6
Smallest Capacitor Current
10mA
CT Input Range
5mA - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
RS485 Modbus
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP50 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
User Manual
Modbus user Manual
Comparison of CX and CX Plus Controllers
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)
ACXP06R (BLR-CX Plus 06R), CX-Plus Power Factor Regulator, 6 Step, 1 Phase Measurement, 3 Phase Control, 110-480V 50/60HZ, Step Time Recording, Alarm Recording
Single CT Sensing
Isolated Switching of Power Factor Correction Contactors
Cos Ï• Setting 0.85 to 0.95 CAP
Auto CT Secondary Selection
Backlit LCD Display
Various Program Combinations
IP41
Up to 6 steps
Measurement System - Automatic/Manual
90-550VAC Aux/Measurement Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
Â
Specification
Beluk Part Number
ACXP06R (BLR-CX Plus 06R) / 3ACXP06R-BEL-G
Function
Reactive Power Correction
Nominal Voltage (Un)
110-480VAC Line to Line
Supply Voltage
90-300VAC (L-N), 15VA 45-65Hz
Relay Rating
250VAC/10Amp
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature/Fan Alarm
1 x Relay as above
Re-connection Delay Time
50 - 1200s User Adjustable
Desired Power Factor
0.80 IND - 0.80 CAP
Number of Output Relays
6
Smallest Capacitor Current
10mA
CT Input Range
0 - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
Optional
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP50 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
User Manual
Modbus user Manual
Comparison of CX and CX Plus Controllers
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)
ACXP12R (BLR-CX Plus 12R), CX-Plus Power Factor Regulator, 12/13 Step, 1 Phase Measurement, 3 Phase Control, 110-480V 50/60HZ, Step Time Recording, Alarm Recording
Single CT Sensing
Isolated Switching of Power Factor Correction Contactors
Cos Ï• Setting 0.85 to 0.95 CAP
Auto CT Secondary Selection
Backlit LCD Display
Various Program Combinations
IP41
Up to 13 steps
Measurement System - Automatic/Manual
90-550VAC Aux/Measurement Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
Â
Specification
Beluk Part Number
ACXP12R (BLR-CX Plus 12R) / 3ACXP12R-BEL-G
Function
Reactive Power Correction
Nominal Voltage (Un)
110-480VAC Line to Line
Supply Voltage
90-300VAC (L-N), 15VA 45-65Hz
Relay Rating
250VAC/10Amp
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature/Fan Alarm
1 x Relay as above (Can be used as 13th Step)
Re-connection Delay Time
50 - 1200s User Adjustable
Desired Power Factor
0.80 IND - 0.80 CAP
Number of Output Relays
12/13 (if no fan output used)
Smallest Capacitor Current
10mA
CT Input Range
5mA - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
Optional
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP50 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
User Manual
Modbus user Manual
Comparison of CX and CX Plus Controllers
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)
ACXP12T (BLR-CX Plus 12T), CX-Plus Power Factor Regulator, 12 Step Solid State Outputs, 1 Phase Measurement, 3 Phase Control, 110-480V 50/60HZ, Step Time Recording, Alarm Recording
Single CT Sensing
Isolated Switching of Power Factor Correction Contactors
Cos Ï• Setting 0.85 to 0.95 CAP
Auto CT Secondary Selection
Backlit LCD Display
Various Program Combinations
IP41
Up to 12 steps
Measurement System - Automatic/Manual
90-550VAC Aux/Measurement Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
Â
Specification
Beluk Part Number
ACXP12T (BLR-CX Plus 12T) / 3ACXP12T-BEL-G
Function
Reactive Power Correction
Nominal Voltage (Un)
110-480VAC Line to Line
Supply Voltage
90-300VAC (L-N), 15VA 45-65Hz
Relay Rating
SOLID STATE TRANSISTOR OUTPUT
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature/Fan Alarm
1 x Relay as above (Can be used as 13th Step)
Re-connection Delay Time
50 - 1200s User Adjustable
Desired Power Factor
0.80 IND - 0.80 CAP
Number of Output Transistors
12
Smallest Capacitor Current
10mA
CT Input Range
5mA - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
Optional
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP50 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
User Manual
Modbus user Manual
Comparison of CX and CX Plus Controllers
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)
ACXP12T (BLR-CX Plus 12T-MB), CX-Plus Power Factor Regulator, 12 Step Solid State Outputs, 1 Phase Measurement, 3 Phase Control, 110-480V 50/60HZ, Modbus RTU Comms, Step Time Recording, Alarm Recording
Single CT Sensing
Isolated Switching of Power Factor Correction Contactors
Cos Ï• Setting 0.85 to 0.95 CAP
Auto CT Secondary Selection
Backlit LCD Display
Various Program Combinations
IP41
Up to 12 steps
Measurement System - Automatic/Manual
90-550VAC Aux/Measurement Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
Â
Specification
Beluk Part Number
ACXP12T-MB (BLR-CX Plus 12T-MB) / 3ACXP12T-BEL-G-MB
Function
Reactive Power Correction
Nominal Voltage (Un)
110-480VAC Line to Line
Supply Voltage
90-300VAC (L-N), 15VA 45-65Hz
Relay Rating
250VAC/10Amp
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature/Fan Alarm
1 x Relay as above (Can be used as 13th Step)
Re-connection Delay Time
50 - 1200s User Adjustable
Desired Power Factor
0.80 IND - 0.80 CAP
Number of Output Transistors
12
Smallest Capacitor Current
10mA
CT Input Range
5mA - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
RS485 Modbus
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP50 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
User Manual
Modbus user Manual
Comparison of CX and CX Plus Controllers
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)