Iskra Doo MT440-SSUDAAMAA, Multifunction Power Transducer, Class 0.5, 4 Wire, 600V 1/5/10Amp AC Input 50/60Hz, 24-300VDC or 40-276VAC Aux Input, 3 Programmable Analogue Outputs, 1 relay output, RS485 + USB Comms
Class 0.5 (EN 60688)
USB Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 50 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy class 0.5
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Specification
Iskra Doo Part Number
MT440-SSUSAAMAA
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
600V L-N, 1/5/10 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
1 x Relay Output
Tariff Input
N/A
Output
3 x Analogue
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Comms
USB (standard) RS485 2400-115200 b/s (RS232 Optional)
Weight
370g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Â
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Â
Datasheet
Product Datasheet
Software
MiQen Setting Software
MIPACK Programmer
Iskra Doo MT540-HSHFNAAAA, Multifunction Power Transducer, Class 0.5S, 4 Wire, 600V L-N, 5A AC Input 50/60Hz, 24-300VDC or 40-276VAC Aux Input, 2 Programmable analogue outputs, USB, Ethernet, RS485 Comms
Class 0.5S Active, Class 0.2 Reactive (EN 60688) , Class 0.2 on Comms
RS485 Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 140 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy Class 0.5s Active, Class 0.2 Reactive (EN 60688), Class 0.1 on Comms
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Optional Remote Display Support
Specification
Iskra Doo Part Number
MT540-HSHFNAAAA
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
600V L-N, 5 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
N/A
Tariff Input
N/A
Output(s)
4 x Analogue
Accuracy
Class 0.2 (I,U,F,PF,θ,THD) Class 0.5s(Active), Class 0.2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Terminations
EU Style Clamp Terminals
Isolation
3.5kV
Comms
USB (standard) RS232 2400-115200 b/s (RS485 Optional)
Weight
900g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Â
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Â
Datasheet
Product Datasheet
Software
MiQen Setting Software
Fastron Electronics Smart ONE 25kvar 400VAC, Smart Capacitor Bank for Kvar Correction, Reactive Power Reduction, IP21
For Automatic Switching of Power Factor Correction Capacitors according to changing site conditions.
Features
Automatic Power Factor Correction up to Cos φ = 0.95
Auto rotation of same capacitors for long life
Overtemperature Alarm
Optional RS485 Comms
IEC 654-1, UL Approved
5 Year Fastron Electronics Warranty
Â
PR-14D.12, Automatic Reactive Power Controller
1 CT Sensing
Automatic Power Factor Correction
Automatic C/K Ratio Setting (0.05 -> 0.95)
Cos Ï• Setting 0.85 to 0.95 CAP
Backlit LCD Display
Various Program Combinations
IP41
Measurement System - Automatic/Manual
230VAC Aux Supply
Optional Modbus RS485
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
2 x 10Kvar, 1 x 5Kvar Caps
Â
Specification
Fastron Part Number
Smart ONE 25kvar 400VAC
Function
Reactive Power Correction
Steps
1Â x 12.5kvar, 1 x 7.5kvar 1 x 5kvarÂ
Dimensions
W:475mm x D:215mm x L:610mm
Nominal Voltage (Un)
110-550VAC Line to Line
Supply Voltage
11-300VAC (L-N), 15VA 45-65Hz
Relay Rating
250VAC/5Amp
Switch Delay Time
1 - 999s User Adjustable
Alarm
1 x Relay as above
Temperature Alarm
1 x Relay as above
Re-connection Delay Time
1 - 999s User Adjustable
Desired Power Factor
0.80 IND - 0.80 CAP
Number of Output Relays
Up to 4
Smallest Capacitor Current
(0.002 - 2A) x CT ratio
CT Input Range
0 - 6 Amp, or 0-1.2Amp (three CT)
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
RS485 (Optional)
Termination Style
Screw
Weight
15kg
Certification
IEC 654-1, UL
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0, & Stainless Steel Painted RAL 1013
Enclosure protection
IP21
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...55 °C
Datasheet
Product Datasheet
Controller user Manual
Installation Guide
MSDS for Vishay PhMKPg Series Capacitors
Iskra Doo MT440-SSUDAAAAA, Multifunction Power Transducer, Class 0.5, 4 Wire, 600V 1/5/10Amp AC Input 50/60Hz, 24-300VDC or 40-276VAC Aux Input, 4 Programmable Analogue Outputs, RS485 + USB Comms
Class 0.5 (EN 60688)
USB Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 50 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy class 0.5
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Specification
Iskra Doo Part Number
MT440-SSUDAAAAA
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
600V L-N, 1/5/10 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
N/A
Tariff Input
N/A
Output
4 x Analogue
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Comms
USB (standard) RS485 2400-115200 b/s (RS232 Optional)
Weight
370g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Â
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Â
Datasheet
Product Datasheet
Software
MiQen Setting Software
MIPACK Programmer
Iskra Doo MT440-SSUSAAAAA, Multifunction Power Transducer, Class 0.5, 4 Wire, 600V 1/5/10Amp AC Input 50/60Hz, 24-300VDC or 40-276VAC Aux Input, 4 Programmable Analogue Outputs, RS232 + USB Comms
Class 0.5 (EN 60688)
USB Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 50 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy class 0.5
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Specification
Iskra Doo Part Number
MT440-SSUSAAAAA
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
600V L-N, 1/5/10 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
N/A
Tariff Input
N/A
Output
4 x Analogue
Accuracy
Class 0.5 (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Comms
USB (standard) RS232 9RS485 Optional)
Weight
370g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Â
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Â
Datasheet
Product Datasheet
Software
MiQen Setting Software
MIPACK Programmer
Fastron Electronics Smart ONE 62.5kvar 400VAC L-L, 62.5kVar Smart One Capacitor Bank for Reactive Power Correction, IP21
For Automatic Switching of Power Factor Correction Capacitors according to changing site conditions.
Features
Automatic Power Factor Correction up to Cos φ = 0.95
Auto rotation of same capacitors for long life
Overtemperature Alarm
Optional RS485 Comms
IEC 654-1, UL Approved
5 Year Fastron Electronics Warranty
Â
PR-14D.12, Automatic Reactive Power Controller
1 CT Sensing
Automatic Power Factor Correction
Automatic C/K Ratio Setting (0.05 -> 0.95)
Cos Ï• Setting 0.85 to 0.95 CAP
Backlit LCD Display
Various Program Combinations
IP41
Measurement System - Automatic/Manual
230VAC Aux Supply
Optional Modbus RS485
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
2 x 10Kvar, 1 x 5Kvar Caps
Â
Specification
Fastron Electronics Part Number
Smart ONE 62.5kvar 400VAC
Function
Reactive Power Correction
Steps
1 x 12.5kvar, 2 x 25kvar
Dimensions
W:475mm x D:215mm x L:610mm
Nominal Voltage (Un)
110-550VAC Line to Line
Supply Voltage
11-300VAC (L-N), 15VA 45-65Hz
Relay Rating
250VAC/5Amp
Switch Delay Time
1 - 999s User Adjustable
Alarm
1 x Relay as above
Temperature Alarm
1 x Relay as above
Re-connection Delay Time
1 - 999s User Adjustable
Desired Power Factor
0.80 IND - 0.80 CAP
Number of Output Relays
Up to 4
Smallest Capacitor Current
(0.002 - 2A) x CT ratio
CT Input Range
0 - 6 Amp, or 0-1.2Amp (three CT)
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
RS485 (Optional)
Termination Style
Screw
Weight
15kg
Certification
IEC 654-1, UL
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0, & Stainless Steel Painted RAL 1013
Enclosure protection
IP21
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...55 °C
Datasheet
Product Datasheet
Controller user Manual
Installation Guide
MSDS for Vishay PhMKPg Series Capacitors
Iskra Doo MT550-SSHFNAASS (DIN), Multifunction Power Transducer, Class 0.1, 4 Wire, 50-500V L-N, 5A AC Input 16-400Hz, 70-300VDC or 80-276VAC Aux Input, 2 Programmable analogue outputs, 2 Pulse Outputs, USB, Ethernet, RS485 Comms
Class 0.1 Active, Class 0.2 Reactive (EN 60688)
RS485 Comms as standard
Up to 4 I/O Modules (analogue output, Multiple break point, non-linear characterstics
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 600 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
Certified ship version available
The Power Transducer is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values of more than 140 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy Class 0.5s Active, Class 0.2 Reactive (EN 60688), Class 0.1 on Comms
32 Adjustable Alarms
Input frequency 50/60 Hz or 400 Hz
RS 232/RS485 communication up to 115,200 bit/s (Optional) or USB communication as standard
MODBUS RTU communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal Supply 24-300VDC or 40-276VAC
Automatic range of nominal current up to 12.5 A and nominal voltage up to 600 V
User-friendly PC MiQen software
Optional Remote Display Support
Specification
Iskra Doo Part Number
MT550-SSHFNAASS (DIN)
Functions
3 Phase Power Transducer
Supply Voltage
24-300VDC or 40-276VAC
Nominal Measurement Range
500V L-N, 5 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
N/A
Tariff Input
N/A
Output(s)
2 x Analogue
Accuracy
Class 0.2 (I,U,F,PF,θ,THD) Class 0.1(Active), Class 0.2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Terminations
EU Style Clamp Terminals
Isolation
3.5kV
Comms
USB (standard) RS232 2400-115200 b/s (RS485 Optional)
Weight
900g
Enclosure Material
UL94,
Factory Pack Qty
1
EU Directives
EN61010, EN60688,EN61326-1,60529,60068-2-1/-2/-6/-27/-30
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP20
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
MiQen Setting Software
Fastron Electronics Smart ONE 75kvar 400VAC L-L, 75kVar Smart Capacitor Bank for Reactive Power Correction, IP21
For Automatic Switching of Power Factor Correction Capacitors according to changing site conditions.
Features
Automatic Power Factor Correction up to Cos φ = 0.95
Auto rotation of same capacitors for long life
Overtemperature Alarm
Optional RS485 Comms
IEC 654-1, UL Approved
5 Year Fastron Electronics Warranty
Â
PR-14D.12, Automatic Reactive Power Controller
1 CT Sensing
Automatic Power Factor Correction
Automatic C/K Ratio Setting (0.05 -> 0.95)
Cos Ï• Setting 0.85 to 0.95 CAP
Backlit LCD Display
Various Program Combinations
IP41
Measurement System - Automatic/Manual
230VAC Aux Supply
Optional Modbus RS485
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
2 x 10Kvar, 1 x 5Kvar Caps
Â
Specification
Fastron Electronics Part Number
Smart ONE 75kvar 400VAC
Function
Reactive Power Correction
Steps
2 x 12.5kvar, 2 x 25kvar
Dimensions
W:475mm x D:215mm x L:610mm
Nominal Voltage (Un)
110-440VAC Line to Line
Supply Voltage
11-300VAC (L-N), 15VA 45-65Hz
Relay Rating
250VAC/5Amp
Switch Delay Time
1 - 999s User Adjustable
Alarm
1 x Relay as above
Temperature Alarm
1 x Relay as above
Re-connection Delay Time
1 - 999s User Adjustable
Desired Power Factor
0.80 IND - 0.80 CAP
Number of Output Relays
Up to 4
Smallest Capacitor Current
(0.002 - 2A) x CT ratio
CT Input Range
0 - 6 Amp, or 0-1.2Amp (three CT)
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
RS485 (Optional)
Termination Style
Screw
Weight
15kg
Certification
IEC 654-1, UL
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0, & Stainless Steel Painted RAL 1013
Enclosure protection
IP21
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...55 °C
Datasheet
Product Datasheet
Controller user Manual
Installation Guide
MSDS for Vishay PhMKPg Series Capacitors
Fastron Electronics Smart ONE 100kvar 400VAC L-L, 100kVar Smart Capacitor Bank for Plug and Play Reactive Power Correction, IP21
For Automatic Switching of Power Factor Correction Capacitors according to changing site conditions.
Features
Automatic Power Factor Correction up to Cos φ = 0.95
Auto rotation of same capacitors for long life
Overtemperature Alarm
Optional RS485 Comms
IEC 654-1, UL Approved
3 Year Fastron Electronics Warranty
Â
PR-14D.12, Automatic Reactive Power Controller
1 CT Sensing
Automatic Power Factor Correction
Automatic C/K Ratio Setting (0.05 -> 0.95)
Cos Ï• Setting 0.85 to 0.95 CAP
Backlit LCD Display
Various Program Combinations
IP41
Measurement System - Automatic/Manual
230VAC Aux Supply
Optional Modbus RS485
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
2 x 10Kvar, 1 x 5Kvar Caps
Â
Specification
Fastron Electronics Part Number
Smart ONE 100kvar 400VAC
Function
Reactive Power Correction
Steps
4Â x 25kvar
Dimensions
W:475mm x D:215mm x L:610mm
Nominal Voltage (Un)
110-440VAC Line to Line
Supply Voltage
11-300VAC (L-N), 15VA 45-65Hz
Relay Rating
250VAC/5Amp
Switch Delay Time
1 - 999s User Adjustable
Alarm
1 x Relay as above
Temperature Alarm
1 x Relay as above
Re-connection Delay Time
1 - 999s User Adjustable
Desired Power Factor
0.80 IND - 0.80 CAP
Number of Output Relays
Up to 4
Steps
4Â x 25kvar
Smallest Capacitor Current
(0.002 - 2A) x CT ratio
CT Input Range
0 - 6 Amp, or 0-1.2Amp (three CT)
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
RS485 (Optional)
Termination Style
Screw
Weight
15kg
Certification
IEC 654-1, UL
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0, & Stainless Steel Painted RAL 1013
Enclosure protection
IP21
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...55 °C
Datasheet
Product Datasheet
Controller user Manual
Installation Guide
MSDS for Vishay PhMKPg Series Capacitors
Fastron Electronics Smart Copy of Smart ONE 100kvar 400VAC IP51 L-L, 100kVar Smart Capacitor Bank for Reactive Power Correction, IP52 Rated
For Automatic Switching of Power Factor Correction Capacitors according to changing site conditions.
Features
Automatic Power Factor Correction up to Cos φ = 0.95
Auto rotation of same capacitors for long life
Overtemperature Alarm
Optional RS485 Comms
IEC 654-1, UL Approved
3 Year Fastron Electronics Warranty
Â
PR-14D.12, Automatic Reactive Power Controller
1 CT Sensing
Automatic Power Factor Correction
Automatic C/K Ratio Setting (0.05 -> 0.95)
Cos Ï• Setting 0.85 to 0.95 CAP
Backlit LCD Display
Various Program Combinations
IP41
Measurement System - Automatic/Manual
230VAC Aux Supply
Optional Modbus RS485
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
2 x 10Kvar, 1 x 5Kvar Caps
Â
Specification
Fastron Electronics Part Number
Smart ONE 100kvar 400VAC-IP52
Function
Reactive Power Correction
Steps
4Â x 25kvar
Dimensions
W:475mm x D:215mm x L:610mm
Nominal Voltage (Un)
110-440VAC Line to Line
Supply Voltage
11-300VAC (L-N), 15VA 45-65Hz
Relay Rating
250VAC/5Amp
Switch Delay Time
1 - 999s User Adjustable
Alarm
1 x Relay as above
Temperature Alarm
1 x Relay as above
Re-connection Delay Time
1 - 999s User Adjustable
Desired Power Factor
0.80 IND - 0.80 CAP
Number of Output Relays
Up to 4
Steps
3 x 25kvar, 1 x 12.5kvar
Smallest Capacitor Current
(0.002 - 2A) x CT ratio
CT Input Range
0 - 6 Amp, or 0-1.2Amp (three CT)
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
RS485 (Optional)
Termination Style
Screw
Weight
15kg
Certification
IEC 654-1, UL
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0, & Stainless Steel Painted RAL 1013
Enclosure protection
IP52
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...55 °C
Datasheet
Product Datasheet
Controller user Manual
Installation Guide
MSDS for Vishay PhMKPg Series Capacitors
Fastron Electronics Smart ONE 40kvar 400VAC L-L, 45kVar Smart Capacitor Bank for Reactive Power Correction, IP21
For Automatic Switching of Power Factor Correction Capacitors according to changing site conditions.
Features
Automatic Power Factor Correction up to Cos φ = 0.95
Auto rotation of same capacitors for long life
Overtemperature Alarm
Optional RS485 Comms
IEC 654-1, UL Approved
5 Year Fastron Electronics Warranty
Â
PR-14D.12, Automatic Reactive Power Controller
1 CT Sensing
Automatic Power Factor Correction
Automatic C/K Ratio Setting (0.05 -> 0.95)
Cos Ï• Setting 0.85 to 0.95 CAP
Backlit LCD Display
Various Program Combinations
IP41
Measurement System - Automatic/Manual
230VAC Aux Supply
Optional Modbus RS485
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
2 x 10Kvar, 1 x 5Kvar Caps
Â
Specification
Fastron Part Number
Smart ONE 40kvar 400VAC
Function
Reactive Power Correction
Steps
1 x 16.67kvar, 2 x 12.5kvar
Dimensions
W:475mm x D:215mm x L:610mm
Nominal Voltage (Un)
110-440VAC Line to Line
Supply Voltage
11-300VAC (L-N), 15VA 45-65Hz
Relay Rating
250VAC/5Amp
Switch Delay Time
1 - 999s User Adjustable
Alarm
1 x Relay as above
Temperature Alarm
1 x Relay as above
Re-connection Delay Time
1 - 999s User Adjustable
Desired Power Factor
0.80 IND - 0.80 CAP
Number of Output Relays
Up to 4
Smallest Capacitor Current
(0.002 - 2A) x CT ratio
CT Input Range
0 - 6 Amp, or 0-1.2Amp (three CT)
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
RS485 (Optional)
Termination Style
Screw
Weight
15kg
Certification
IEC 654-1, UL
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0, & Stainless Steel Painted RAL 1013
Enclosure protection
IP21
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...55 °C
Datasheet
Product Datasheet
Controller user Manual
Installation Guide
MSDS for Vishay PhMKPg Series Capacitors