TCD-S-1-K HEATING Temp Controller, 48x48mm, 230VAC, C/O Relay output, Type K Input. Encoder Control,amp; Digital Display, 0-999 Deg C
Pushbutton Encoder Setpoint
3-digit display (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated ON/OFF Relay, output, Optional cooling or time proprtional versions output available
Each unit needs just 75 mm depth panel space
Specification
Fastron Part Number
TCD-S-1-K
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Input
Type K Thermocouple
Control Mode
Heating ON/OFF Control
Control Range
0- 999 Deg C
Mounting Style
48x48mm Panel Mount
Supply Voltage
230VAC
Termination Style
Screw
Sampling Time
50ms
Weight
270g
Factory Pack Qty
1
Datasheet
TCD/TCR/FC5 Datasheet
TCD/TCR User Manual
TCD-H-2-PT COOLING Temp Controller, 48x96mm 230VAC, C/O Relay output, PT100 RTD Input. Encoder Control, Digital Display, 0-999 Deg C
Pushbutton Encoder Setpoint
3-digit display (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated ON/OFF Relay, output, Optional cooling or time proprtional versions output available
Each unit needs just 75 mm depth panel space
Specification
Fastron Part Number
TCD-H-2-PT
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Input
Pt100 RTD
Control Mode
Cooling ON/OFF Control
Control Range
0- 999 Deg C
Mounting Style
48x96mm Panel Mount
Supply Voltage
230VAC
Termination Style
Screw
Sampling Time
50ms
Weight
270g
Factory Pack Qty
1
Datasheet
TCD/TCR/FC5 Datasheet
TCD/TCR User Manual
Fastron Electronics FGC3-D323, Star-Delta Reduced Voltage starter, 240/400/500/690V, Nominal Current = 32 Amps (AC-3), 50/60Hz Operation, 230VAC Coil Voltage, 3 Pole 3 x NO + 1NO
Contactors are designed to meet the requirements of heavy Duty applications. Contactors may be fitted with auxiliary contacts. Peak current is limited to the value within the contactor making capacity.
Features :
High contact reliability at low voltages
High electrical and mechanical endurance and high switching capacity
Four and Three-pole contactors
Optional auxiliary contacts
Ratings from 6 Amp to 1000 Amp
CE, CB Approved
Advantages :
Saves costs of expensive replacement
Long electrical life
Reduces watt losses during “ON” condition, saves energy
High safety
No risk of dangerous voltage
Less maintenance and downtime
Standard control voltages: 24 V 50/60 Hz, 240 V 50/60 Hz, 415 V 50/60 Hz
Specification
Fastron Electronics Part Number
FGC3-D323
Functions
3 Pole NO + 1NO 1NC Contactor
Nominal Voltage
230/400/500/690VAC @ 50/60Hz
Current Carrying Capacity as per UL
32 Amp Continuous @ 55 Deg C
Main Contacts
3 x NO
Auxiliary Contacts
1 x NO
Trip Delay Time
2-10ms
Electrical Life
200,000 Ops
Operating Temperature
-25 to 55 Deg C
Mechanical Operations
10.000,000 Ops
Control Voltage
240VAC
Power Dissipation
2.3W
Approvals
UL, CSA
Standards
IEC/EN 60947-4-1, AS/NZ 61009-1
Weight
900g
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
Fastron Electronics FGC2-D32-230VAC, Interlocking AC Contactor / Motor Reverser, 240VAC Control Voltage, 3 Pole 3 x NO , 3 x NC + 1NO1NC Aux, Nominal Current = 32 Amps(AC-3) @ 240/400/500/690V
Contactors are designed to meet the requirements of heavy Duty applications. Contactors may be fitted with auxiliary contacts. Peak current is limited to the value within the contactor making capacity.
Features :
High contact reliability at low voltages
High electrical and mechanical endurance and high switching capacity
Four and Three-pole contactors
Optional auxiliary contacts
Ratings from 6 Amp to 1000 Amp
CE, CB Approved
Advantages :
Saves costs of expensive replacement
Long electrical life
Reduces watt losses during “ON” condition, saves energy
High safety
No risk of dangerous voltage
Less maintenance and downtime
Standard control voltages: 24 V 50/60 Hz, 240 V 50/60 Hz, 415 V 50/60 Hz
Specification
Fastron Electronics Part Number
FGC2-D32-230VAC
Functions
3 Pole (x2) + 1NO 1NC Contactor
Nominal Voltage
230/400/500/690VAC @ 50/60Hz
Current Carrying Capacity as per UL
32 Amp Continuous @ 55 Deg C
Main Contacts
3 x NO, 3 x NC
Auxiliary Contacts
1 x NO, 1 x NC
Trip Delay Time
2-10ms
Electrical Life
200,000 Ops
Operating Temperature
-25 to 55 Deg C
Mechanical Operations
10.000,000 Ops
Control Voltage
240VAC
Power Dissipation
2.3W
Approvals
UL, CSA
Standards
IEC/EN 60947-4-1, AS/NZ 61009-1
Weight
600g
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
Gigavac GXV600P, Contactor SPST-NO, 600+ AMP, 12-900VDC, 12/24VDC EXTERNAL PWM Coil, Coil Termination to SCPT-A021GF-0.5, IP67
Features
Hermetically Sealed
UL1604 for Class I & II Div 2 and Class III for use in hazardous locations
IP67 - Temporary water immersion (30 Min)
SAE J1171 External ignition protection
ISO8846 Protection against ignition around flammable gasses
CE Approved
12/24VDC Internal or External PWM Coils
Flexible package for installation
Specification
Gigavac Part Number
GXV600P
Main Contact Type
SPST-NO
Auxiliary Contact Type
None
Coil Voltage
12/24VDC External PWM
Load Current
600+ Amp
Mechanical Life @ 0 Amp
1,000,000 Operations
Dielectric at Sea Level (leakage <1mA)
2.5kV rms
Control Input Terminals
JST Connector: 02CPT-B-2A JST Terminal: SCPT-A021GF-0.5
Special Feature
N/A
Mounting Style
Panel Mount (M5)
Load Voltage Range
12 - 900VDC
Standards
CE, UL1604, IP67, SAEJ1171, UL508
Termination Style
M8
Unit Weight
450g
Factory Pack Qty
1
Datasheet
Product Datasheet
Gigavac GXV600M, Contactor SPST-NO, 600+ AMP, 12-900VDC, 12/24VDC INTERNAL PWM Coil, Coil Termination to SCPT-A021GF-0.5, IP67
Features
Hermetically Sealed
UL1604 for Class I & II Div 2 and Class III for use in hazardous locations
IP67 - Temporary water immersion (30 Min)
SAE J1171 External ignition protection
ISO8846 Protection against ignition around flammable gasses
CE Approved
12/24VDC Internal or External PWM Coils
Flexible package for installation
Specification
Gigavac Part Number
GXV600M
Main Contact Type
SPST-NO
Auxiliary Contact Type
None
Coil Voltage
12/24VDC Internal PWM
Load Current
600+ Amp
Mechanical Life @ 0 Amp
1,000,000 Operations
Dielectric at Sea Level (leakage <1mA)
2.5kV rms
Control Input Terminals
JST Connector: 02CPT-B-2A JST Terminal: SCPT-A021GF-0.5
Special Feature
N/A
Mounting Style
Panel Mount (M5)
Load Voltage Range
12 - 900VDC
Standards
CE, UL1604, IP67, SAEJ1171, UL508
Termination Style
M8
Unit Weight
450g
Factory Pack Qty
1
Datasheet
Product Datasheet
Crydom DRC3R40E420, AC Motor Controller & Contactor, 7.6 Amp, 18-30VDC control, 48-530VAC Load, 2 Solid State NO Aux Contacts, Zero Crossing
Features
7.6 Amp AC Semiconductor Motor Controller
Load voltage range up to 600VAC
Fits standard 35mm DIN Rail
LED input status indicator
AC or DC control
Zero Voltage (resistive loads) or instantaneous (inductive loads) turn-on output
C-UL-US Listed, CCC Certified, IEC Rated, CE & RoHS Compliant, Horsepower Rated
Built-in Overvoltage Protection
Ultra-efficient thermal management design (Patented)
Spec
Crydom Part Number
DRC3R40E420
Switching Type
DC Load
Approvals
ROHS,UL,CE,IEC
Control Voltage
18-30VDC
Load Current
7.6 Amp (rms)
Surge Capability (10ms)
716 Amp (peak)
Special Feature
LED Status Indicator
Mounting Style
DIN Rail Mount
Load Voltage Range
48-440VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
197g
Factory Pack Qty
20
Datasheet
Product Datasheet
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Trent FGV2-M21, Motor Protection Switch, 3 Phase, 690VAC, 17 - 23 Amp Setting Range, Thermal and Magnetic Release
Motor Protection Circuit Breakers are a special type of circuit breaker designed for protection of a wide range of single and 3 phase AC motors against overload and Short circuit. Used in industry, small machines, agricultural machines, compressors etc.
Features :
Magnetic and Thermal releases
< 50mS Trip Delay Time
3 Pole Disconnect
Short Circuit Breaking Capacity up to 4kA
Voltage resettable version available
Customised versions available
Standards :
IEC/EN 60898,60947-3
IP20 (IP40 Installed) IEC 61008
AS/NZ 61009-1
Specification
Trent Part Number
FGV2-M21
Functions
3 Phase Motor Protection Switch
Nominal Voltage
230/400VAC @ 50/60Hz
Nominal Current Range
17 - 23 Amp RMS
Trip Delay Time
< 50ms
Rated Frequency
50/60 Hz
Operating Temperature
-25 to 60 Deg C
Rated Operations
100,000 Ops
Insulation Voltage
690V
Overload Protection
Thermal and Magnetic Release
Breaking Capacity
230V(6kA) 415V(4kA) 500V(2.5kA) 690V(2kA)
Approvals
CSA, EAC
Standards
IEC/EN 60947-2/4-1/5-1, IP20 (IP40 Installed) IEC 61008 ; AS/NZ 61009-1
Weight
230g
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
Trent FGV2-MAN20, Auxiliary Contact for FGV2 series Motor Protection Switch, 2x NO, Ith = 6 Amp
Motor Protection Circuit Breakers are a special type of circuit breaker designed for protection of a wide range of single and 3 phase AC motors against overload and Short circuit. Used in industry, small machines agricultural machines, compressors etc.
Features :
Magnetic and Thermal releases
< 50mS Trip Delay Time
3 Pole Disconnect
Short Circuit Breaking Capacity up to 4kA
Voltage resettable version available
Customised versions available
Standards :
IEC/EN 60898,60947-3
IP20 (IP40 Installed) IEC 61008
AS/NZ 61009-1
Specification
Trent Part Number
FGV2-MAN20
Functions
Auxiliary Contact
Nominal Voltage
230/400VAC @ 50/60Hz
Configuration
1 x NO 1 x NC
Trip Delay Time
< 50ms
Rated Frequency
50/60 Hz
Operating Temperature
-25 to 60 Deg C
Rated Operations
100,000 Ops
Insulation Voltage
690V
Approvals
CE
Standards
IEC/EN 60947-2/4-1/5-1, IP20 (IP40 Installed) IEC 61008 ; AS/NZ 61009-1
Weight
100g
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
Trent FGV2-MAN11, Auxiliary Contact for FGV2 series Motor Protection Switch, 1x NO, 1 x NC, Ith = 6 Amp
Motor Protection Circuit Breakers are a special type of circuit breaker designed for protection of a wide range of single and 3 phase AC motors against overload and Short circuit. Used in industry, small machines agricultural machines, compressors etc.
Features :
Magnetic and Thermal releases
< 50mS Trip Delay Time
3 Pole Disconnect
Short Circuit Breaking Capacity up to 4kA
Voltage resettable version available
Customised versions available
Standards :
IEC/EN 60898,60947-3
IP20 (IP40 Installed) IEC 61008
AS/NZ 61009-1
Specification
Trent Part Number
FGV2-MAN11
Functions
Auxiliary Contact
Nominal Voltage
230/400VAC @ 50/60Hz
Configuration
1 x NO 1 x NC
Trip Delay Time
< 50ms
Rated Frequency
50/60 Hz
Operating Temperature
-25 to 60 Deg C
Rated Operations
100,000 Ops
Insulation Voltage
690V
Approvals
CE
Standards
IEC/EN 60947-2/4-1/5-1, IP20 (IP40 Installed) IEC 61008 ; AS/NZ 61009-1
Weight
100g
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet