Fastron FRI8-01/2, Current Monitoring Relay AC 0.2 - 2A, Adjustable delay 0.5 - 10 s, 1 x CO 10 Amp, Universal 24-240VAC 24VDC Aux Supply
FRI 8 Series serves to monitor AC currents up to 16 Amp, and provides Relay alarm output with adjustable delay time 0.5 - 10s.
Features :
Suitable for Current Transformer Monitoring
Flexible adjustment by potentiometer, choise of
6 Models: 0.05 - 0.5 A; 0.1 - 1 A; 0.2 - 2 A; 0.5 - 5 A; 0.8 - 8 A; 1.6 - 16 A Adjustable delay 0.5 - 10 s to eliminate short current peaks
Possible to use current scanning from current transformer - up to 600 A Universal supply AC 24 - 240 V and DC 24 V
Supply is galvanically separated from measured current
Output contact: 1 x changeover 8 A
1-phase, 1-MODULE, DIN rail mounting
Applications :
Heating bars in sliding rails
Heating cables
Indication of current flow
Controlling of 1-phase motor consumption
Specification
Fastron Part Number
FRI 8-01/2
Voltage Range
AC 24 - 240 V, DC 24 V (AC 50 - 60 Hz)
Operating Range
-15 %; ? %
Current Range
0.1 - 2 A (AC 50 Hz)
Current Trip Adjustment
Potentiometer
Setting Accuracy
5 %
Burden
max. 1.5 VA
Repeatability
1 %
Temperature Drift
0.1%/??C
Peak Overload (10s)
1.1 x Ipn
Time delay T1
max. 500 ms
Time delay T2
adjustable 0.1-10 s
Output
??
Number of contacts
1x changeover/ SPDT (AgNi / Silver Alloy)
Current rating
10 A / AC1
Breaking capacity
2500 VA / AC1, 240 W / DC
Inrush current
10 A
Switching voltage
250 V AC1 / 24 V DC
Min. breaking capacity DC
500 mW
Indication of state
red LED
Mechanical life
1 x 107
Electrical life (AC1)
1 x 105
Other information
??
Operating temperature
-20 ... ? ??C
Storage temperature
-30 ... ? ??C
Electrical strength
4 kV (supply - output)
Operating position
any
Mounting
DIN rail EN 60715
Protection degree
IP 40 from front panel / IP 10 terminals
Overvoltage cathegory
III.
Pollution degree
2
Max. cable size (mm )2
solid wire max. 2x2.5 or 1x4 ; with sleeve max. 1x2.5 or 2x1.5
Dimensions
90 x 17,6 x 64 mm
Weight
69 g
Standards
EN 60255-6, EN 61010-1, RoHS, CE
Datasheet
Product Datasheet
Application Notes
Monitoring relay FRI serves to monitor current level in single phase AC circuits. Due to its fluent adjustment of release current, it is predestined for applications with necessity of current flow indication, and can be used as precedence relay. Output relay is off in normal state. In case the set current level is exceeded, it switches. Multivoltage supply is an advantage.
GMTA-DVO(0-75mV)-A-RN, DC Voltage Transducer with Alarm, 0-75mVDC Input, 100-240VAC/DC Aux, 1 x Relay Alarm
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals, Voltages up to 60mV, can be converted to insulated 4 to 20 mA DC output (for direct current output type) or 0-10V/0-5V (For Direct Voltage Type), or given alarm Setpoint.
Each unit needs just 50mm x 120mm depth DIN Rail cabinet space
Specification
Part Number
GMTA-DVO(0-75mV)-A-RN
Control Output
1 x SPST Alarms 3 Amp
Input
0-75mVDC
Alarm Type
1 x SPST NO Relay 3 Amp
Over Range
x 1.2
Operating Temperature
0 - 60°C
Load Voltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
GMTA-DV1-A-RN, DC Voltage Transducer with Alarm, 0-50mVDC Input, 100-240VAC/DC Aux, 1 x Relay Alarm
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals, Voltages up to 60mV, can be converted to insulated 4 to 20 mA DC output (for direct current output type) or 0-10V/0-5V (For Direct Voltage Type), or given alarm Setpoint.
Each unit needs just 50mm x 120mm depth DIN Rail cabinet space
Specification
Part Number
GMTA-DV1-A-RN
Control Output
1 x SPST Alarms 3 Amp
Input
0-50mVVDC
Alarm Type
1 x SPST NO Relay 3 Amp
Over Range
x 1.2
Operating Temperature
0 - 60°C
Load Voltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Crouzet Automation 84872120, Single Phase Multi-Function Voltage Control Relay Under/Overvoltage Detection and Latching (Memory) Function- 35 mm HUL, 0.2-60 VAC/DC Measurement, 24/240 VAC/DC Supply
For under and overvoltage monitoring of Single phase AC or DC Voltages up to 600V
Â
Features:
Control of AC and DC voltages
Automatic recognition of AC/DC
Measurement ranges from 0.2 V to 60 V
Choice between under and overvoltage
True RMS measurement
Selectable latching (memory) function
Specification
Crouzet Part Number
84872120 (Single Phase C-Lynx Voltage Monitoring Relay With DPDT Contacts)
Function
Undervoltage/Overvoltage
Nominal Voltage
1 x 0.2 - 60 VAC/DC
Digital Outputs
2 x C/O Relays, 250VAC/DC @ 8 Amp
Min Breaking Current
10mA/5VDC
Delay on Threshhold Crossing
0.1 → 3s (0, +10%)
Delay on Pickup
600ms
Alarm Delay on Time (max)
200ms
Reset Time
1500ms
Adjustable Hysteresis
5 - 50% of Threshhold
Maximum Measurement Cycle Time
30ms/True RMS Measurement
Measurement Accuracy
1%
Supply Voltage Range
Same as Measurement
Termination Style
Screw
Weight
170g
Certification
CE, UL, CSA, GL, ROHS
Factory Pack Qty
1
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Â
Datasheet
Product Datasheet
Fastron FRI8-02/16, Under Current Monitoring Relay AC 0.16 - 16 A, Adjustable delay 0.5 - 10 s, 1 x CO 10 Amp, Universal 24-240VAC 24VDC Aux Supply
FRI 8 Series serves to monitor AC currents up to 16 Amp, and provides Relay alarm output with adjustable delay time 0.5 - 10s.
Features :
Suitable for Current Transformer Monitoring
Flexible adjustment by potentiometer, choice of
6 Models: 0.05 - 0.5 A; 0.1 - 1 A; 0.2 - 2 A; 0.5 - 5 A; 0.8 - 8 A; 1.6 - 16 A Adjustable delay 0.5 - 10 s to eliminate short current peaks
Possible to use current scanning from current transformer - up to 600 A Universal supply AC 24 - 240 V and DC 24 V
Supply is galvanically separated from measured current
Output contact: 1 x changeover 8 A
1-phase, 1-MODULE, DIN rail mounting
Applications :
Heating bars in sliding rails
Heating cables
Indication of current flow
Controlling of 1-phase motor consumption
Specification
Fastron Part Number
FRI8-02/16
Voltage Range
AC 24 - 240 V, DC 24 V (AC 50 - 60 Hz)
Operating Range
Current Range
0.16 - 16 A (AC 50 Hz)
Current Trip Adjustment
Potentiometer
Setting Accuracy
5 %
Burden
max. 1.5 VA
Repeatability
1 %
Temperature Drift
0.1%/??C
Peak Overload (10s)
1.1 x Ipn
Time delay T1
max. 500 ms
Time delay T2
adjustable 0.1-10 s
Output
??
Number of contacts
1x changeover/ SPDT (AgNi / Silver Alloy)
Current rating
10 A / AC1
Breaking capacity
2500 VA / AC1, 240 W / DC
Inrush current
10 A
Switching voltage
250 V AC1 / 24 V DC
Min. breaking capacity DC
500 mW
Indication of state
red LED
Mechanical life
1 x 107
Electrical life (AC1)
1 x 105
Other information
??
Operating temperature
-20 ... ? ??C
Storage temperature
-30 ... ? ??C
Electrical strength
4 kV (supply - output)
Operating position
any
Mounting
DIN rail EN 60715
Protection degree
IP 40 from front panel / IP 10 terminals
Overvoltage cathegory
III.
Pollution degree
2
Max. cable size (mm )2
solid wire max. 2x2.5 or 1x4 ; with sleeve max. 1x2.5 or 2x1.5
Dimensions
90 x 17,6 x 64 mm
Weight
69 g
Standards
EN 60255-6, EN 61010-1, RoHS, CE
Datasheet
Product Datasheet
Application Notes
Monitoring relay FRI serves to monitor current level in single phase AC circuits. Due to its fluent adjustment of release current, it is predestined for applications with necessity of current flow indication, and can be used as precedence relay. Output relay is off in normal state. In case the set current level is exceeded, it switches. Multivoltage supply is an advantage.
Fastron FRI8-02/1, Under Current Monitoring Relay AC 0.1 - 1 A, Adjustable delay 0.5 - 10 s, 1 x CO 10 Amp, Universal 24-240VAC 24VDC Aux Supply
FRI 8 Series serves to monitor AC currents up to 16 Amp, and provides Relay alarm output with adjustable delay time 0.5 - 10s.
Features :
Suitable for Current Transformer Monitoring
Flexible adjustment by potentiometer, choice of
6 Models: 0.05 - 0.5 A; 0.1 - 1 A; 0.2 - 2 A; 0.5 - 5 A; 0.8 - 8 A; 1.6 - 16 A Adjustable delay 0.5 - 10 s to eliminate short current peaks
Possible to use current scanning from current transformer - up to 600 A Universal supply AC 24 - 240 V and DC 24 V
Supply is galvanically separated from measured current
Output contact: 1 x changeover 8 A
1-phase, 1-MODULE, DIN rail mounting
Applications :
Heating bars in sliding rails
Heating cables
Indication of current flow
Controlling of 1-phase motor consumption
Specification
Fastron Part Number
FRI8-02/1
Voltage Range
AC 24 - 240 V, DC 24 V (AC 50 - 60 Hz)
Operating Range
Current Range
0.1 - 1 A (AC 50 Hz)
Current Trip Adjustment
Potentiometer
Setting Accuracy
5 %
Burden
max. 1.5 VA
Repeatability
1 %
Temperature Drift
0.1%/??C
Peak Overload (10s)
1.1 x Ipn
Time delay T1
max. 500 ms
Time delay T2
adjustable 0.1-10 s
Output
??
Number of contacts
1x changeover/ SPDT (AgNi / Silver Alloy)
Current rating
10 A / AC1
Breaking capacity
2500 VA / AC1, 240 W / DC
Inrush current
10 A
Switching voltage
250 V AC1 / 24 V DC
Min. breaking capacity DC
500 mW
Indication of state
red LED
Mechanical life
1 x 107
Electrical life (AC1)
1 x 105
Other information
??
Operating temperature
-20 ... ? ??C
Storage temperature
-30 ... ? ??C
Electrical strength
4 kV (supply - output)
Operating position
any
Mounting
DIN rail EN 60715
Protection degree
IP 40 from front panel / IP 10 terminals
Overvoltage cathegory
III.
Pollution degree
2
Max. cable size (mm )2
solid wire max. 2x2.5 or 1x4 ; with sleeve max. 1x2.5 or 2x1.5
Dimensions
90 x 17,6 x 64 mm
Weight
69 g
Standards
EN 60255-6, EN 61010-1, RoHS, CE
Datasheet
Product Datasheet
Application Notes
Monitoring relay FRI serves to monitor current level in single phase AC circuits. Due to its fluent adjustment of release current, it is predestined for applications with necessity of current flow indication, and can be used as precedence relay. Output relay is off in normal state. In case the set current level is exceeded, it switches. Multivoltage supply is an advantage.
GMTA-DV6-D-RN, DC Voltage Transducer with Alarm, 0-300VDC Input, 22-60VAC/DC Aux, 1 x Relay Alarm
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals, Currents up to 10 Amp, and Voltages up to 600VAC or DC, can be converted to insulated 4 to 20 mA DC output (for direct current output type) or 0-10V/0-5V (For Direct Voltage Type), or given alarm Setpoint.
Each unit needs just 50mm x 120mm depth DIN Rail cabinet space
Specification
Part Number
GMTA-DV6-D-RN
Control Output
1 x SPST Alarms 3 Amp
Input
0-300VDC
Alarm Type
1 x SPST NO Relay 3 Amp
Over Range
x 1.2
Operating Temperature
0 - 60°C
Load Voltage
22-60VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
GMTA-DV7-D-RN, DC Voltage Transducer with Alarm, 0-600VDC Input, 22-60VAC/DC Aux, 1 x Relay Alarm
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals, Currents up to 10 Amp, and Voltages up to 600VAC or DC, can be converted to insulated 4 to 20 mA DC output (for direct current output type) or 0-10V/0-5V (For Direct Voltage Type), or given alarm Setpoint.
Each unit needs just 50mm x 120mm depth DIN Rail cabinet space
Specification
Part Number
GMTA-DV7-D-RN
Control Output
1 x SPST Alarms 3 Amp
Input
0-600VDC
Alarm Type
1 x SPST NO Relay 3 Amp
Over Range
x 1.2
Operating Temperature
0 - 60°C
Load Voltage
22-60VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
GMTA-AV7-D-RN, AC Voltage Transducer with Alarm, 0-600VAC Input, 22-60VAC/DC Aux, 1 x Relay Alarm
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals, Currents up to 10 Amp, and Voltages up to 600VAC or DC, can be converted to insulated 4 to 20 mA DC output (for direct current output type) or 0-10V/0-5V (For Direct Voltage Type), or given alarm Setpoint.
Each unit needs just 50mm x 120mm depth DIN Rail cabinet space
Specification
Part Number
GMTA-AV7-D-RN
Control Output
1 x SPST Alarms 3 Amp
Input
0-600VAC
Alarm Type
1 x SPST NO Relay 3 Amp
Over Range
x 1.2
Operating Temperature
0 - 60°C
Load Voltage
22-60VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
GMTA-AV6-D-RN, AC Voltage Transducer with Alarm, 0-300VAC Input, 22-60VAC/DC Aux, 1 x Relay Alarm
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals, Currents up to 10 Amp, and Voltages up to 600VAC or DC, can be converted to insulated 4 to 20 mA DC output (for direct current output type) or 0-10V/0-5V (For Direct Voltage Type), or given alarm Setpoint.
Each unit needs just 50mm x 120mm depth DIN Rail cabinet space
Specification
Part Number
GMTA-AV6-D-RN
Control Output
1 x SPST Alarms 3 Amp
Input
0-300VAC
Alarm Type
1 x SPST NO Relay 3 Amp
Over Range
x 1.2
Operating Temperature
0 - 60°C
Load Voltage
22-60VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
GMTA-DV6-A-RN, DC Voltage Transducer with Alarm, 0-300VDC Input, 100-240VAC/DC Aux, 1 x Relay Alarm
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals, Currents up to 10 Amp, and Voltages up to 600VAC or DC, can be converted to insulated 4 to 20 mA DC output (for direct current output type) or 0-10V/0-5V (For Direct Voltage Type), or given alarm Setpoint.
Each unit needs just 50mm x 120mm depth DIN Rail cabinet space
Specification
Part Number
GMTA-DV6-A-RN
Control Output
1 x SPST Alarms 3 Amp
Input
0-300VDC
Alarm Type
1 x SPST NO Relay 3 Amp
Over Range
x 1.2
Operating Temperature
0 - 60°C
Load Voltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
GMTA-DV7-A-RN, DC Voltage Transducer with Alarm, 0-600VDC Input, 100-240VAC/DC Aux, 1 x Relay Alarm
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals, Currents up to 10 Amp, and Voltages up to 600VAC or DC, can be converted to insulated 4 to 20 mA DC output (for direct current output type) or 0-10V/0-5V (For Direct Voltage Type), or given alarm Setpoint.
Each unit needs just 50mm x 120mm depth DIN Rail cabinet space
Specification
Part Number
GMTA-DV7-A-RN
Control Output
1 x SPST Alarms 3 Amp
Input
0-600VDC
Alarm Type
1 x SPST NO Relay 3 Amp
Over Range
x 1.2
Operating Temperature
0 - 60°C
Load Voltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet