Fastron FRT 8-S2/W240 24-240 V AC/DC Two Pole Multifunction Time Relay with 2 x SPDT C/O Contacts, Can Replace Crouzet 88826155, 88827155
Features :
Multi-range (0.1s - 100days)
Multi-voltage 12 →240 V AC/DC
LED status indicator
Possibility of external load connection in parallel to the control input
Specification
Iskra Part Number
FRT 8-S2/W240
Function
Asymmetric T1-T2 Timer
Nominal Voltage
12 → 240 V AC/DC
Digital Output
2 x C/O (SPDT) (Changeover -Single Pole), 250VAC/DC @ 16 Amp
Min Breaking Current
10mA/12VDC
Timing Ranges
Selectable 1s - 100 Days
Minimum Pulse Duration
30ms/100ms with load
Repeatability
0.5%
Reset Time
120ms
Isolation
4kV
Repetition Accuracy
0.5%
Threshold Adjustment Range
10 → 100 % of the range
Termination Style
Screw
Weight
80g
Factory Pack Qty
1
Certification
CE, RoHS
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
Fastron Monitoring/Time Relays Catalogue
For items in our catalogue which are not listed online please Contact Us for Possible Replacement
F921 DC Series Current Transducer 100mA to 400 Amp Range with Adjustable High and Low C/O Relay Alarm
Features
Isolated measurement of DC currents using a Hall effect transducer with external aperture.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned DC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty. Otherwise 4-6 weeks
Specification
Oztherm Part Number
F921-X-XX-DC-XX-XX
Functions
Single Phase AC Current Transducer
Supply Voltage
9-36VDC
Nominal Measurement Range
0-400 Amp (Sensor dependant)
Maximum Measurement Range
2500 Amp with External Sensor
Alarm
C/O Relay 4Amp @ 30VDC, 0.5Amp @ 150VAC
Response Time
250mS
Accuracy @ 25 Deg C
Class 1
Bandwidth
DC - 1kHz
linearity
< 0.15%
Isolation
2.5kV
Comms
N/A
Weight
250g
Enclosure Size
79 x 60 x 85mm
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
Polyamide non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP40
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Fastron PT100 RTD Class A, or Class B with Transmitter, Various Probe Lengths and Diameter w/ LARGE Terminal Head, -50 to 500 Deg C, KNE(wire entry:M20x1.5, probe entry: G1/2'')
Pt100 Class A RTD
Class A Accuracy
Powder Coated Die Cast Alloy Terminal Head
Low Long Term Drift
Rated for -50 to 500 Deg C Max
Spring Cable Connection
3 or 6mm or Custom
304 SS Sheath
Optional Transmitter
Recommended to use BSP Fitting or Flange for mounting
Specification
Fastron Part Number
FRTD Large Terminal Series FRTD-X-XXX-XXX-KNE
Sensor Type
Pt100 Class A RTD /With Transmitter Class B
No of Wires
3
Probe Length
Various
Sheath Thickness
3/6mm (or Custom)
Sheath Material
SS 304 Stainless Steel
Accuracy
Class A/Class B with Transmitter
Approvals
CE, ANSI, ROHS
Cable length
Large Terminal Head (105 x 70mm)
Terminal Head Type
Large Powder Coated Die Cast Alloy (Weather Proof), KNE(wire entry:M20x1.5, probe entry: G1/2'')
Temperature Range
-50 to 500 Deg C
Special Feature
Large Terminal Head
Mounting Style
BSP Bayonet or Flange Fitting Recommended
Weight
470-700g
Factory Pack Qty
1
Datasheet
Datasheet
F920-A-XX-XX-XX - Signal Conditioner and +/-15VDC Bipolar Power Supply with Adjustable High and Low C/O Relay Alarm. +/- 4V Bipolar Input, For External LEM Hall Effect Sensor
Features
Isolated measurement of AC or DC currents using a Hall effect transducer with external aperture.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned AC Average RMS or DC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty, Otherwise 4-6 weeks
Datasheet
Datasheet
F921 Series DC Current Transducer with Process Outputs & High and Low Sold State Alarm
Features
Isolated measurement of DC currents using a Hall effect transducer with external aperture.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned DC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty. Otherwise 4-6 weeks
Specification
Oztherm Part Number
F921-X-XX-DC-XX-XX
Functions
Single Phase AC Current Transducer
Supply Voltage
9-36VDC
Nominal Measurement Range
0-400 Amp (Sensor dependant)
Maximum Measurement Range
2500 Amp with External Sensor
Alarm
C/O Relay 2Amp @ 40VDC, 2Amp @ 60VAC
Response Time
250mS
Accuracy @ 25 Deg C
Class 1
Bandwidth
DC - 1kHz
linearity
< 0.15%
Isolation
2.5kV
Comms
N/A
Weight
250g
Enclosure Size
79 x 60 x 85mm
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
Polyamide non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP40
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
F923 Series DC Current Transducer with Process Outputs & High and Low C/O Alarm
Features
Isolated measurement of DC currents using internal Hall effect transducer.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned DC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty. Otherwise 4-6 weeks
Specification
Oztherm Part Number
F923-X-XX-DC-XX
Functions
Single Phase AC Current Transducer
Supply Voltage
9-36VDC
Nominal Measurement Range
0-8 Amp (Sensor dependant)
Maximum Measurement Range
8 Amp
Alarm
C/O Relay 4Amp @ 30VDC, 0.5Amp @ 150VAC
Response Time
250mS
Accuracy @ 25 Deg C
Class 1
Bandwidth
DC - 1kHz
linearity
< 0.15%
Isolation
2.5kV
Comms
N/A
Weight
250g
Enclosure Size
79 x 60 x 85mm
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
Polyamide non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP40
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
F923 Series DC Current Transducer with Process Outputs & High and Low Sold State Alarm
Features
Isolated measurement of DC currents using internal Hall effect transducer.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned DC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty. Otherwise 4-6 weeks
Specification
Oztherm Part Number
F923-X-XX-DC-XX
Functions
Single Phase DC Current Transducer
Supply Voltage
9-36VDC
Nominal Measurement Range
0-8 Amp (Sensor dependant)
Maximum Measurement Range
8 Amp
Alarm
C/O Relay 2Amp @ 40VDC, 2Amp @ 60VAC
Response Time
250mS
Accuracy @ 25 Deg C
Class 1
Bandwidth
DC - 1kHz
linearity
< 0.15%
Isolation
2.5kV
Comms
N/A
Weight
250g
Enclosure Size
79 x 60 x 85mm
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
Polyamide non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP40
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Advanced Energy Thyro S 3S Series Three Phase SCR Power Controller, 16-1500Amp, 400VAC, Phase(VAR), Burst(TAKT), SWITCH Operating Modes. Compatible Replacement for Eurotherm
Features
400VAC +10/-57% Line to Line Voltage, Current or Power Control
Smallest footprint on the market
Built in Fuses
3 Phase, Phase Angle & Burst Controller with SWITCH operation mode
SWITCH between Phase(VAR) or Burst(TAKT) control modes
(0)4-20mA, 0(1)-5V, 0(2)-10V or POT input Proportional Control
Removable Cover
USB Configuration/Bias Setting
Potentiometer Adjustments
Synchronisation Function for Multiple TAKT Sync
Applications
Electrical Ovens, Kilns, or Furnaces
Primary Control of Transformer Loads in Phase or Burst Fire mode
Resistive Loads up to 6:1 Hot/Cold Ratio
AC Soft Starter (VAR Mode Combined with PLC)
Power Regulation Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for extreme environments such as mining
Series Optional Features
For HRL
Current Control/Feedback
Programmable Relay Alarm Output
Load Monitoring
Analogue Output
For HRLP
As above with Power Control Feedback
Communication Options
Standard Thyro Bus Module
BasicBus Module
Specification
Advanced Energy Part Number
Thyro S 3S 400VAC or Thyro S 3S 500VAC
Approvals
CE, UL508A, EU Directive 2014/35/EU & 2004/108/EC
Control Accuracy
3% at rated voltage
Rated Operating Temperature
45°C
Temperature Derating
0.9 x Inom @ 50 Deg C, 1.1 x Inom @ 35 Deg C
SCR Configuration
Single Phase AC Switch
Control Modes
Phase(VAR), Burst(TAKT), QUick TAKT(QTM), Hybrid(VT on request)
Control Input
4(0)-20mA, 0(1)-5V, 0(2)-10V, POT
Load Current
16 to 1500 Amp @ 45 Deg C (110% @ 35 Deg C Max)
Control Range
0-100%
Options
Conformal Coating for Gas or High Humidity Environments
Mounting Style
Panel Mount
Supply Voltage Range
400VAC +10/-15% (-57% with 24VDC Aux Supply)
Soft Start
Via PLC input
Termination Style
Screw
Unit Weight
2.1 to 74kg
Factory Pack Qty
1
Technical Docs
Brochure
User Manual
2 Leg Control Application Blog
Thyro A Series Quick Installtion Guide
Setting Up Comms on Thyro A Series Controllers
Anybus Device Ethernet IP Setup Guide
Advanced Energy Thyro S 1S Series Single Phase SCR Power Controller, Phase(VAR), Burst(TAKT), Quick TAKT(QTM), SWITCH Operating Modes. Compatible Replacement for Erutotherm
Features
Optional Profinet,Profibus,Ethernet,Modbus Comms
500VAC +10/-57% Voltage, Current or Power Control
Built in Fuse
Smallest footprint on the market
Single Phase Phase Angle & Burst Controller with SWITCH operation mode
SWITCH between Phase(VAR) or Burst(TAKT) control modes
Quick TAKT Mode (QTM), VT Mode (on request)
(0)4-20mA, 0(1)-5V, 0(2)-10V or POT input Proportional Control
Removable Cover
Potentiometer Adjustment
USB Configuration/Bias Setting
Synchronisation Function (dASM Module Recommended)
Applications
Electrical Ovens, Kilns, or Furnaces
Primary Control of Transformer Loads in Phase or Burst Fire mode
AC Soft Starter (Combined with PLC)
Power Regulation Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for extreme environments such as mining
Series Optional Features
For HRL
Current Control/Feedback
Programmable Relay Alarm Output
Load Monitoring
Analogue Output
For HRLP
As above with Power Control Feedback
Communication Options
Standard Thyro Bus Module
BasicBus Module
Specification
Advanced Energy Part Number
Thyro S 1S 500VAC
Approvals
CE, UL508A, EU Directive 2014/35/EU & 2004/108/EC
Control Accuracy
3% at rated voltage
Rated Operating Temperature
45°C
Temperature Derating
0.9 x Inom @ 50 Deg C, 1.1 x Inom @ 35 Deg C
SCR Configuration
Single Phase AC Switch
Control Modes
Phase(VAR), Burst(TAKT), QUick TAKT(QTM), Hybrid(VT on request)
Control Input
4(0)-20mA, 0(1)-5V, 0(2)-10V, POT
Load Current
16 to 1500 Amp @ 45 Deg C (110% @ 35 Deg C Max)
Control Range
0-100%
Options
Conformal Coating for Gas or High Humidity Environments
Mounting Style
Panel Mount
Supply Voltage Range
500VAC +10/-15% (-57% with 24VDC Aux Supply)
Soft Start
Via PLC input
Termination Style
Screw
Unit Weight
2.1 to 30kg
Factory Pack Qty
1
Technical Docs
Brochure
User Manual
Thyro A Series Quick Installtion Guide
Setting Up Comms on Thyro A Series Controllers
Anybus Device Ethernet IP Setup Guide
Advanced Energy Thyro S 2S Series 2 Leg 3 Phase Solid State Contactor, Burst(TAKT)Firing Mode Only. Compatible Replacement for Eurotherm
Features
400VAC +10/-57% Line to Line Voltage, Current or Power Control
Smallest footprint on the market
Built in Fuses
3 Phase, 2 Leg Economical Burst Controller Firing Mode
(0)4-20mA, 0(1)-5V, 0(2)-10V or POT input Proportional Control
Removable Cover
USB Configuration/Bias Setting
Potentiometer Adjustment
Synchronisation Function
Applications
Electrical Ovens, Kilns, or Furnaces
Primary Control of Transformer Loads in Phase or Burst Fire mode
Resistive Loads up to 6:1 Hot/Cold Ratio
AC Soft Starter (Combined with PLC)
Power Regulation Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for extreme environments such as mining
Series Optional Features
For HRL
Current Control/Feedback
Programmable Relay Alarm Output
Load Monitoring
Analogue Output
For HRLP
As above with Power Control Feedback
Communication Options
Standard Thyro Bus Module
BasicBus Module
Specification
Advanced Energy Part Number
Thyro S 2S 400VAC
Approvals
CE, UL508A, EU Directive 2014/35/EU & 2004/108/EC
Control Accuracy
3% at rated voltage
Rated Operating Temperature
45°C
Temperature Derating
0.9 x Inom @ 50 Deg C, 1.1 x Inom @ 35 Deg C
SCR Configuration
Single Phase AC Switch
Control Modes
2 Leg Burst(TAKT) for low dissipation
Control Input
4(0)-20mA, 0(1)-5V, 0(2)-10V, POT
Load Current
16 to 1500 Amp @ 45 Deg C (110% @ 35 Deg C Max)
Control Range
0-100%
Options
Conformal Coating for Gas or High Humidity Environments
Mounting Style
Panel Mount
Supply Voltage Range
400VAC +10/-15% (-57% with 24VDC Aux Supply)
Soft Start
Via PLC input
Termination Style
Screw
Unit Weight
2.1 to 74kg
Factory Pack Qty
1
Technical Docs
Brochure
User Manual
2 Leg Control Application Blog
Thyro A Series Quick Installtion Guide
Setting Up Comms on Thyro A Series Controllers
Anybus Device Ethernet IP Setup Guide