Pilz 777301, E-STOP Safety Relay 24VAC/DC, 3 x NO Safety Contacts, 1 x NC Auxiliary Contact, PNOZ X2.8P C 24VAC/DC 3n/o 1n/c
Safety Relay for Monitoring E-STOP Pushbuttons, safety gates and light barriers.
Safety Features:
Positive guides relay outputs, 3 x NO Safety Contacts, 1 x NC Auxiliary Contact
Connection options for:
E-Stop Pushbutton
Safety Gate limit switch
Reset button
Light barriers
LED Indicator for;
Status channel 1/2
Supply Voltage
Plug In connection terminals (cage clamp terminal or screw terminal)
Redundant Circuit with in built monitoring
Failsafe operation in case of component failure
Correct Open/Close Operation is tested automatically in each on-off cycle
Specification
Pilz Part Number
777301, E-STOP Safety Relay PNOZ X2.8P C 24VAC/DC 3n/o 1n/c
Function
E-Stop Relay for E-stop, Gate or Lighting
Supply Voltage
24VAC/DC
Relay Outputs
3 x NO Safety Contacts, 1 x NC Auxiliary Contact
maximum Relay Current
Safety Contacts 6 Amp, Auxiliary Contact 4 Amp
Switch on Delay
340ms
Delay on Energisation
10ms
Termination Style
Screw
Weight
250g
Certification
UL
Factory Pack Qty
1
Application Certification
In accordance with EN 60947-5-1, EN 60204-1 and VDE 0113-1
Applications
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Datasheet
Product Datasheet
User Manual
F916-SP001 (P030850) (P971211) 25 Amp DC Trackside Measurement Transducer, 0-10VDC Output, 9-36VDC Supply ARTC Approved
Features
Originally designed for ARTC for lamp monitoring of Rail level crossings for improved safety and status monitoring as mandatory requirement in global Rail networks. In conjunction with direction from Motherwell, Fastron designed a 'bullet proof' Current Transducer to enable reliable status monitoring. We have since designed several AC & DC variations to this design including F920, F922, which are also widely used in rail and several other control and automation industries.
Datasheet
Product Datasheet
XLG-240-H-AB, LED Driver/Power Supply with built in PFC, 240W, 100-305VAC input, 56VDC, 4.9Amp, Constant Current/Power/Voltage , Built In POT for Dimming with 0-10V PWM. IP67, Used as LED Driver
Wide Supply Voltage: 100-305VAC
Output Voltage: 56V
Output Current: 4.9A
Power Rating: 240W
Short Circuit, Overload, Overcurrent, Overvoltage Protected
PFC Feature PF>0.93 (93% Efficiency)
UL, CE, ROHS Approved
Datasheet
Product Datasheet
VAT810, CO2 Indoor Air Quality Monitor. Desktop Mount, 5VDC Supply (1.5W). Temperature Measurement Range -20 to 50 Deg C Accuracy +/-0.5 Deg C. Humidity 0-100% +/-3%RH, CO2 300-3000ppm +/-(50ppm + 3%). With Sound and Light Alarm, Modbus RS485
Features
Desktop Mount
5VDC Supply (1.5W)
Temperature Measurement Range -20 to 50 Deg C Accuracy +/-0.5 Deg C Humidity 0-100% +/-3%RH
CO2 300-3000ppm +/-(50ppm + 3%)
With Sound and Light Alarm
Capacitive Humidity Sensor
NDIR CO2 sensor
IP40
125x85x30mm
Touch Key Operation
Specification
Datasheet
Datasheet
Advanced Energy Basic Bus & dASM Modules, 8 Channel Communication Interface for Thyro Series SCR Controllers
Note: Basicbus not required For Thyro PX Controllers, only requires Anybus and dASM (for Dynamic Mains load optimised Burst Fire Modes)
Optional Connection for up to 8 Power Controllers (32 Optional)
One Address per Module
Access to controller setpoints, actual points, and parameters
Transfer of setpoints as float number in physical units
Control Function of LED's
24VDC 200mA Supply
UL and CE Approved
Thyro S, Thyro A, Thyro AX
Note Requires Anybus Module for dASM Mode(TAKT Control Only)
Communication Options :
Ethernet (Inc Ethern/IP/Profinet/Modbus TCP
Profibus DPV1
Modbus RTU
DeviceNet
Specification
Advanced Energy Part Numbers
2.000.190.002,2.000.190.003
Functions
Access to controller setpoints, actual points, and parametersTransfer of setpoints as float number in physical unitsControl Function of LED's
Supply Voltage
24VDC
Protocols
EthernetIP, Profinet, Modbus TCP ProfibusDPV1, ModbusRTU, DeviceNet (with Suitable Anybus Module)
No. of Communication Ports
Up to 8
Weight
750g
Factory Pack Qty
1
Approvals
CE, UL
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
User Manual
User Guide
Blog for initial communication setup issue
Setting Up Comms on Thyro A Series Controllers
Thyro Touch Software and Touch Display User Guide
Anybus Device Ethernet IP Setup Guide
F921 DC Series Current Transducer 100mA to 400 Amp Range with Adjustable High and Low C/O Relay Alarm
Features
Isolated measurement of DC currents using a Hall effect transducer with external aperture.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned DC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty. Otherwise 4-6 weeks
Specification
Oztherm Part Number
F921-X-XX-DC-XX-XX
Functions
Single Phase AC Current Transducer
Supply Voltage
9-36VDC
Nominal Measurement Range
0-400 Amp (Sensor dependant)
Maximum Measurement Range
2500 Amp with External Sensor
Alarm
C/O Relay 4Amp @ 30VDC, 0.5Amp @ 150VAC
Response Time
250mS
Accuracy @ 25 Deg C
Class 1
Bandwidth
DC - 1kHz
linearity
< 0.15%
Isolation
2.5kV
Comms
N/A
Weight
250g
Enclosure Size
79 x 60 x 85mm
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
Polyamide non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP40
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
F920-A-XX-XX-XX - Signal Conditioner and +/-15VDC Bipolar Power Supply with Adjustable High and Low C/O Relay Alarm. +/- 4V Bipolar Input, For External LEM Hall Effect Sensor
Features
Isolated measurement of AC or DC currents using a Hall effect transducer with external aperture.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned AC Average RMS or DC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty, Otherwise 4-6 weeks
Datasheet
Datasheet
F923 Series AC Current Transducer with Process Outputs & High and Low C/O Alarm
Features
Isolated measurement of AC currents using internal Hall effect transducer.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned AC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty. Otherwise 4-6 weeks
Specification
Oztherm Part Number
F923-X-XX-AC-XX
Functions
Single Phase AC Current Transducer
Supply Voltage
9-36VDC
Nominal Measurement Range
0-8 Amp (Sensor dependant)
Maximum Measurement Range
8 Amp
Alarm
C/O Relay 4Amp @ 30VDC, 0.5Amp @ 150VAC
Response Time
250mS
Accuracy @ 25 Deg C
Class 1
Bandwidth
DC - 1kHz
linearity
< 0.15%
Isolation
2.5kV
Comms
N/A
Weight
250g
Enclosure Size
79 x 60 x 85mm
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
Polyamide non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP40
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
LEM LAH 25-NP, Multi Range C/L Current Sensor, Multi Range 25 Amp, 25mA Out, PCB Mount, +/-12..15V, X = 0.25% PCB Mount
Features
Bandwidth DC to 200kHz
Multi Range through pin selection
Closed loop transducer using Hall effect
Compact and versatile
PCB Mount
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
High accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Current overload capability
Low power consumption
Applications
AC variable speed drives and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications
Water Treatment Electronics
Specification
LEM Part Number
LAH 25-NP
Technology
Closed Loop Hall Effect
Aperture
No Aperture
ROHS
Yes
Supply Voltage
+/-12..15 VDC Bipolar, Isolated
Load Current (RMS + DC)
8,12,25 Amp Multirange through pin selection
Measurement Range
+/-55 Amp
Output
25 mA
Isolation
5 kV
Bandwidth
DC-200 kHz
Mounting Style
PCB Mount
Operating Temperature Range
-40°C / 85°C
Accuracy
0.3%
Termination Style
Through Hole PCB
Unit Weight
20g
Factory Pack Quantity
25
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition