BLR-Q(U)12R DM (3ACM12R-BEL-O-DM), Power Factor Regulator & Power Quality Analyser, 12 Step, 1 Phase Measurement, Power Quality Alarms, WITH BATTERY BACKUP, 3 Phase Control, 50-530V 50/60HZ
Single CT Sensing
32nd Harmonic Measurement
Isolated Switching of Power Factor Correction Contactors
Cos ϕ Setting 0.9 to 0.9 CAP
Auto CT Secondary Selection
Backlit LCD Display
Various Program Combinations
IP41
Up to 12 steps
Measurement System - Automatic/Manual
50-530VAC Measurement
100-132V / 207-253VAC (L-N) Aux Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
Specification
Beluk Part Number
BLR-Q(U)12R DM / 3ACM12R-BEL-O-DM
Function
Reactive Power Correction & Power Quality Analyser
Nominal Voltage (Un)
50-530VAC Line to Line
Supply Voltage
100-132V / 207-253VAC (L-N), 45-65Hz, max fuse 6A
Relay Rating
250VAC/5Amp
Static Output Rating (T Models)
8-48VDC / 100mA
Internal 2MB Logger
Optional
Battery Backup
YES
3 x CT Measurement
Optional
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature/Fan/THD Alarm
1 x Relay as above
Re-connection Delay Time
50 - 1200s User Adjustable
Desired Power Factor
0.90 IND - 0.90 CAP
Number of Output Relays
12
Smallest Capacitor Current
10mA
CT Input Range
15mA - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
Optional
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP50 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
User Manual
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)
BLR-Q(U)06R DM (3ACM06R-BEL-O-DM), Power Factor Regulator & Power Quality Analyser, 6 Step, 1 Phase Measurement, Power Quality Alarms, WITH BATTERY BACKUP, 3 Phase Control, 50-530V 50/60HZ
Single CT Sensing
32nd Harmonic Measurement
Isolated Switching of Power Factor Correction Contactors
Cos ϕ Setting 0.9 to 0.9 CAP
Auto CT Secondary Selection
Backlit LCD Display
Various Program Combinations
IP41
Up to 6 steps
Measurement System - Automatic/Manual
50-530VAC Measurement
100-132V / 207-253VAC (L-N) Aux Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
Specification
Beluk Part Number
BLR-Q(U)06R DM / 3ACM06R-BEL-O-DM
Function
Reactive Power Correction & Power Quality Analyser with battery backup
Nominal Voltage (Un)
50-530VAC Line to Line
Supply Voltage
100-132V / 207-253VAC (L-N), 45-65Hz, max fuse 6A
Relay Rating
250VAC/5Amp
Static Output Rating (T Models)
8-48VDC / 100mA
Internal 2MB Logger
Optional
Battery Backup
YES
3 x CT Measurement
Optional
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature/Fan/THD Alarm
1 x Relay as above
Re-connection Delay Time
50 - 1200s User Adjustable
Desired Power Factor
0.90 IND - 0.90 CAP
Number of Output Relays
6
Smallest Capacitor Current
10mA
CT Input Range
15mA - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
Optional
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP50 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
User Manual
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)
Crydom PMP2450WP, Phase/Burst control, 240VAC, 50 Amp, Selectable 0-5V,0-10V,4-20mA input, w/Overvoltage Protection
Features
Selectable Proportional Phase or Burst Control Input
Ratings from 25A to 90 Amp @ 170-600 VAC
SCR output for heavy industrial loads
Zero voltage or Instantaneous turn-on outputs
UL/CE/ROHS Compliant
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
PMP2450WP
Switching Type
Phase Angle or Burst (Selectable)
ROHS/CE/UL
Yes
Control Voltage
0 - 10V/0 - 5V/4 - 20mA Proportional Input (Selectable)
Note Requires DC Power Supply for 0-5V/0-10V input modes
Load Current
50 Amp (rms)
Surge Capability
716Amp (peak)
Special Feature
Proportional Controller + SSR
Mounting Style
Panel Mount
Load Voltage Range
170-280VAC
Dielectric Strength
4kV
Termination Style
Terminal Plug
Unit Weight
160g
Factory Pack Qty
20
Datasheet
Product Datasheet
PMP24 Installation/Wiring Guide
Notifications
Please note Changes from Gen 3 to Gen 4 (current) package design here
Equivalent
RS1A
Contact Us for Possible Replacement
Heatsink
SSR and Heatsink Assemblies
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
MTC300-16-413F3D, Dual Thyristor Module, 300 Amp, 1600V, 50mm package
Features
Thyristor for line frequency
Pressure Contact Technology
Electrically insulated base plate
Industrial standard package
Long-term stability
3600V Isolation
50mm Base Width
Applications
Power Converter
Line rectifying 50/60 Hz
Deep Cycle Applications
Controlled Rectifiers
Softstart AC motor control
AC power control
Lighting and temperature control
Specification
Techsem Part Number
MTC300-16-413F3D
Vrrm
1600V
Diode Configuration
Dual Thyristor Module
IF(av) @ 85 Deg C
300 Amp
Package Size
W:50mm L:115mm D:52mm
Itsm
7.2 kA
VF(to)
0.85V
Tj(max)
125°C
rF
0.9mΩ
I(gt) @ 25 Deg C
30-180mA
Terminals
M10 Screw
Hole Centres
38mm x 88mm(M6)
Gate Terminals
Spade (A 2.8 - 0.8 DIN 46244)
R th(j-c)
0.09°C/W
R th(c-h)
0.04°C/W
Weight
1260g
Mounting Torque
5 Nm (12 Nm Terminals)
Factory Pack Qty
8
Certification
UL Listed, ROHS
Techsem Headquarters
China
Datasheet
Product Datasheet
Alternatives
See MCC312-16io1 for Solder bonded alternative
BLR-Q(U)12R MB(3ACM12R-BEL-O-QMB), Power Factor Regulator & Power Quality Analyser, 12 Step, 1 Phase Measurement, Power Quality Alarms, 3 Phase Control, 50-530V 50/60HZ
Single CT Sensing
32nd Harmonic Measurement
Isolated Switching of Power Factor Correction Contactors
Cos ϕ Setting 0.9 to 0.9 CAP
Auto CT Secondary Selection
Backlit LCD Display
Various Program Combinations
IP41
Up to 12 steps
Measurement System - Automatic/Manual
50-530VAC Measurement
100-132V / 207-253VAC (L-N) Aux Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
RS485 Modbus RTU
Specification
Beluk Part Number
BLR-Q(U)12R MB / 3ACM12R-BEL-O-QMB
Function
Reactive Power Correction & Power Quality Analyser
Nominal Voltage (Un)
50-530VAC Line to Line
Supply Voltage
100-132V / 207-253VAC (L-N), 45-65Hz, max fuse 6A
Relay Rating
250VAC/5Amp
Static Output Rating (T Models)
8-48VDC / 100mA
Internal 2MB Logger
Optional
3 x CT Measurement
Optional
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature/Fan/THD Alarm
1 x Relay as above
Re-connection Delay Time
50 - 1200s User Adjustable
Desired Power Factor
0.90 IND - 0.90 CAP
Number of Output Relays
12
Smallest Capacitor Current
10mA
CT Input Range
15mA - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
RS485 Modbus RTU
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP50 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
User Manual
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)
BLR-Q(U)06R MB(3ACM06R-BEL-O-QMB), Power Factor Regulator & Power Quality Analyser, 6 Step, 1 Phase Measurement, Power Quality Alarms, 3 Phase Control, 50-530V 50/60HZ
Single CT Sensing
32nd Harmonic Measurement
Isolated Switching of Power Factor Correction Contactors
Cos ϕ Setting 0.9 to 0.9 CAP
Auto CT Secondary Selection
Backlit LCD Display
Various Program Combinations
IP41
Up to 6 steps
Measurement System - Automatic/Manual
50-530VAC Measurement
100-132V / 207-253VAC (L-N) Aux Supply
Configurable Alarms
Dual Password Protection
Programmable Fan Control
Programmable 1A/5A CT Ratio
RS485 Modbus RTU
Specification
Beluk Part Number
BLR-Q(U)06R MB/ 3ACM06R-BEL-O-QMB
Function
Reactive Power Correction & Power Quality Analyser
Nominal Voltage (Un)
50-530VAC Line to Line
Supply Voltage
100-132V / 207-253VAC (L-N), 45-65Hz, max fuse 6A
Relay Rating
250VAC/5Amp
Static Output Rating (T Models)
8-48VDC / 100mA
Internal 2MB Logger
Optional
3 x CT Measurement
Optional
Switch Delay Time
1s - 1200s User Adjustable
Alarm
1 x Relay as above
Temperature/Fan/THD Alarm
1 x Relay as above
Re-connection Delay Time
50 - 1200s User Adjustable
Desired Power Factor
0.90 IND - 0.90 CAP
Number of Output Relays
6
Smallest Capacitor Current
10mA
CT Input Range
15mA - 6 Amp
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
RS485 Modbus RTU Included
Termination Style
Screw
Weight
700g
Certification
IEC 654-1
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP50 for case, IP20 for terminals
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...60 °C
Datasheet
User Manual
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Quick Start Guide(Blog)
Electronicon 275.186-709600/221K02 25kvar 525V 50Hz, Power Factor Correction Capacitor, 3 Phase, 116 x 230(+32 +5/-2)mm Gas Filled, 3 x 96.2uF, DOUBLE SIDED TERNINALS Replaces 275.186-809600
Characteristics and utility
25kVar @ 525V @ 50 Hz 10.0kvar 10kvar
Three phase capacitor DUAL WINDING internally delta connected
Discharge resistors Incorporated
Reactive power factor correction
Gas Filled Lightweight Construction
Connector type - single sided terminal
Indoor mounting
Triple safety
Overpressure disconnection system
Protection by internal fuses
Self Healing
Construction and materials
Low losses metallized self-healing polypropylene film, high density, high temperature and greater dielectric resistance Volt/µ
Aluminium case with bottom fixing M12x16
Standards
IEC 60831-1/2
EN 60831-1/2
Specification
Electronicon Part Number
275.186-709600/221K02 25kvar 525V 50Hz
Technology
Gas Filled, Low Loss, Self Healing
Dimensions
116 x 230(+32)mm
Standards
IEC 60831-1/2, EN 60831-1/2
Voltage
525V @ 50Hz
Kvar
25 Kvar
Capacitance
3 x 96.2uF
Discharge Resistors (Not Included)
275.105-10120 & 275-100-10180
Tolerance On Capacitance
-5% + 10% (others on request)
Current (In)
3 x 45 Amp
Overpressure Disconnection System
YES
Self Extinguishing Resin
YES
Internal Fuses
YES
Self Healing
YES
Mounting
M12 x 16mm (Indoor)
Operating Temperature Range
50°C Max, 30°C Mean(1 year), 40°C Mean(24 hrs)
Lifetime
120,000 Hours
Termination Style
Filter Type Terminal
Approvals
UL 810, CSA C22.2 No.90
Unit Weight
2.3kg
Factory Pack Quantity
25
Datasheet
Product Datasheet
Replaces Part# 275.189-714301-221702 which is now obsolete
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Eastron Europe SDM630MCT-MODBUS-CL1 V2, DIN Rail Mount kWh Meter, 3 Phase, 240VAC aux, Class 1, 1/5 Amp CT Connect, w/ 2 x pulse outputs and RS485 Modbus RTU Comms, NON MID VERSION, WILL NOT LOCK AFTER INTIAL SETTING
NON MID Version -> Will not lock you out after first CT configuration
1/5 Amp CT Input
RS 485 communication up to 38,400 bit/s as standard
Optional Mbus Model available
True RMS values of currents and voltages
1 x Configurable Pule Output (via Display Menu or Modbus)
1 x Fixed Pulse Output (1000imp/kwh)
The meter is intended for measuring, and monitoring single-phase or 3 phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
Accuracy class 1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Pulse output as standard
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM630MCT-MODBUS-CL1 V2
Functions
Three Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
1/5 Amp
Pulse Output
2 x Passive, (1 x Configurable 60/100/200ms)
Tariff Input
N/A
Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
150g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Setup Video - CT Ratio Unlock
Alternatives
WM3-6 230DB
Modbus Utility
EEM Meter Setting Software Utility
Crydom PMP4850WP, Phase/Burst control, 240VAC, 50 Amp, Selectable 0-5V,0-10V,4-20mA Input, w/Overvoltage Protection
Features
Selectable Proportional Phase or Burst Control Input
Ratings from 25A to 90 Amp @ 170-600 VAC
SCR output for heavy industrial loads
Zero voltage or Instantaneous turn-on outputs
UL/CE/ROHS Compliant
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
PMP4850WP
Switching Type
Phase Angle or Burst (Selectable)
ROHS/CE/UL
Yes
Control Voltage
0 - 10V/0 - 5V/4 - 20mA Proportional Input (Selectable)
Note Requires DC Power Supply for 0-5V/0-10V input modes
Load Current
50 Amp (rms)
Surge Capability
716Amp (peak)
Special Feature
Proportional Controller + SSR, Overvoltage protection
Mounting Style
Panel Mount
Load Voltage Range
345-530VAC
Dielectric Strength
4kV
Termination Style
Terminal Plug
Unit Weight
160g
Factory Pack Qty
20
Datasheet
Product Datasheet
PMP24 Installation/Wiring Guide
Equivalent
Crydom PMP2425W or Contact Us for Possible Replacement
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Fastron Electronics SCT-F50-400-5A, 5 Amp, 400Amp measurement Split Core CT's
Features
Quick Release Split Core System
Cable Mount
5 Amp Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F50-400-5A
Technology
Split Core AC Current Transformer
Ratio
400/5 Amp
Aperture Size
ø 50 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
5 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
400Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
1000g
Factory Pack Qty
9
Datasheet
Product Datasheet
Stocked Split Core CT's Listing
Application Notes
Installation Guide
Types of Current Transformers - Blog
Cable Losses and CT's
High Accuracy or High Burden Requirements for CT's
Protec Protec T2 Protec T2-350-3+0-R, Uc = 350VAC Surge Protection Device (SPD) for AC Applications, 20kA (10/350uS), Varistor Voltage. For 277VAC systems, 3 Pole + 0, DIN Rail Mount, Protection Modes L-PEN, Class II, Type 2, Type 1CA, Open Type 1 SPD Listed, with Remote Contact
Specifications
Raycap part number
T2 Protec T2-350-3+0-R
Nominal Voltage Un
277VAC systems (for Uc = 350VAC )
No of Poles
3
Category IEC / EN / VDE
Type 2/Open Type 1CA SPD Listed
Location of use
Sub Distribution Boards
Protection modes
L-PEN
Additional Remote Contacts
YES
Protective element
MOV
No Fault/Fault Indication
Green Flag / Not Green Flag
Surge discharge rating
Per pole 20kA(8/20uS) 50kA Max
Internal protection and safety
Thermal disconnector in each MOV
Standards
IEC/EN 61643-11
Datasheet
Product Datasheet
GDT/MOV/TVS Tester
SPD Tester
FP150125P, 1500/5 Amp Split Core CT, Class 0.5, 7.5VA Series Clip On Current Transformer
Features
Quick Release Split Core System
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
IEC185, BS 7626, BSEN 60044-1 and IEC 60044-1
Applications
Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Electronics Part Number
FP150125P
Technology
Split Core AC Clip On Current Transformer
Ratio
1500/5
Aperture Size
85 x 120mm
VA Rating
7.5VA
Accuracy Class
Class 0.5
Output
5 Amp AC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10°C / 50°C
Continuous Current (max)
1500Amp x 1.2
Termination Style
Screw
Approvals
CE
Unit Weight
1150g
Factory Pack Qty
1
Datasheet
Product Datasheet
Installation Guide