PGFM-211-B-A1-187, GFCI Lineguard Ground Fault Protection Relay for Single or Split Phase Systems, 30mA Detection, 50 Amp Max Ipn, 240VAC Supply, Panel Mount, Auto Reset, Note: Requires Suitable Air Pax Breaker
Features :
Suitable for Air Pax Breaker LEL Series
Applications :
On Board Vessel Earth Leakage Detection (Marine)
Specification
Sensata - Klixon Part Number
PGFM-211-B-A1-187
Supply Voltage
240VAC
Dimensions
55.4mm x 93.2mm x 83.3mm
Application
Earth Leakage Detection 30mA ( 50 Amp Max Ipn)
Trip Level
+/-30mA Nominal (Fixed) (Auto Reset)
Relay
Auto Reset, Requires Air Pax LEL Series Breaker
Protection
IP20
Approvals
E-11 GFP - UL 943 Category FTTJ2 when used in tandem with Airpax LEL series
Trip Time of Assembly
100mS or Less (60mS nominal)
Sensing Coil Voltage Limit
600VAC max
Aperture
16mm??
Operating Temnperature
-35 to 66 Deg C
Weight
200g
Mounting Style
Din Rail
Datasheet
Product Datasheet
Premier 211-PT5A0-GJO+5581901, Three Phase Market Grade Revenue Meter for Small Commercial Applications, 5-20 Amp CT Connect, NMI 6
Three Phase Market/Revenue Grade Meter for small commercial applications
Usage
The meter is intended for measuring, monitoring three-phase electrical power network in residental, or small commercial applications for billing purposes. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Specification
Secure Part Number
Premier 211-PT5A0-GJO+5581901
Functions
Commercial Billing Meter with LCD Display
Nominal Measurement/Supply Range
3 x 2300/460VAC, 5-20 Amp 50Hz
Maximum Measurement Range
460VAC, 10/100 Amp 50Hz
4 Quadrant Measurement
Import/Export
Tariff Input
N/A
Accuracy
Class 1
Comms
N/A Optional Addon Module
Weight
2000g
Certification
CIEC/AS 62052-11, IEC/AS 62053-21, NMI M6-1
Factory Pack Qty
1
Safety
IP53
Enclosure Material
Engineering Plastic
Optional
RTC,Load Profile, RS485 Interface, Outputs
Operating Temperature
-40 →+80 °C
Datasheet
Datasheet
User Manual
IGC meters
MT860
MT830/831
ICG Meter Shortform
LEL12-1REC5-37583-30-G2-V, Magenetic Circuit Breaker 30mA to 50 Amp Range, 240VAC Supply, Panel Mount, Suitable for PGFM Series Earth Leakage System
Features :
Suitable for PGFM Series Earth Leakage Sensor
Applications :
On Board Vessel Earth Leakage Detection (Marine)
Hydraulic/Magnetic Circuit Protection
Specification
Sensata - Klixon Part Number
LEL12-1REC5-37583-30-G2-V
Supply Voltage
240VAC
Dimensions
38.5mm x 80mm x 65mm
Application
Earth Leakage Detection 27mA - 50 Amp
Trip Level
27mA (30mA Nominal)
Relay
Requires Air Pax LEL Series Breaker
Protection
IP20
Approvals
E-11 GFP - UL 943 Category FTTJ2 when used in tandem with FPGM Marine Earth leakage Sensor
Trip Time of Assembly
100mS or Less (60mS nominal)
Sensing Coil Voltage Limit
600VAC max
Operating Temnperature
-35 to 66 Deg C
Weight
200g
Mounting Style
Din Rail
Datasheet
Product Datasheet
FFRS3-C40-1500R-T2, 1500VDC Surge Protection Device for Photovoltaic Systems, Type 2 (Class II) 40kA WITH REMOTE C/O CONTACTS
Specifications
Trent part number
FRS3-C40-1500R
Nominal Voltage
1500VDC
No of Poles
3
Category IEC / EN / VDE
Type 2 (Class II)
Location of use
String Box, Inverter, Sub Board Only
Protection modes
(+)-PE,(-)-PE,(+)-(-) PE
Additional Remote Contacts
YES NO/NC/COM
Protective element
MOV
No Fault/Fault Indication
Green Flag / Not Green Flag
Surge discharge rating
Per pole 40kA (8/20uS)9KA) Max, 20kA (8/20uS)9KA) Nominal
Internal protection and safety
Thermal disconnector in each MOV
Weight
420g
Standards
IEC614643-31:2018 (TUV, CE Approved)
Datasheet
Product Datasheet
GDT/MOV/TVS Tester
SPD Tester
Schurter 6200.4115, IEC Appliance Inlet C14, 1.5mm Snap In Panel Mounting, Front Side, Quick Connect Terminals 3.8 x 0.8mm, with Fuse Drawer
Features
Panel Mount : Srew Mounting from Front Side
Appliance Inlet C14/M Socket acc to IEC 60320-1
70 °C pin Temperature
Quick Connect Terminals
Characteristics
UL 60320-1, CSA C22.2 no. 60320-1 (for hot conditions) pin-temperature 120 °C, 10A, Protection Class I
Other Thickness versions available on request
Types for enhanced glow wire test requirements acc. IEC 60695-2- 12 and -13 for the use in unattended household equipment acc. IEC 60335-1
Specification
Schurter Part Number
6200.4115
Rated Voltage
250V
Rated Current
10A (CE) 15A (UL/CSA)
Panel Thickness
N/A Screw Mounted
Operating Temperature
-25°C to 120°C
Filter Type
N/A
Fuse Holder
N/A
Line Switch
N/A
Mounting
Panel Mount with Screws
Material
Thermoplastic, black, UL 94V-0
Termination Style
C14 Male to Solder Terminals 3.8 x 0.8mm
Weight
25g
Factory Pack Qty
1
Protection Class
From front side IP30 acc. to IEC 60529
Isolation
2kV
VDE/UL/CSA/CE/ROHS
Yes
Datasheet
Product Datasheet
Trent NBR-20 005 13-630A-500V-120kA-NH3, Semiconductor Type gG/gL Fuse, 630 Amp, 120kA, 500VAC, 150 x 75 x 65mm
Features
Square Body Size NH3
Wide Range of I²t
Ratings up to 2000 Amp
Busbar or Fuse Holder Mounted
IEC Standard 60269.1 AND 4
500 V Voltage Rating
Applications
Protection of High Powered Semiconductors according to I²t
Short Circuit Protection
DC or AC Motor I²t Protection
Battery Fuse
Specification
Trent Part Number
NBR-20 005 13-630A-500V-120kA-NH3
Fuse Type
I²t gG/gL Class
Nominal Voltage
500VAC @ 50Hz
Nominal Current (RMS + DC)
630 Amp
Tested Breaking Capacity
120kA @ 690VAC
Dimensions
150 x 75 x 65mm
Hole Centers
N/A Blade Style
Mounting
Fuse Holder Mounting
Operating Temperature Range
-40°C / 125°C
Termination
Blade
Unit Weight
900g
Factory Pack Qty
10
Datasheet
Product Datasheet
Trent NBR-20 004 13-315A-500V-120kA-NH2, Semiconductor Type gG/gL Fuse, 315 Amp, 120kA, 500VAC, NH2, 150 x 59 x 53mm
Features
Square Body Size NH2
Wide Range of I²t
Ratings up to 2000 Amp
Busbar or Fuse Holder Mounted
IEC Standard 60269.1 AND 4
500 V Voltage Rating
Applications
Protection of High Powered Semiconductors according to I²t
Short Circuit Protection
DC or AC Motor I²t Protection
Battery Fuse
Specification
Trent Part Number
NBR-20 004 13-315A-500V-120kA-NH2
Fuse Type
I²t gG/gL Class
Nominal Voltage
500VAC @ 50Hz
Nominal Current (RMS + DC)
315 Amp
Tested Breaking Capacity
120kA @ 690VAC
Dimensions
150 x 75 x 65mm
Hole Centers
N/A Blade Style
Mounting
Fuse Holder Mounting
Operating Temperature Range
-40°C / 125°C
Termination
Blade
Unit Weight
900g
Factory Pack Qty
10
Datasheet
Product Datasheet
FRS3-C40-1500R, 1500VDC Surge Protection Device for Photovoltaic Systems, Type 1 (Class I) + Type 2 (Class II) 40kA WITH REMOTE C/O CONTACTS
Specifications
Trent part number
FRS3-C40-1500R
Nominal Voltage
1500VDC
No of Poles
3
Category IEC / EN / VDE
Type 1 (Class I) + Type 2 (Class II)
Location of use
String Box, Inverter
Protection modes
(+)-PE,(-)-PE,(+)-(-) PE
Additional Remote Contacts
YES NO/NC/COM
Protective element
MOV
No Fault/Fault Indication
Green Flag / Not Green Flag
Surge discharge rating
Per pole 40kA (8/20uS)9KA) Max, 20kA (8/20uS)9KA) Nominal
Internal protection and safety
Thermal disconnector in each MOV
Weight
420g
Standards
IEC614643-31:2018 (TUV, CE Approved)
Datasheet
Product Datasheet
GDT/MOV/TVS Tester
SPD Tester
Trent NBR-20 005 13-315A-500V-120kA-NH3, Semiconductor Type gG/gL Fuse, 315 Amp, 120kA, 500VAC, NH3, 150 x 59 x 53mm
Features
Square Body Size NH3
Wide Range of I²t
Ratings up to 2000 Amp
Busbar or Fuse Holder Mounted
IEC Standard 60269.1 AND 4
500 V Voltage Rating
Applications
Protection of High Powered Semiconductors according to I²t
Short Circuit Protection
DC or AC Motor I²t Protection
Battery Fuse
Specification
Trent Part Number
NBR-20 005 13-315A-500V-120kA-NH3
Fuse Type
I²t gG/gL Class
Nominal Voltage
500VAC @ 50Hz
Nominal Current (RMS + DC)
315 Amp
Tested Breaking Capacity
120kA @ 690VAC
Dimensions
150 x 75 x 65mm
Hole Centers
N/A Blade Style
Mounting
Fuse Holder Mounting
Operating Temperature Range
-40°C / 125°C
Termination
Blade
Unit Weight
900g
Factory Pack Qty
10
Datasheet
Product Datasheet
Trent NBR-20 004 13-400A-500V-120kA-NH2, Semiconductor Type gG/gL Fuse, 400 Amp, 120kA, 500VAC, NH2, 150 x 59 x 53mm
Features
Square Body Size NH2
Wide Range of I²t
Ratings up to 2000 Amp
Busbar or Fuse Holder Mounted
IEC Standard 60269.1 AND 4
500 V Voltage Rating
Applications
Protection of High Powered Semiconductors according to I²t
Short Circuit Protection
DC or AC Motor I²t Protection
Battery Fuse
Specification
Trent Part Number
NBR-20 004 13-400A-500V-120kA-NH2
Fuse Type
I²t gG/gL Class
Nominal Voltage
500VAC @ 50Hz
Nominal Current (RMS + DC)
400 Amp
Tested Breaking Capacity
120kA @ 690VAC
Dimensions
150 x 75 x 65mm
Hole Centers
N/A Blade Style
Mounting
Fuse Holder Mounting
Operating Temperature Range
-40°C / 125°C
Termination
Blade
Unit Weight
900g
Factory Pack Qty
10
Datasheet
Product Datasheet
Trent NBR-20 004 13-40A-500V-120kA-NH2, Semiconductor Type gG/gL Fuse, 40 Amp, 120kA, 500VAC, NH2, 150 x 46 x 29.5mm
Features
Square Body Size NH2
Wide Range of I²t
Ratings up to 2000 Amp
Busbar or Fuse Holder Mounted
IEC Standard 60269.1 AND 4
500 V Voltage Rating
Applications
Protection of High Powered Semiconductors according to I²t
Short Circuit Protection
DC or AC Motor I²t Protection
Battery Fuse
Specification
Trent Part Number
NBR-20 004 13-40A-500V-120kA-NH2
Fuse Type
I²t gG/gL Class
Nominal Voltage
500VAC @ 50Hz
Nominal Current (RMS + DC)
40 Amp
Tested Breaking Capacity
120kA @ 690VAC
Dimensions
150 x 75 x 65mm
Hole Centers
N/A Blade Style
Mounting
Fuse Holder Mounting
Operating Temperature Range
-40°C / 125°C
Termination
Blade
Unit Weight
900g
Factory Pack Qty
10
Datasheet
Product Datasheet
Trent NBR-20 004 13-160A-500V-120kA-NH2, Semiconductor Type gG/gL Fuse, 160 Amp, 120kA, 500VAC, NH2, 150 x 46 x 29.5mm
Features
Square Body Size NH2
Wide Range of I²t
Ratings up to 2000 Amp
Busbar or Fuse Holder Mounted
IEC Standard 60269.1 AND 4
500 V Voltage Rating
Applications
Protection of High Powered Semiconductors according to I²t
Short Circuit Protection
DC or AC Motor I²t Protection
Battery Fuse
Specification
Trent Part Number
NBR-20 004 13-160A-500V-120kA-NH2
Fuse Type
I²t gG/gL Class
Nominal Voltage
500VAC @ 50Hz
Nominal Current (RMS + DC)
160 Amp
Tested Breaking Capacity
120kA @ 690VAC
Dimensions
150 x 75 x 65mm
Hole Centers
N/A Blade Style
Mounting
Fuse Holder Mounting
Operating Temperature Range
-40°C / 125°C
Termination
Blade
Unit Weight
900g
Factory Pack Qty
10
Datasheet
Product Datasheet