RCS-1800-5000, 0.333V, 3 Phase 5000Amp AC Measurement 6 Inch Rogowski Coils with Integrator, Class 1:
The RCS-1800 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-1800 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Suitable Alternative to Solar Edge CTRC-07500-3000
Specification
Magnelab Part Number
RCS-1800-5000
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
5000 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 3000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
6 Inch
Coil Circumference
18 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
VA Instruments VA520B, LCR Meter with USB Interface, LCR, Phase Angle, Q factor, Free Software Included
For Testing of:
DC Resistance
Series Inductance
Parallel Inductance
Phase Angle
Dissipation factor
Equivalent Series Resistance
Quality Factor
Equivalent Parallel Resistance
with Min USB interface and Free Software
Specification
Datasheet
Datasheet
User Manual
SSP-RED-4mm (2pcs), RED 4mm Fully Sheathed Safety/Banana Plugs, 32 Amp, 1000V Rated. For Test Equipment/Leads (Current Clamps)
4mm
Fully Sheathed
Suitable for M1/M2 or other 4mm Current Clamps
32 Amp / 1000V AC (rms) or DC Maximum Rating
Fastron S-2P-C, 2 Pole Ceramic Terminals for Thermocouple
Rated for 0 to 650 Deg C Max
Specification
Fastron Part Number
S-2P-C
Sensor Type
For RTD's or Thermocouples
No of Wires
3
Shaft Length
N/A
Shaft Thickness
N/A
Accuracy
N/A
Temperature Range
Up to 650 Deg C
Span/ Zero Adjustment
YES
Weight
50g
Factory Pack Qty
1
Fastron Electronics F41F-S, Spacer for F41F Series Slim Relays
Features
DIN Rail Mount
Changeover Contact
Ultra slim package
UL Listed
Specification
Fastron Part Number
F41F-S
Approvals
UL94V0
Dimensions
76.6 x 94.7 x 6.2
Suits Relay Type
Fastron F41F Series
Unit Weight
10g
Factory Pack Qty
100
Datasheet
Datasheet
Fastron Electronics DEVD200E1DA4, Contactor SPST-NO Non Polar, 200 AMP, 12-800VDC, 12-36VDC Coil, SPST-NO Auxiliary Contact
Features
Hermetically Sealed with inert gas
CE, CCC Approved
Ideal for battery powered systems or where low power is needed
PWM option provides additional drive control flexibility
Built in Coils suppression for all DC Coils
Side mounted version available
Specification
Fastron Part Number
DEVD200E1DA4
Main Contact Type
SPST-NO (silver plated copper)
Auxiliary Contact Type
SPST-NO
Coil Voltage
12-36VDC
Load Current
200 Amp
Mechanical Life @ 0 Amp
200,000 Operations
Dielectric at Sea Level (leakage <1mA)
2.5kV rms
Control Input Terminals
Lead Wire Connection
Special Feature
N/A
Mounting Style
Panel Mount (M5)
Load Voltage Range
12 - 800VDC
Standards
CE, CCC
Termination Style
M8
Unit Weight
550g
Factory Pack Qty
1
Datasheet
Product Datasheet
Fastron Electronics FESCTHY-19-50-100mA, 50Amp measurement Split Core CT's, w/1M Flying Leads, HY2.0 Connection, 19x19mm Aperture
Features
Quick Release Split Core System
1m Flying Leads
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.60/3kV
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
FESSCT-19-50-100mA
Technology
Split Core AC Current Transformer
Ratio
50/100mA
Aperture Size
19 x 19mm
VA Rating
N/A
Accuracy Class
Class 1
Output
100mA AC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 55°C
Continuous Current (max)
50Amp x 1.2
Termination Style
1M Twisted Pair 0.34mm^2
Unit Weight
350g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Trent FGM6S-4P-160M 100A, 4 Pole Moulded Case Circuit Breaker (MCCB) Thermal, Adjustable Type 36kA 100 Amp, 400/690VAC
Miniature Circuit Breakers are used for over-current (overload and short-circuit) protection of installations and devices, and as a disconnector in case of electric shock
Features :
4 Pole Disconnect
36kA Short Circuit Rating @400VAC
Suitable for Main Incoming Breaker
Standards :
IEC/EN 60898,60947-3
IP20 (IP40 Installed) IEC 61008
AS/NZ 61009-1
Specification
Trent Part Number
FGM6S-4P-160M 100A
Functions
4 Pole MCCB
Nominal Voltage
400/690VAC @ 50/60Hz
Nominal Current Range
100 Amps RMS
Trip Delay Time
< 50ms
Rated Impulse Voltage
8kV
Operating Temperature
-25 to 50 Deg C
Mechanical Operations
20,000 Ops
Insulation Voltage
800V
Short Circuit Current
36kA
Approvals
KEMA EUR, CE
Standards
IEC/EN 60898-1,IEC/EN 60947-3, IP20 (IP40 Installed) IEC 61008 ; AS/NZ 61009-1
Weight
1.2kg
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
Trent FGM6DC-2PL-320 100A, 2 Pole DC Moulded Case Circuit Breaker (MCCB) Fixed Type 20kA 100 Amp, 1000VDC
Miniature Circuit Breakers are used for over-current (overload and short-circuit) protection of installations and devices, and as a disconnector in case of electric shock
Features :
2 Pole Disconnect
20kA Short Circuit Rating @1000VDC
Suitable for DC Power Systems Including Solar and Battery
Standards :
IEC/EN 60947-3
IP20 (IP40 Installed) IEC 61008
Specification
Trent Part Number
FGM6DC-2PL-320 100A
Functions
2 Pole DC MCCB
Nominal Voltage
1500VDC
Nominal Current Range
100 Amps
Trip Delay Time
< 50ms
Operating Temperature
-35 to 70 Deg C
Electrical Operations
5,000 Ops
Insulation Voltage
1500V
Short Circuit Current Ics=Icu
20kA
Approvals
CE
Standards
GB/T14048.2, IEC/EN 60947-3, IP20 (IP40 Installed)
Weight
2.2kg
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
CE Declaration
Fastron FRTD-PT100-50, Pt100 Air Temperature Sensor, 50mm shaft length, 77 x 77 x 55mm Body
4-20mA Output 2 Wire
Temp Measurement for 0 to 100 Deg C Max
190 x 18mm with 1M Cable
20 Second Response Time
12-30VDC Supply 150mA max
Pt100 Temp Sensing Elements
Specification
Fastron Part Number
FRTD-PT100-50
Sensor Type
RTD (Temperature) & Thin Film Capacitor (Humidity)
No of Wires
3
Shaft Length
190mm
Shaft Thickness
18mm
Approvals
CE, ROHS
Cable length
1 Meter
Temperature Range
0 to 100 Deg C
Mounting Style
Through Hole
Weight
45g
Factory Pack Qty
1
Datasheet
Datasheet
Installation Guide
Wiring Diagram