Elite E500C-2402, Power Quality Recorder with PQ Measurements Harmonics (31st), Class 0.2S, 50..500VAC 50/60Hz, Modbus RTU Comms,35..300V DC/85..300VAC Aux, 16MB Dual Logger , TFT Touch Screen, 10 Years Warranty
Automatic range of nominal current up to 6 A (Includes 5A/1A CT Input) and nominal voltage up to 500 V L-L, 300V L-N
Dual Loggers, configurable for Instant or accumulated energy
Configurable 2 x Tariff Inputs or 2 x Pulse Outputs, or Alarm Outputs
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Measurements of energy in all 4 quadrants Average values of measurands per interval
RS 485 communication up to 38400 bit/s as standard
Optional Protocol Modules Modbus TCP, BACNet IP, Profinet, SCADA EC61850
Optional Modules for Analogue outputs and Relay Alarms
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Features :
Measurement of instantaneous values and accumulated energy. Includes Harmonics to the 15th
Accuracy class 0.5S
Dual Internal Loggers
Measurement of 20 minimal and maximal values in different time periods
RS 232/RS 485 communication up to 38400 bit/s or Ethernet communication
MODBUS communication protocol
Optional Protocol Modules Modbus TCP, BACNet IP, Profinet, SCADA EC61850
Configurable 2 x Tariff Inputs or 2 x Pulse Outputs, or Alarm Outputs
Universal or AC power supply
Graphic Colour TFT 320 x 240 pixels (53x70mm)
Automatic range of nominal current up to 6 A and nominal voltage up to 500 V
Multilingual support
User-friendly Free ECon Configuration software
Specification
Secure Part Number
E500C-2402
Functions
Power Quality Meter, Energy Meter
Supply Voltage
Universal 35..300V DC, 85..300VAC
Nominal Measurement Range
240V L-N, 1/5 Amp, 415V L-L 1/5 Amp
Maximum Measurement Range
300V L-N, 1/5 Amp, 500V L-L 1/5 Amp
Alarm
Optional Module 2 Relay/Pulse Outputs
Tariff/Digital Inputs
TOU Tarriff Clock
Accuracy
Class 0.2S (I,U,F,PF,θ,THD) Class 1(Active), Class 2 (Reactive)
Analogue Output
Optional Module 2 x Programmable Analogue Outputs
Internal Memory
2 x 8MB
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS232/RS485
N/A Optional
CT Termination
Ring Terminals
Weight
600g
Certification
CE, CSA, ROHS
Warranty
10 Years from dispatch from Secure Warehouse
Factory Pack Qty
1
EU Directives
Degree on electrical equipment designed for use within certain voltage limits URLRS 53/00 (Directive 73/23/EEC on low voltage): SIST EN 61010-1:2002
Safety Requirement for electrical equipment for measurement, control and laboratory use, part1 : general requirement
Decree on electromagnetic Compatibility (EMC) URLRS 61/00 (Directive 89/336/EEC on electromagnetic compatibility): SIST EN 61036 item 4.5: 1998 Meters for active energy (class 1 and 2)
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP52 (IP00 for terminals) in compliance with SIST EN 60529:1997
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Cross Reference
The Following meters are close equivalents to Elite 500 Series. For further details please contact Fastron Sales Team
Elite 500_400_300_100 series competition replacement for
Schneider
Siemens
Accuenergy (RS485 +DNP3 default)
Socomec
Selec
PM 5000 series
PAC 2000 series
ACCUVIM-CL + DNP3.0
DIRIS A-20
Selec MFM376
PM 5100
PAC 3200
ACCUVIM-CL + DNP3.0
DIRIS A-20
MFM384, CL-1, RS485
PM 5300
ACCUVIM-IIR
DIRIS A-20
MFM383A
PM 5500
PAC 4200
ACCUVIM-IIR(+ BACnet)
DIRIS A-20
MFM384. RS485
PM 6463
Siemens 7KMPAC4200
ACCUVIM-IIR (+ Profibus)
DIRIS A-30/ DIRIS - A60 (PQ Feature)
MFM384-C-CE-CL05, RS485
PM 5650
ACCUVIM-IIR (+ IEC 61850)
DIRIS A-30 + Profibus
MFM384-C-CE-CL05, RS485
PM 5760
ACCUVIM-EL
DIRIS A-30 +Ethernet
MFM384-C-CE-CL05, RS485
PM5330
ACCUVIM-EL (+ BACnet)
DIRIS A-30/ DIRIS A-60
PM 5560
ACCUVIM-EL (+ Profibus)
DIRIS A-30/ DIRIS A-60
DM6200H
ACCUVIM-EL (+ IEC 61850)
PM2220
ACCUVIM-II R +Ethernet
PM2230 / DM2120 (LED)
PM 5350
Fastron FPC1-32-22C-R-230VAC/DC, 4 Pole 2 x SPST NO, Configuration_2 x SPST (2 x NC), Modular Contactor 440VAC 32 Amp, 230VAC/DC Coil Voltage, 50/60Hz, Hum Free
Features
32 Amp (rms) @ 230VAC
DIN Rail Mount
Slim package
CE Compliant to IEC 60664
IP20
Specification
Fastron Part Number
FPC1-32-22C-R-230VAC
Switching Type
2 x SPST NO, Configuration_2 x SPST (2 x NC)
Approvals
CE
Coil Voltage
230VAC/DC 50/60Hz
Load Rating
32 Amp
Special Feature
Hum Free
Mounting Style
DIN Rail Mount
Load Voltage Range
440VAC 50/60Hz
Isolation
4kV
Termination Style
Screw
Unit Weight
295g
Factory Pack Qty
20
Datasheet
Datasheet
Auxiliary Contacts Selection Guide
Electronicon 275.266-608300/221K02 21.6kvar 525V 50Hz, Power Factor Correction Capacitor, 3 Phase, 116 x 245(+33 +/-2)mm Gas Filled, Requires Discharge Resistor, 3 x 83uF, Can Replace Epcos MKP525-D-20.8 (B32344E5202A020), SINGLE SIDED TERMINALS, Discharge Resistors Included
Characteristics and utility
21.6kVar @ 525V @ 50 Hz 10.0kvar 10kvar
Three phase capacitor DUAL WINDING internally delta connected
Discharge resistors Incorporated
Reactive power factor correction
Gas Filled Lightweight Construction
Connector type - single sided terminal
Indoor mounting
Triple safety
Overpressure disconnection system
Protection by internal fuses
Self Healing
Construction and materials
Low losses metallized self-healing polypropylene film, high density, high temperature and greater dielectric resistance Volt/µ
Aluminium case with bottom fixing M12x16
Standards
IEC 60831-1/2
EN 60831-1/2
Specification
Electronicon Part Number
275.266-608300/221K02 21.6kvar 525V 50Hz
Technology
Gas Filled, Low Loss, Self Healing
Dimensions
95 x 245(+33 +/-2)mm
Standards
IEC 60831-1/2, EN 60831-1/2
Voltage
525V @ 50Hz
Kvar
21.6 Kvar
Capacitance
3 x 83uF
Tolerance On Capacitance
-5% + 10% (others on request)
Current (In)
3 x 36 Amp
Overpressure Disconnection System
YES
Self Extinguishing Resin
YES
Internal Fuses
YES
Self Healing
YES
Mounting
M12 x 16mm (Indoor)
Operating Temperature Range
50°C Max, 30°C Mean(1 year), 40°C Mean(24 hrs)
Lifetime
120,000 Hours
Termination Style
Filter Type Terminal
Approvals
UL 810, CSA C22.2 No.90
Unit Weight
2.3kg
Factory Pack Quantity
25
Datasheet
Product Datasheet
Can Replace Epcos MKP525-D-20.8
Application Notes
Discharge Resistor Usage
Power Factor Correction Blog
Eastron SDM630MCT-1L-TCP 3 Phase DIN Rail Mount kWh Meter with Easyclick, 240VAC aux, Class 1, 100mA RJ12 CT Connect, w/RS485 Modbus RTU Comms
100mA RJ12 CT 4 x 3 Phase Connect
100mA RJ12 12 x Single Phase RJ12 CT with adapter
RS 485 communication up to 38,400 bit/s as standard
True RMS values of currents and voltages
Easyclick CT system reduces installation costs
Dual Metering System Reduces Cost and saves space
The meter is intended for measuring, and monitoring 1 x three phase or 3 x single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
System Accuracy Class B/Class1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM630MCT-1L
Functions
Quad Three Phase Energy Meter/ 12 x Single Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
100mA via RJ12 Easyclick CT's
Pulse Output
N/A
Tariff Input
N/A
System Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
700g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Suitable RJ12 CT's
Three Phase J12 Connected CT's
Split Core Single Phase CT's for RJ12 Connected Meters
Modbus Utility
EEM Meter Setting Software Utility
Risbabh EMDC 6002-1000-LA-C-2R, 4 Channel DC kWh Meter, Class 0.5, 150-150mV Shunt input, 201-1000VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, 4 Line LCD Display, 12-70VDC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 10-60VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EMDC 6002-1000-LA-C-2R
Functions
4 Channel DC kWh Meter, Energy Meter
Supply Voltage
12-70VDC
Nominal Measurement Range
201-1000VDC
Maximum Measurement Range
201-1000VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Risbabh EMDC 6002-60-LA-C-2R, 4 Channel DC kWh Meter, Class 0.5, 150-150mV Shunt input, 10-60VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, 4 Line LCD Display, 12-70VDC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 10-60VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EMDC 6002-60-LA-C-2R
Functions
4 Channel DC kWh Meter, Energy Meter
Supply Voltage
12-70VDC
Nominal Measurement Range
10-60VDC
Maximum Measurement Range
10-60VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Rishabh Rish Con M-22122, Class 0.5 Power Transducer 4 wire, 20-480V L-L, 5Amp measurement, 85-253VAC/90-320VDC Supply, 2 x Analogue -20-20mA/4-20mA/-10-10V output, 2 Relay Outputs, USB Programming Port, Modbus RTU Comms, 750 OHM Load Resistance, without display
Measures Active Power/Phase Angle/Power Factor
Measures Apparent/Reactive/Active Power
Analogue output setting -20-20mA/4-20mA/-10-10V
2 x Relay Outputs 0.5 Amp @ 250VAC
300mS response time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 122.5 x 66 x 106.5mm depth DIN Rail cabinet space
Specification
Rishabh Part Number
Rish Con M-22121
Functions
Active Power/Phase Angle/Power Factor Transducer 4 wire
Measurement Output
2 x 4-20mA/0-20mA/0-10V User Selectable
Minimum Load Resistance
750 Ohm
Relay Output
2 x 0.5 Amp @ 250VAC NO Voltage Free Contacts
Relay Type
Voltage Free Contact, 0.5 Amp @ 250VAC
Input
20 - 480VAC L-L 50/60Hz
Overload (Continuous)
120%
Overload (1 second)
150%
Operating Temperature
-10 - 55°C
Supply Voltage
85-253VAC/90-320VDC
Accuracy
0.2%
Response Time
300mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Mounting Size
122.5 x 66 x 106.5mm
Safety
IP40/IP20 EN60529 Protection Class II EN61010
Weight
400g
Factory Pack Qty
1
Datasheet
Product Datasheet
Product User Manual
Technical Support
Rish Con P setup procedure blog
Risbabh EM94-Z-V1-L-Z, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 60-300VDC, Single Line LCD Display,12-60V DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V1-L-Z
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
60-300VDC
Maximum Measurement Range
60-300VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Risbabh EM94-Z-V2-L-M, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 61-200VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,12-60V DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
4 x DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V2-L-M
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
61-200VDC
Maximum Measurement Range
61-200VDC
Display
4 Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Risbabh EM94-Z-V3-L-M, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 201-1000VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,12-60V DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 201-1000VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
4 x DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V3-L-M
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
201-1000VDC
Maximum Measurement Range
201-1000VDC
Display
4 Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.