Fastron Electronics SCT-F10-75-1A, 1 Amp Output, 75Amp Measurement, Class 1 Split Core CT's Class 1
Features
Quick Release Split Core System
Cable Mount
1 Amp Output
Self Powered
Rated System Voltage 0.60/3kV
0.5M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F10-75-1A
Technology
Split Core AC Current Transformer
Ratio
75/1Amp
Aperture Size
ø 8 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
1 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
50Amp x 1.2
Termination Style
0.5M Flying Leads
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Fast ONE AHF 100A-400V, Active Harmonic Filter & Static Var Generator, 70Kvar/ 100 Amp, 3 Phase + N, 400VAC +/-20%, WALL MOUNT
For Automatic Switching of Power Factor Correction Capacitors according to changing site conditions. and for the filtering or control of Harmonic Distortion
Features
Automatic Power Factor Correction up to Cos φ = 0.99
Overtemperature Alarm
Optional RS485 Comms
IEC 654-1, UL Approved
3 Year Fastron Electronics Warranty
Modular Construction for Rack or Wall Mount Installations
Perfect for Residential Applications
Stack multiple modules for larger Power Factor Correction Requirements
Specification
Fastron Part Number
Fast ONE AHF 100A-400V
Function
Reactive Power Correction & Active Harmonic Filter
Current /Load Rating
100 Amp per Phase /70Kvar
Nominal Voltage (Un)
400VAC Line to Line 50Hz
Switch Delay Time
Instant Correction/Inverter Based
Desired Harmonic
0.99 IND - 0.99 CAP
LCD Display Accuracy
IGBT Temp, Grid Current Grid THDi, Grid PF, Grid Imbalance
Current imbalance
< 5%
Comms
RS485 (Optional)
Mounting Style
Wall Mount
Termination Style
Screw
Dimensions
486x220x610mm
Weight
60kg
Certification
EN 61000-6-4:2007+A1:2011
EN 61000-6-2:2005
EN 61000-3-2:2014
EN 61000-3-3:2013+A1:2019
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0, & Stainless Steel Painted RAL 1013
Enclosure protection
IP21
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...55 °C
Datasheet
Datasheet
User Manual
Taisuo TMD-N7611 PID Controller, 100-240VAC with 1 Alarm, RS485, E,J,N,T,S,R,B Thermocouple, Linear Current/Voltage and PT100/Cu20 RTD Input, 72x72mm, SCR Trigger Output
4-digit displays (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated -0-10V, Relay, 12VDC (SSR) and 4 to 20 mA DC outputs available
Each unit needs just 75 mm depth panel space
Specification
Taisuo Part Number
TMD-N7611
Control Output
SCR/AC Switch Trigger (Single Phase)
Input
Multirange Type,E,J,N,T,S,R,B, Pt100, Cu50/(Optional)Linear Current 4(0)-20mA/(Optional)Linear Voltage 0-10(5)V
Option 1
1 Alarm
Mounting Style
72x72mm Panel Mount
Supply Voltage
100 - 240VAC +/-10%
Termination Style
Screw
Sampling Time
250ms
Weight
150-270g
Factory Pack Qty
1
Datasheet
FC5 Datasheet and User Manual
Fastron Electronics F41F-2Z-C2-1 12~24VAC/DC, Slimline SOCKET ONLY with Screw Terminals, for F115F Series for 12-24VAC/DC Coil
Features
6 Amp @ 1-36 VDC
DIN Rail Mount
Changeover Contact
Ultra slim package
UL Listed
CE Compliant to IEC 60664
IP67
Specification
Fastron Part Number
F41F-2Z-C2-1 12~24VAC/DC
Switching Type
250VAC or 30VDC Load
Control Input
12-24VAC/DC
Current @ Rated Voltage
2 x 8 Amp
Contact Arrangement
2 x SPDT C/O (Double Pole Changeover)
Approvals
UL, CE
Dimensions
76.6 x 94.7 x 6.2
Ingress Protection
IP20
Relay Type
Fastron F41F Series
Termination Style
Screw
Unit Weight
80g
Factory Pack Qty
100
Datasheet
Datasheet
Suitable Parts
F41F-60ZS
FPC1-32-04C-230VAC/DC, 4 Pole 4 x SPST NO Modular Contactor 440VAC 32 Amp, 230VAC/DC Coil Voltage, 50/60Hz, Hum Free
Features
32 Amp (rms) @ 440VAC
DIN Rail Mount
Slim package
CE Compliant to IEC 60664
IP20
Specification
Fastron Part Number
FPC1-32-04C-230VAC
Switching Type
4 x SPST NO
Approvals
CE
Coil Voltage
230VAC/DC 50/60Hz
Load Rating
32 Amp
Special Feature
Hum Free
Mounting Style
DIN Rail Mount
Load Voltage Range
440VAC
Isolation
4kV
Termination Style
Screw
Unit Weight
295g
Factory Pack Qty
20
Datasheet
Relay Datasheet
Auxiliary Contacts Selection Guide
Eastron SDM630MCT-4L-TCP, Quad 3 Phase DIN Rail Mount kWh Meter with Easyclick, 4 x 3 Phase or 12 x Single Phase, 240VAC aux, Class 1, 100mA RJ12 CT Connect, w/RS485 Modbus RTU Comms
100mA RJ12 CT 4 x 3 Phase Connect
100mA RJ12 12 x Single Phase RJ12 CT with adapter
RS 485 communication up to 38,400 bit/s as standard
True RMS values of currents and voltages
Easyclick CT system reduces installation costs
Dual Metering System Reduces Cost and saves space
The meter is intended for measuring, and monitoring 4 x three phase or 12 x single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
System Accuracy Class B/Class1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Graphic LCD with illumination
Specification
Eastron Part Number
SDM630MCT-4L
Functions
Quad Three Phase Energy Meter/ 12 x Single Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
100mA via RJ12 Easyclick CT's
Pulse Output
N/A
Tariff Input
N/A
System Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
700g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Suitable RJ12 CT's
Three Phase J12 Connected CT's
Split Core Single Phase CT's for RJ12 Connected Meters
Modbus Utility
EEM Meter Setting Software Utility
Eastron SDM630MCT-1L-TCP 3 Phase DIN Rail Mount kWh Meter with Easyclick, 240VAC aux, Class 1, 100mA RJ12 CT Connect, w/RS485 Modbus RTU Comms
100mA RJ12 CT 4 x 3 Phase Connect
100mA RJ12 12 x Single Phase RJ12 CT with adapter
RS 485 communication up to 38,400 bit/s as standard
True RMS values of currents and voltages
Easyclick CT system reduces installation costs
Dual Metering System Reduces Cost and saves space
The meter is intended for measuring, and monitoring 1 x three phase or 3 x single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
System Accuracy Class B/Class1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Graphic LCD with illumination
Specification
Eastron Europe Part Number
SDM630MCT-1L
Functions
Quad Three Phase Energy Meter/ 12 x Single Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
100mA via RJ12 Easyclick CT's
Pulse Output
N/A
Tariff Input
N/A
System Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
700g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Suitable RJ12 CT's
Three Phase J12 Connected CT's
Split Core Single Phase CT's for RJ12 Connected Meters
Modbus Utility
EEM Meter Setting Software Utility
Risbabh EM94-Z-V1-H-M, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 60-300VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display, 60-300V AC/DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
4 x DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V1-H-M
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
60-300VDC
Maximum Measurement Range
60-300VDC
Display
4 Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Risbabh EM94-Z-V3-H-M, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 201-1000VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display, 60-300V AC/DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 201-1000VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
4 x DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EM94-Z-V3-H-M
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
201-1000VDC
Maximum Measurement Range
201-1000VDC
Display
4 Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Risbabh EMDC 6002-1000-LA-C-2R, 4 Channel DC kWh Meter, Class 0.5, 150-150mV Shunt input, 201-1000VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, 4 Line LCD Display, 12-70VDC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 10-60VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EMDC 6002-1000-LA-C-2R
Functions
4 Channel DC kWh Meter, Energy Meter
Supply Voltage
12-70VDC
Nominal Measurement Range
201-1000VDC
Maximum Measurement Range
201-1000VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Risbabh EMDC 6002-200-LA-C-2R, 4 Channel DC kWh Meter, Class 0.5, 150-150mV Shunt input, 61-200VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, 4 Line LCD Display, 12-70VDC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 10-60VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DC power supply
Specification
Rishabh Part Number
EMDC 6002-200-LA-C-2R
Functions
4 Channel DC kWh Meter, Energy Meter
Supply Voltage
12-70VDC
Nominal Measurement Range
61-200VDC
Maximum Measurement Range
61-200VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YES 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
IP54
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
96 x 96mm x 83.5mm (72mm behind panel)
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.