Risbabh EM94-Z-V2-M-M, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 61-200VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,10-60V AC/DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
4 x DC Measurement Only
Â
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Â
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
10-60VAC/DCÂ power supply
Specification
Rishabh Part Number
EM94-Z-V2-M-M
Functions
kWh Meter, Energy Meter
Supply Voltage
10-60VAC/DC
Nominal Measurement Range
61-200VDC
Maximum Measurement Range
61-200VDC
Display
4Â Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YESÂ 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
Â
IP54
Â
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Â
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Â
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Â
TRBM-22D-G-240, 22mm Pushbutton Momentary GREEN 240VAC, Metal, IEC60947-5-1
Pushbutton Switches will activate while the contacts are connected. Widely Used for Rugged Industrial Applications Including Critical Machinery requiring safe operation by the user.
Features :
240VAC or 24VAC/DC (400VAC Special Orders)
1 Pole Momentary
Rated for 6 Amp @ 230VAC, or 0.3 Amp @ 230VDC
Ø 22.5mm Cutout
Standards :
IP40
IEC60947-5-1
CE
Specification
TRENT Part Number
TRBM-22D-G-240
Functions
Momentary
Colour
Black Body, Green Button
Nominal Voltage
230VAC @ 50/60Hz
Impulse Voltage Wear Resistance
6kV
Short Circuit Protection (Fuse)
Recommend 10A gG Fuse
Nominal Current Range AC
6 Amp @240VAC
Nominal Current Range DC
0.3 Amp @ 230VDC
Mechanical Compression Force at Closing
20N
Mechanical Compression Force at Closing
8N
Humidity
35-85%
Approvals
CE
Standards
IP40, IEC60947-5-1
Weight
Enclosure Material
UL94V0
Factory Pack Qty
1
TRENT(Fastron) Head Office
Australia
Â
Datasheet
Product Datasheet
DCBT-100-24-10-10, Hall Effect DC Current Transducer, +/-100 Amp DC, +/-10VDC bipolar output, 24VDC supply, 20mm Aperture
Compact and versatile Split Core DC current sensor, +/-100 Amp DC, +/-10VDC Bipolar Output
Features
⌀20mm Aperture
DC Bipolar Measurement
+/-10VDC analogue output
Busbar, or panel mounting
Isolated plastic case recognised according to UL94-V0
Advantages
High isolation between primary and secondary circuits
Easy installation
DIN Rail Kit available
Applications
-Automation Systems
Analogue current reading for remote monitoring (e.g. Motor)
-Data Loggers
Self Powered. Will not drain data logger batteries
-Panel Meters
Simple connection displays power consumption
Specification
Fastron Part Number
DCBT-100-24-10-10
Technology
 DC Hall Effect Current Transducer with Instant Output
Yes
Supply Voltage
24VDC
Nominal Current (RMS + DC)
+/-100 Amp
Response Time
< 1uS
Output
Bipolar +/-10VDC Analogue
Isolation
2.5kV (AC, 50Hz, 1 min)
Bandwidth
DC
Aperture
20mm
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 85°C
Accuracy
1%
Termination Style
Molex 4 Pin
Unit Weight
120g
Factory Pack Qty
6
Â
Datasheet
Product Datasheet
Fastron GPH10048ZD3, Solid State Contactor SSR, Single Phase 5-24VDC Control, 100Amp 70-480VAC Load, Din Rail Mount
Ratings from 10A to 100 Amp @ 70-480 VAC
Contactor Style for retrofit
SCR output for heavy industrial loads
Zero voltage or instantaneous turn-on outputs
CE Compliant to EN60950-1
IP20
AC & DC control types
Direct bond copper substrate
EMC compliant to Level 3
Direct power lead frame
Spec
Fastron Part Number
GPH10048ZD3
Switching Type
Zero Crossing
ROHS
Yes (Details)
Control Voltage
5-24VDC
Load Current (single unit)
92 Amp (rms) @ 20 Deg C Ambient, 68 Amp (rms) @ 40 Deg C Ambient
Surge Capability
1600 Amp (peak)
Special Feature
Contactor Style IP20 Terminals
Mounting Style
DIN Rail Mount
Load Voltage Range
70 - 480VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
500g
Factory Pack Qty
20
Datasheet
Product Datasheet
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Fastron Electronics GBMA-4-MA7-ANNN, 140x420mm Digital Ammeter, Panel Mount, 0-2 Amp TRUE RMS Input, 100-240VAC/VDC supply, with IR Remote Control
Adjustable Zero and Span Setting
Adjustable Display Scaling
Remote Control Included
Wall Mount
LED Tile Display
Large 4 Digit 100mm (40 Inch) LED Display
250mS Response Time
PC 94 UL V0
100mm Depth
CE Approved
Specification
Fastron Electronics Part Number
GBMA-4-MA7-ANNN
Conditioner Output
None (optional)
Input
0-2 Amp True RMS
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
140 x 420 mm Wall Mount
Case Material
PC - UL 94 V0
Weight
3.6kg
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Application Notes
Panel Meters Blog Articles
PGFM-211-B-A1-188, ELCI Marine Ground Fault Protection Relay for Single or Split Phase Systems, 27mA Detection, 50 Amp Max Ipn, 240VAC Supply, Panel Mount, Auto Reset, Note: Requires Suitable Air Pax Breaker
Features :
Suitable for Air Pax Breaker LEL Series
Applications :
On Board Vessel Earth Leakage Detection (Marine)
Specification
Sensata - Klixon Part Number
PGFM-211-B-A1-188
Supply Voltage
240VAC
Dimensions
⌀70.82mm x 59.77mm
Application
Earth Leakage Detection 27mA - 50 Amp
Trip Level
+/-27mA Nominal (Auto Reset)
Relay
Auto Reset, Requires Air Pax LEL Series Breaker
Protection
IP20
Approvals
E-11 GFP - UL 943 Category FTTJ2 when used in tandem with Airpax LEL series
Trip Time of Assembly
100mS or Less (60mS nominal)
Sensing Coil Voltage Limit
600VAC max
Operating Temnperature
-35 to 66 Deg C
Weight
200g
Mounting Style
Din Rail
Datasheet
Product Datasheet
HS103DR-D53TP50D, Solid State Relay, and Heatsink Assembly, 3 Phase 4-32VDC Control, 19.33 Amp per phase @ 40 Deg C, 48-530VAC Load, LED Status Indicator
Features
Ratings from 25A to 50 Amp @ 70-530 VAC
SCR output for heavy industrial loads
Zero voltage or Instantaneous turn-on outputs
UL/CE/ROHS Approved
IP20 Cover Available
AC & DC control types
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
HS103DR + D53TP50D
Switching Type
Zero Crossing
ROHS/CE/UL
Yes
Control Voltage
4-32VDC
Load Current
3 x 21 Amp (rms) per Phase
Surge Capability
597 Amp (peak)
Special Feature
LED Status Indicator
Mounting Style
Din Rail Mount
Load Voltage Range
48-530VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
315g
Factory Pack Qty
10
Datasheet
HS103DR
D53TP Series
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
NP200-03, Program/Step Controller, 96x96mm, 100-240VAC, Multirange Input, RS485/RS422 Comms, Universal Relay/SSR/4-20mA Outputs, 4 Digital Inputs (Event Input), 10 Alarms
Multirange Dual Output and Input, User Selectable
5-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
UL/CE Approved
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 60 mm depth panel space
EC Compliant
Specification
Hanyoung Nux Part Number
NP200-03
Control Output 1 (Heat)
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4), or 4-20mA, or SSR (12VDC, 30mA 600 Ohm)
Control Output 2 (Cool)
N/A
Input
Multirange (refer to datasheet)
Alarm
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Option 1
2nd Alarm Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Option 2
4 Digital Inputs (External Setting Input)
Comms
RS485/RS422
Mounting Style
96Â x 96mm Panel Mount
Supply Voltage
85Â - 265VAC
Termination Style
Screw
Weight
450g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CE
Yes
Â
Datasheet
NP200 Series Datasheet
NP200 Series Instruction Manual
Free Software
Hanyoung Nux TCS Software
Hanyoung Nux TCS Software User Manual
VX Series SB Driver (Windows 7) Not required for Windows 10 or 11
Â
A53TP50D + HS212DR-F, Solid State Relay, and Heatsink Assembly, 3 Phase 90-280VAC Control, 36 Amp per phase @ 40 Deg C, 48-530VAC Load, LED Status Indicator
Features
Ratings from 25A to 50 Amp @ 70-530 VAC
SCR output for heavy industrial loads
Zero voltage or Instantaneous turn-on outputs
UL/CE/ROHS Approved
IP20 Cover Available
AC & DC control types
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
D53TP50D + HS212DR-F
Switching Type
Zero Crossing
ROHS/CE/UL
Yes
Control Voltage
90-280VAC
Load Current
3 x 36 Amp (rms) per Phase
Surge Capability
597 Amp (peak)
Special Feature
LED Status Indicator
Mounting Style
Din Rail Mount
Load Voltage Range
48-530VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
315g
Factory Pack Qty
10
Â
Datasheet
D53TP Series
3 Phase SSR and Heatsink Mounted
HS212 Datasheet
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
TRENT TG-63H 1P/25/C/10kA, 1 Pole Miniature Circuit Breaker C Curve 25 Amp, 10kA, 400VAC
Miniature Circuit Breakers are used for over current (overload and short circuit) protection of installations and devices, and as a disconnector in case of electric shock
Features :
< 50mS Trip Delay Time
1 Pole Disconnect
10kA Short Circuit Rating
Suitable for Isolation
Customised versions available
Type B, C, D Curve available
Standards :
IEC/EN 60898
IEC/EN/AS60898-1
IP20 (IP40 Installed) IEC 61008
CE,CB
Specification
TRENT Part Number
TG-63H 1P/25/C/10kA
Functions
1 Pole MCB - C Curve
Nominal Voltage
400VAC @ 50/60Hz
Nominal Current Range
25 Amps RMS
Trip Delay Time
< 50ms
Rated Impulse Voltage
6kV
Operating Temperature
-25 to 40 Deg C
Mechanical Operations
10,000 Ops
Insulation Voltage
690V
Breaking Capacity
10kA
Approvals
CE,CB
Standards
IEC/EN/AS60898-1, IP20 (IP40 Installed) IEC 61008 ;
Weight
350g
Enclosure Material
UL94
Factory Pack Qty
1
TRENT Headquarters
Australia
Datasheet
Product Datasheet
Infineon BSM200GA120DLC IGBT Single Module
Features
IGBT for Low Frequency Inverter
Pressure Contact Technology
Electrically insulated base plate
Wide Temperature Range
Medium Switching Speed
2500V Isolation
61mm Base Width
Applications
Frequency Converter
Line rectifying 50/60 Hz
Deep Cycle Applications
Controlled Rectifiers
Softstart AC motor control
Low Frequency Inverter
Drives
Specification
Infineon Part Number
BSM200GA120DLC
Vces
1200V
Transistor Configuration
Single IGBT Module
Ic(nom) @ 80 Deg C
200 Amp
Package Size
W:61.4mm L:106.4mm D:30mm
V(isol)
2.5 kV
Vf @ 25 Deg C
1.8 - 2.3V
Tj(max)
150°C
Td(on) @ 25 Deg C
0.09uS
Td(off) @ 25 Deg C
0.54uS
I(ces) @ 25 Deg C
5mA
Rcc
0.5mOhm
Terminals
M6 Screw
Hole Centres
93 x 48mm(M6)
Gate Terminals
Spade (A 2.8 - 0.5mm)
R th(j-c)
0.1°C/W
R th(c-h)
0.02°C/W
Weight
340g
Mounting Torque
1.5 Nm (4 Nm Terminals)
Factory Pack Qty
10
Certification
UL Listed, ROHS
Infineon Headquarters
Germany
Datasheet
Product Datasheet
Alternatives
Contact Us for Possible Replacement for alternative