Fastron FKPC-200-400 Rev 3 (FKPC-240-CE Rev 3), Single Phase Voltage Control SCR Trigger Module, 4-20mA,0-10V,0-5V,5K POT Input, 200-450VAC, 240VAC Aux Supply, Can Replace Semikron Semi-PCM 2 SKPC200-240
Rev 2: Supports Inputs: 4-20mA,0-10V, 0-5V or 10K POT Proportional Phase Control Input
Rev 3: As above and with added internal circuit protection to imporve reliability in noisy environments.Â
Suitable for SCR Blocks up to 3000 Amp
Instantaneous turn-on output
CE Approval (Pending)
Can Replace Semikron Semi-PCM 2 SKPC200 for most applications. Please take care to connect 240VAC Aux Supply Seperately and connect the gate leads to cathode rather than anode . see full wirign detail in the datasheet Tab in this page
Specification
Fastron part Number
FKPC200-400 Rev 3 (Previously FKPC-240-CE Rev 3) (Possible Replacement to SKPC200-240)
Switching Type
Phase Angle (Random Crossing)
Control Voltage
4-20mA,0-10V,0-5V,10K POT Proportional Input (Note the zero value is 0.20.3V to avoid noise to cause gate firing
Load Current
Based on SCR Stack
Special Feature
Single Phase Proportional Controller/Trigger
Mounting Style
Panel Mount
Load Voltage Range
200-450VAC +10%
Auxiliary Power Supply
200-450VAC +10%
Termination Style
Barrier Strip Screw
Dimensions
105 x 90 x 40mm
Certifications EMC
EN 61000-6-3:2007+A1:2011, EN IEC 61000-3-2:2019+A1:2021, EN 61000-3-3:2013+A1:2019, EN IEC 61000-6-1:2019
Certifications LVD
Low Voltage Directive 2014/35/EU, EN IEC 60947-1:2021
Unit Weight
400g
Factory Pack Qty
20
Â
Datasheet and User Manual
User Manual
FKPC wiring Half Controlled M505012F Crydom Bridge for up to 240VAC - 400VAC Load
FKPC wiring Half Controlled SKCH28/16 Bridge for up to 240VAC - 400VAC Load
FKPC AC Switch Wiring
Trent NBR-CH14/UQ/20A/690V, gR Semiconductor Fuse, 20 Amp, 51x14mm 690V Semiconductor I²t Fuse Cartridge Style 51 x 14mm
Features
Cylindrical Standard Fuses Sizes
Wide Range of I²t
Ratings up to 125 Amp
Quick Release with RT18-63L fuse holder
DIN Rail Mount with RT18-63L fuse holder
Compatible with all 58 x 21mm fuse holders
IEC Standard 60269.1 AND 4
690 V Voltage Rating complying with IEC 33
Applications
Solid State Relay Switchboards
Bridge rectifier Fusing
Protection of High Powered Semiconductors according to I²t
Short Circuit Protection
DC or AC Motor I²t Protection
Battery Fuse
Specification
Trent Part Number
NBR-CH14/UQ/40A/690V
Fuse Type
I²t gR Class
Nominal Voltage
690VAC @ 50Hz
I²t Rating (Pre-Arcing)
180 A²/s
Nominal Current (RMS + DC)
20 Amp
Tested Breaking Capacity
200kA @ 690VAC
Dimensions
51 x 14mm
Fuse Holder
RT18-63L
Mounting Style
Requires fuse holder
Operating Temperature Range
-40°C / 125°C
Watt Loss
8W
DC Breaking Capacity
50kA
Unit Weight
60g
Factory Pack Qty
10
Â
Datasheet
Product Datasheet
Compatible Fuse Holder
RT18-63L
Â
FPT-60 800/5A 5P20 5VA, Protection Class CT, 800/5A, Class 5P20 5VA, 63 x 56mm Aperture
Features
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Applications
Protection Relays
Safety Equipment
Fault Monitoring
Specification
Fastron Electronics Part Number
FPT-60 800/5A 5P20 5VA
Technology
Protection Class Current Transformer
Ratio
800/5
Aperture Size
63 x 56mm
VA Rating
5VA
Accuracy Class
Class 5P20
Output
5 Amp AC
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10 Deg C / 50 Deg C
Continuous Current (max)
800Amp x 20
Termination Style
Screw
Stanbards
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Unit Weight
1.2 kg
Factory Pack Qty
1
Datasheet
Product Installation Guide and Datasheet
FPT-135 1000/5A 5P20 15VA Protection Class CT, 1000/5A, Class 5P20 15VA, 135 x 81mm Aperture
Features
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Applications
Protection Relays
Safety Equipment
Fault Monitoring
??
Specification
Fastron Electronics Part Number
FPT-135 1000/5A 5P20 15VA
Technology
Protection Class Current Transformer
Ratio
1000/5
Aperture Size
81 x 135mm
VA Rating
15VA
Accuracy Class
Class 5P20
Output
5 Amp AC (?%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10??C / 50??C
Continuous Current (max)
1000Amp x 1.3
Termination Style
Screw
Stanbards
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Unit Weight
3kg
Factory Pack Qty
1
??
Datasheet
Product Installation Guide and Datasheet
??
Crouzet Syr-Line Single Pole Multifunction Timer With SP-NO/NC Contacts
MDF Timers Syrline 48x48mm - 1 Relay 10A :
Large LED or LCD Screen (13.2 mm)
Multi-function and single-function
Basic & Advance configuration modes
Multi-range (0.05 s – 9999 h)
Multi-voltage (24-240 V AC/DC)
1 or 2 relay outputs (Changeover)
Memory option in event of a break in supply
Lock function › Up or down timing
DIN Sized (48x48 mm) Housing
Compact body (63 mm long)
Water & Dust-proof (IP66)
8-Pin
Multifunction Timers Include The Following :
Function A Delay on energisation 1 relay
Function Ac Timing after closing and opening of control contact 1 relay
Function Ad Timing delay on start with memory 1 relay
Function B Timing on impulse one shot 1 relay
Function C Timing after impulse 1 relay
Function H Timing on energisation 1 relay
Function L Recycler (OFF start) with memory 1 relay
Function Li Recycler (ON start) with memory 1 relay
Function D Symmetrical Flashing (OFF start) with Memory 1 relay
Function Di Symmetrical Flashing (ON start) with Memory 1 relay
Specification
Crouzet Part Number
MDF1R10MV2 (Syr-Line Timer Single Pole 5A Multifunction, 12 - 240VAC/DC, 48x48 mm)
Function
Multifunction Timer A - Ac - Ad - B - C - H - L - Li - D -N - Di
Nominal Voltage
12 → 240 V AC/DC
Digital Output
1 x C/O (SPDT) (Changeover -Single Pole Double Throw), 250VAC/DC @ 10 Amp
Min Breaking Current
10mA/12VDC
Timing Ranges
Selectable 0.05→9999h
Minimum Pulse Duration
30ms/100ms with load
Repeatability
0.5%
Reset Time
120ms
Isolation
1kV
Repetition Accuracy
0.5%
Threshold Adjustment Range
10 → 100 % of the range
Termination Style
8 Pin Base
Weight
180g
Certification
CE, cULus,CCC, ROHS, Reach, WEEE
Factory Pack Qty
1
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
KW62-MDC300-16, 600 Amp 130mm long Isolated Water Cooled SCR Module
Â
Replacement to Semikron SKIW500/16
Nominal 1000 Amp RMS Output using TT500N16KOF
Nominal 1100 Amp RMS Output using MCC552-16
Comes with Brass inlet and outlet for hose, along with plug.
Pressure Tested to 300 mbar
110 Deg C Normally Closed Thermal switch included
Specification
Thermal Rating based on 25 Deg C max inlet water temperature, and 50 Deg C max Ambient
Â
Type No
Litres/min
Device
Rcw deg C/W
mbar
kg
Continous Current (rms)
KW62-MDC300-16
2
50 x 92
0.055
50
2.7
500 Amp
4
50 x 92
0.042
190
600 Amp
Â
Â
Datasheet
KW62 Datasheet
Fastron GFIN/150M-DR, GFIN Heatsink for Solid State Relays, 150mm long with DIN Rail Clip 0.78 Deg C per Watt
DIN Rail or Panel Mount heat sink types
Suitable for SSR Mounting
Pre drilled for single or 3 phase SSR
Raw Finish
Specification
Fastron Part Number
GFIN/150M-DR
Mounting Type
Din Rail
Suitable SSR Rating
60/75 Amp
Dimensions (without SSR)
L:150mm x W:67mm x 88.5mm
Thermal Impedance
0.78°C/W
Unit Weight
1000g
Factory Pack Qty
10
Â
Datasheet
Product Datasheet
FPT-135 1500/1A 5P20 15VA Protection Class CT, 1500/1A, Class 5P20 15VA, 135 x 81mm Aperture
Features
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Applications
Protection Relays
Safety Equipment
Fault Monitoring
??
Specification
Fastron Electronics Part Number
FPT-135 1500/1A 5P20 15VA
Technology
Protection Class Current Transformer
Ratio
1500/5
Aperture Size
81 x 135mm
VA Rating
15VA
Accuracy Class
Class 5P20
Output
1 Amp AC (?%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10??C / 50??C
Continuous Current (max)
1500Amp x 1.3
Termination Style
Screw
Stanbards
VDE0414-44-1, GB1208-2006, EN 60044-1 and IEC 61869-2
Unit Weight
7kg
Factory Pack Qty
1
??
Datasheet
Product Installation Guide and Datasheet
??
Fastron FPC1-AUX-20-CTS Auxiliary Contact for FPC1 Series NON HUM FREE Contactors 2 x NO, 5 Amp @ 230VAC/ 1 Amp @ 130VDC. Side/Din Rail Mount
Features
UL94V0
IP20
Specification
Fastron Part Number
FPC1-AUX-20-CTS
Switching Type
2 x SPST NO
Approvals
CE
Coil Voltage
N/A
Load Rating
5 Amp @ 230VAC/ 1 Amp @ 130VDC
Special Feature
Auxiliary Contact for NON HUM FREE Contactors
Mounting Style
DIN Rail Mount
Load Voltage Range
N/A
Isolation
4kV
Unit Weight
40g
Factory Pack Qty
120
Â
Datasheet
Datasheet
Auxiliary Contacts Selection Guide
Fastron FPC1-AUX-11-CTS Auxiliary Contact for FPC1 Series NON HUM FREE Contactors 1 x NO 1 x NC, 5 Amp @ 230VAC/ 1 Amp @ 130VDC. Side/Din Rail Mount
Features
UL94V0
IP20
Specification
Fastron Part Number
FPC1-AUX-11-CTS
Switching Type
1 x SPST NO Configuration_SPST (1 x NC)
Approvals
CE
Coil Voltage
N/A
Load Rating
5 Amp @ 230VAC/ 1 Amp @ 130VDC
Special Feature
Auxiliary Contact for NON HUM FREE Contactors
Mounting Style
DIN Rail Mount
Load Voltage Range
N/A
Isolation
4kV
Unit Weight
40g
Factory Pack Qty
120
Â
Datasheet
Datasheet
Auxiliary Contacts Selection Guide
Crydom RPC2440, Phase Angle Controller, for 500K - 1M POT input, 240VAC, 40 Amps out
Features
150k Ohm POT Phase Control Input
Ratings from 15A to 40 Amp @ 70-280 VAC
SCR output for heavy industrial loads
Instantaneous turn-on outputs
UL/CE/ROHS Compliant
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
RPC2440
Switching Type
Phase Angle (Random Crossing)
ROHS/CE/UL
Yes
Control Input
500K-1M Ohm POT
Load Current
40 Amp (rms)
Surge Capability
625 Amp (peak)
Special Feature
Proportional Controller + SSR
Mounting Style
Panel Mount
Load Voltage Range
70-280VAC
Max Non Repetitive Peak Voltage
850 Vp
Termination Style
Screw
Unit Weight
160g
Factory Pack Qty
20
Â
Datasheet
Product Datasheet
Equivalent
Relequick RS1API420MA280060R RS1API420MA280080R or Crydom MCPC2450 MCPC2490 or Contact Us for Possible Replacement
Â
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Â