Crydom HD4850K-10, Solid State Relay, Single Phase 3-32VDC Control, 50A, 48-530VAC Load, Random Crossing, Gen 3 style
Features
Ratings from 25A to 125 Amp @ 48-480VAC
SCR output for heavy industrial loads
Zero voltage or instantaneous turn-on outputs
UL/CSA/VDE Approved, CE Compliant to EN60950-1
Improved SEMS screw and washer
Redesigned housing with anti-rotation barriers
AC & DC control types
Direct bond copper substrate
EMC compliant to Level 3
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
HD4850K-10
Switching Type
Random Crossing
ROHS
Yes (Details)
Control Voltage
3-32VDC
Load Current
50 Amp (rms)
Surge Capability
597 Amp (peak)
Special Feature
Gen 3 Terminals
Mounting Style
Panel Mount
Load Voltage Range
48-530VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
75g
Factory Pack Qty
20
Â
Datasheet
Product Datasheet
Notifications
Please note Changes from Gen 3 to Gen 4 (current) package design here
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Fastron Electronics FAT300D420T, AC Current Transducer, 300Amp Measurement, 36mm Split Core, 4-20mA Average RMS Output, Accuracy = 1%, Terminal Version
Features
Quick Release 36mm Split Core System
Cale Mount
4-20mA Output
24VDc Aux
Rated System Voltage 0.60/2.5kV
0.5M Flying Leads
Applications
Control Systems
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Fastron Part Number
FAT300D420T
Technology
36mm Split Core AC Current Transformer
Ratio
300/4-20mA
Aperture Size
ø 24 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
4-20mA (+20%)
Isolation
2.5kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
300Amp x 1.2
Termination Style
Screw Terminals
Unit Weight
250g
Factory Pack Qty
9
Â
Datasheet
Product Datasheet
Application Notes
Installation Guide
Eastron Smart Smart X96-5J-2-1-C, Panel Mount Multifuction Meter, Class 0.5s, 65-480VAC, 1A/5A CT input, 30 Parameter, 2 x Digital Pulse/Alarm Outputs, Ethernet Gateway, 65-480VAC Aux
Ethernet Gateway Function
Metering and Numerical Display
Adjustable tariff clock (Optional 4 Tarriffs), display of electric energy consumption in optional currency
Ethernet communication as standard
True RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Â
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Â
Features :
Measurement of instantaneous values of more than 30 quantities (U, I, P, THD, IHD, S, PF, PA, f, f, MD, etc.).
Accuracy class 0.5s
Optional 2 or 4 tariff inputs,
Digital Output and Input
Ethernet communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal or AC power supply
Graphic LCD with Dual Metering and PF Displays
Specification
Eastron Part Number
Smart X96-5I-2-1-C
Functions
Power Quality Meter, Energy Meter
Supply Voltage
65-480VAC < 7VA/3.5W
Nominal Measurement Range
65-480V L-N, 1/5 Amp
Maximum Measurement Range
280V L-N, 1/5 Amp
Pulse Outputs
2 x Digital Outputs (shared with Alarm function)
Alarm
2 x Digital Outputs (shared with Pulse function)
Tariff Input
1 (Optional 4 x )
Accuracy
Class 0.5s (I,U,F,PF,θ,THD) Class 0.5(Active), Class 1 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
2.5kV (1 Min)
Ethernet
2400-38400 b/s (Gateway Function)
Weight
500g
Certification
MID, UL
Factory Pack Qty
1
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Operating Temperature
-25 →+55 °C
Â
Datasheet
Product Datasheet
User Manual
Modbus Registers
Fastron Electronics SCT-F24-30-100mV, 30Amp/100mV Measurement, Class 1 Split Core CT's
Features
Quick Release Split Core System
Cable Mount
100mVÂ Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Fastron Part Number
SCT-F24-30-100mV
Technology
Split Core AC Current Transformer
Ratio
30/100mV
Aperture Size
ø 24 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
100mVÂ (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
30Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Â
Datasheet
Product Datasheet
Application Notes
Installation Guide
Fastron Electronics SCT-F24-20-100mV, 20Amp/100mV Measurement, Class 1 Split Core CT's
Features
Quick Release Split Core System
Cable Mount
100mVÂ Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Fastron Part Number
SCT-F24-20-100mV
Technology
Split Core AC Current Transformer
Ratio
20/100mV
Aperture Size
ø 24 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
100mVÂ (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
20Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Â
Datasheet
Product Datasheet
Application Notes
Installation Guide
Fastron Electronics SCT-F16-60-5A-CL2, 60/5 Amp Measurement, Class 2 Split Core CT's
Features
Quick Release Split Core System
Cable Mount
5 Amp Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Fastron Part Number
SCT-F16-60-5A-CL2
Technology
Split Core AC Current Transformer
Ratio
60/5 Amp
Aperture Size
ø 16 mm
VA Rating
N/A
Accuracy Class
Class 2
Output
5 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
60Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Â
Datasheet
Product Datasheet
Application Notes
Installation Guide
FRS3-C40-600R-T2, 600VDC Surge Protection Device for Photovoltaic Systems, Type 2 (Class II) 40kA WITH REMOTE C/O CONTACTS
Â
Specifications
Trent part number
FRS3-C40-600R-T2
Nominal Voltage Un
600VDC
Max Operating Voltage
720VDC
No of Poles
3
Category IEC / EN / VDE
Type 2 (Class II)
Location of use
String Box, Inverter, Sub Board Only
Protection modes
(+)-PE,(-)-PE,(+)-(-) PE
Additional Remote Contacts
YES NO/NC/COM
Protective element
MOV
No Fault/Fault Indication
Green Flag / Not Green Flag
Surge discharge rating
Per pole 40kA (8/20uS)9KA) Max, 20kA (8/20uS)9KA)Â Nominal
Internal protection and safety
Thermal disconnector in each MOV
Weight
420g
Standards
IEC614643-31:2018 (TUV, CE Approved)
Â
Datasheet
Product Datasheet
GDT/MOV/TVSÂ Tester
SPD Tester
FP150125P, 1500/5 Amp Split Core CT, Class 0.5, 7.5VA Series Clip On Current Transformer
Features
Quick Release Split Core System
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
IEC185, BS 7626, BSEN 60044-1 and IEC 60044-1
Applications
Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Fastron Electronics Part Number
FP150125P
Technology
Split Core AC Clip On Current Transformer
Ratio
1500/5
Aperture Size
85 x 120mm
VA Rating
7.5VA
Accuracy Class
Class 0.5
Output
5 Amp AC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10°C / 50°C
Continuous Current (max)
1500Amp x 1.2
Termination Style
Screw
Approvals
CE
Unit Weight
1150g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Installation Guide
Â
Fastron Electronics BTCR/A-M-A3-EI, PID Controller 48x96mm, 85-265VAC, 4-20mA output 3 Alarms, Event input (2xSV ), Multirange TC/RTD/4-20mA Input
4-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
Dust-proof IP56 (front panel only)
Optional 32-step pattern (for SV and time) is a standard feature
CE Approved
Each unit needs just 80 mm depth panel space
Specification
Fastron Electronics Part Number
BTCR/A-M-A3-EI
Control Output
4-20mA
Input
Multirange TC/RTD/4-20mA (Optional Linear voltage/current other than 4-20mA. Refer to datasheet)
Option 1
2nd and 3rd Alarm
Option 2
Event Input (2 x SV)
Mounting Style
48 x 96mm Panel Mount
Load Voltage Range
100-240VAC
Termination Style
Screw
Weight
450g
Factory Pack Qty
1
CE
Yes
Â
Datasheet
BTC Series Brochure
BTC Series User Manual
BTC Series RS485 Comms Manual
Fine Tuning PID Adjustments
Fastron Electronics GBMA-4-MA7-ANNN, 140x420mm Digital Ammeter, Panel Mount, 0-2 Amp TRUE RMS Input, 100-240VAC/VDC supply, with IR Remote Control
Adjustable Zero and Span Setting
Adjustable Display Scaling
Remote Control Included
Wall Mount
LED Tile Display
Large 4 Digit 100mm (40 Inch) LED Display
250mS Response Time
PC 94 UL V0
100mm Depth
CE Approved
Specification
Fastron Electronics Part Number
GBMA-4-MA7-ANNN
Conditioner Output
None (optional)
Input
0-2 Amp True RMS
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
140 x 420 mm Wall Mount
Case Material
PC - UL 94 V0
Weight
3.6kg
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Application Notes
Panel Meters Blog Articles
Advanced Energy Thyro-A-2A-400-130-HRL3, Thyro-A-2A-Series 2 Leg 3 Phase SCR Controller 130Amp 400VAC +10/-57% Burst(TAKT) Fire Mode, Economical Firing Mode, Voltage Control, Current Limit Option
Features
400VAC +10/-57% Line to Line Voltage, Current or Power Control
Smallest footprint on the market
Built in Fuses
3 Phase, 2 Leg Economical Burst Controller Firing Mode
(0)4-20mA, 0(1)-5V, 0(2)-10V or POT input Proportional Control
Removable Cover
USB Configuration/Bias Setting
Potentiometer Adjustment
Synchronisation Function
Applications
Electrical Ovens, Kilns, or Furnaces
Primary Control of Transformer Loads in Phase or Burst Fire mode
Resistive Loads up to 6:1 Hot/Cold Ratio
AC Soft Starter (Combined with PLC)
Power Regulation Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for extreme environments such as mining
Series Optional Features
For HRL
Current Control/Feedback
Programmable Relay Alarm Output
Load Monitoring
Analogue Output
For HRLP
As above with Power Control Feedback
Communication Options
Standard Thyro Bus Module
BasicBus Module
Â
Specification
Advanced Energy Part Number
Thyro-A-2A-400-130-HRL3
Approvals
CE, UL508A, EU Directive 2014/35/EU & 2004/108/EC
Control Accuracy
3% at rated voltage
Rated Operating Temperature
45°C
Temperature Derating
0.9 x Inom @ 50 Deg C, 1.1 x Inom @ 35 Deg C
SCR Configuration
Single Phase AC Switch
Control Modes
2 Leg Burst(TAKT) for low dissipation
Control Input
4(0)-20mA, 0(1)-5V, 0(2)-10V, POT
Load Current
16 to 1500 Amp @ 45 Deg C (110% @ 35 Deg C Max)
Control Range
0-100%
Options
Conformal Coating for Gas or High Humidity Environments
Mounting Style
Panel Mount
Supply Voltage Range
400VAC +10/-57% (-57% with 24VDC Aux Supply)
Soft Start
Via PLC input
Termination Style
Screw
Unit Weight
2.1 to 74kg
Factory Pack Qty
1
Â
Technical Docs
Brochure
User Manual
2 Leg Control Application Blog
Thyro A Series Quick Installation Guide
Setting Up Comms on Thyro A Series Controllers
Anybus Device Ethernet IP Setup Guide