Hanyoung Nux UP12RM-2PA-C, Inductive Proximity Sensor M12 Cylindrical Shielded, 2mm Sensing Distance (0-1.6mm Set), 12-24VDC PNP Output, Normally Open NO, Connector Type
800HZ Response
12-24VDC Operating voltage
200mA Maximum Output
Built in reverse power, surge, overcurrent protection
50 Meg Ohm Insulation residtance
Specification
Hanyoung Nux Part Number
UP12RM-2PA-C
Sensor Type
Inductive Proximity Sensor M12 Cylindrical Shielded
No of Wires
3
Material
Stainless Steel Body / Face PBT / Cable Holder Polyester Elastomer
Shielded
YES
Sensing Distance
2mm (0-1.6mm Set)
Frequency Response
800Hz
Output Type
12-24VDC PNP Normally Open
Sensor Thread Size
M12
Standard Target
Ferrous Metal 12 x 12 x 1mm
Approvals
CE
Residual Voltage
1.5V
Current Consumption
6mA
Ambient Operating Temperature
-25 to 70 Deg C
Insulation Resistance
50 Meg Ohm (500V dc in Megohms) between all terminals and case
Dielectric Strength
1500Vac 1 min at 50/60Hz Between all terminals and case
Shock Resistance
500m/s^2, 3 times in each direction
Vibration Resistance
10-55Hz Double amplitude: 1.5mm, 2 hours in each direction X,Y,Z)
Termination
Cable Type (stdnard 2M cabel length), connector cable type, connector type
Colour
NPN:Green, PNP:Navy
Protection Class
IP67
Approvals
CE
Weight
80g
Factory Pack Qty
1
??
Datasheet
Product Datasheet
Iskra IPO-24, 24 Module Compact Distribution Boards, Flush Mounted IP40, 15 x PE and 15 x N Conductor Terminals
Features
IP40 Protection Class
RAL 7035
Double Insulation
IEC 60670-1, IEC 60670-24
INstallation Temperature -20 to 60 Deg C
Glow Wire Test 650 Deg C
15 x PE and 15 x N Conductor Terminals
Datasheet
Product Datasheet
Current Transducer, GMTA-DV4-A-RN, DC Voltage Transmitter with Alarm, 0-10V DC Input, 100-240VAC/DC Aux, 1 x Relay Output
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals, Currents up to 10 Amp, and Voltages up to 600VAC or DC, can be converted to insulated 4 to 20 mA DC output (for direct current output type) or 0-10V/0-5V (For Direct Voltage Type), or given alarm Setpoint.
Each unit needs just 50mm x 120mm depth DIN Rail cabinet space
Specification
Part Number
GMTA-DV4-A-RN
Control Output
1 x RelayÂ
Input
0-10VDC
Alarm Type
1 x SPSTÂ NO Relay 3 Amp
Over Range
x 1.2
Operating Temperature
0 - 60°C
Load Voltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Fastron Electronics SCT-Y24-100A/100mA, 100A/100mA Measurement, Class 1 Split Core CT's, Easy Click HY2.0 Connector for CRJ-31 RJ45 Splitter
Features
Quick Release Split Core System
Cable Mount
100mAmp Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads with HY-2.0 Connector
Applications
Eastron Modular Metering Equipment
Energy Monitoring
Load Balancing
Power Quality Measurements
Â
Specification
Fastron Part Number
SCT-Y24-100A/100mA
Technology
Split Core AC Current Transformer
Ratio
100/100mA
Aperture Size
ø 24 mm
VA Rating
1VA
Accuracy Class
Class 1
Output
100mA (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
100Amp x 1.2
Termination Style
0.9M Flying leads with HY-2.0 Connector
Unit Weight
100g
Factory Pack Qty
9
Â
Datasheet
Product Datasheet
Application Notes
Installation Guide
CRJ-31 Connector User Guide
VX3-UMNA-A4T, Temp Controller/Indicator, 48x96mm, 100-240VAC, Multirange Input, 4-20mA PV Retransmission Output, 3 Alarms, Can replace Shinko JIR301M
Multirange Input (Programmable)
4-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
Drip-proof / Dust-proof IP65 (front panel only)
UL/CE Approved
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 60 mm depth panel space
EC Compliant
Specification
Hanyoung Nux Part Number
VX3-UMNA-A4T
Control Output 1 (Heat)
Relay
Control Output 2 (Cool)
4-20mA PV Retransmission
Input
Multirange Type K/J/E/T/R/B/S/L/N/U/W/PLII/PT100/JPT100/4-20mA/0-20mA/1-5V/0-5V/0-10V/0-50mV/0-100mV. Note for Direct Current Input please use 250 Ohm Resistor in Parallel to the input terminals.
Alarm
4 x Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Option 1
2nd Alarm Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Option 2
N/A
Mounting Style
48 x 96mm Panel Mount
Supply Voltage
85Â - 265VAC
Termination Style
Screw
Weight
350g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CE
Yes
Â
Datasheet
VX Series Brochure
VX Series Instruction Manual
Free Software
Hanyoung Nux TCS Software
Hanyoung Nux TCS Software User Manual
VX Series SB Driver (Windows 7) Not required for Windows 10 or 11
Â
Fastron Electronics SCT-F36-250-5A, 5 Amp, 250Amp measurement Split Core CT's
Features
Quick Release Split Core System
Cable Mount
5 Amp Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F36-250-5A
Technology
Split Core AC Current Transformer
Ratio
250/5 Amp
Aperture Size
ø 35 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
5 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
250Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
400g
Factory Pack Qty
9
Datasheet
Product Datasheet
Stocked Split Core CT's Listing
Application Notes
Installation Guide
Types of Current Transformers - Blog
Cable Losses and CT's
High Accuracy or High Burden Requirements for CT's
Iskra INO-24, 24 Module Compact Distribution Boards, Surface Mounted IP65, 15 x PE and 15 x N Conductor Terminals
Features
IP65 Protection Class
RAL 7035
Double Insulation
IEC 60670-1, IEC 60670-24
Installation Temperature -20 to 60 Deg C
Glow Wire Test 650 Deg C
15 x PE and 15 x N Conductor Terminals
Datasheet
Product Datasheet
Shinko BCD2S1000 Series Digital Indicating Controllers
• Program control, converter function are standard features
• 5-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
• Drip-proof / Dust-proof IP66 (front panel only)
• 9-step pattern (for SV and time) is a standard feature
• UL/CSA Approved
• Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
• Each unit needs just 60 mm depth panel space
• EC Compliant (Details)
Specification
Shinko Part Number
BCD2S1000
Control Output
SSR 12VDC +/-15%, 40mA (short circuit protected)
Input
Multirange (refer to datasheet)
Option 1
2nd Alarm, 4-20mA Cooling Output
Option 2
None
Mounting Style
96 x 96mm Panel Mount
Load Voltage Range
24VAC/DC
Termination Style
Screw
Weight
170g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CE
Yes
Datasheet
BC Series Brochure
BC Series User Manual
BC Series RS485 Comms Manual
Shinko Product Guide
Fine Tuning Adjustments