Shinko BCR2R1016 Series Digital Indicating Controllers
• Program control, converter function are standard features
• 5-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
• Drip-proof / Dust-proof IP66 (front panel only)
• 9-step pattern (for SV and time) is a standard feature
• UL/CSA Approved
• Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
• Each unit needs just 60 mm depth panel space
• EC Compliant (Details)
Specification
Shinko Part Number
BCR2R1000
Control Output
SSR 12VDC +/-15%, 40mA with (short circuit protected)
Input
Multirange (refer to datasheet)
Option 1
2nd Alarm Relay
Option 2
RS485 Comms
Mounting Style
48 x 96mm Panel Mount
Load Voltage Range
24VAC/DC
Termination Style
Screw
Weight
170g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CE
Yes
Datasheet
BC Series Brochure
BC Series User Manual
BC Series RS485 Comms Manual
Shinko Product Guide
Fine Tuning Adjustments
Fastron FDV-25-V10-24, DC Voltage Transducer, Din Rail Mount, 0-25VDC, 0-10V output, 24VDC Supply Voltage, 150mS Response
150mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 5V DC output (for voltage output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Part Number
FDV-25-V10-24
Analogue Output
0-10V
Input
0 - 300VDC
Measurement Range
120%
Overload
150% Continuous
Operating Temperature
-30 - 70°C
Operating Voltage
24VDC +/-15%
Voltage Isolation (1 min)
2.5kV
Accuracy
1%
Response Time
150mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Safety
CE, UL94V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Fastron FPC1-63-04C-230VAC, 4 Pole 4 x SPST NC, Modular Contactor 440VAC 63 Amp 50/60Hz, 230VAC Coil Voltage, Hum Free
Features
63 Amp (rms) @ 440VAC
DIN Rail Mount
Slim package
CE Compliant to IEC 60664
IP20
Specification
Fastron Part Number
FPC1-63-04C-230VAC/DC
Switching Type
4 x SPST NC
Approvals
CE
Coil Voltage
230VAC/DC, 50/60Hz
Load Current (RMS/DC)
63 Amp (rms) @ 440VAC
Special Feature
Hum Free
Mounting Style
DIN Rail Mount
Load Voltage Range
440VAC, 50/60Hz
Isolation
4kV
Termination Style
Screw
Unit Weight
295g
Factory Pack Qty
20
Datasheet
Relay Datasheet
Auxiliary Contacts Selection Guide
Fastron FRI8-02/16, Under Current Monitoring Relay AC 0.16 - 16 A, Adjustable delay 0.5 - 10 s, 1 x CO 10 Amp, Universal 24-240VAC 24VDC Aux Supply
FRI 8 Series serves to monitor AC currents up to 16 Amp, and provides Relay alarm output with adjustable delay time 0.5 - 10s.
Features :
Suitable for Current Transformer Monitoring
Flexible adjustment by potentiometer, choice of
6 Models: 0.05 - 0.5 A; 0.1 - 1 A; 0.2 - 2 A; 0.5 - 5 A; 0.8 - 8 A; 1.6 - 16 A Adjustable delay 0.5 - 10 s to eliminate short current peaks
Possible to use current scanning from current transformer - up to 600 A Universal supply AC 24 - 240 V and DC 24 V
Supply is galvanically separated from measured current
Output contact: 1 x changeover 8 A
1-phase, 1-MODULE, DIN rail mounting
Applications :
Heating bars in sliding rails
Heating cables
Indication of current flow
Controlling of 1-phase motor consumption
Specification
Fastron Part Number
FRI8-02/16
Voltage Range
AC 24 - 240 V, DC 24 V (AC 50 - 60 Hz)
Operating Range
Current Range
0.16 - 16 A (AC 50 Hz)
Current Trip Adjustment
Potentiometer
Setting Accuracy
5 %
Burden
max. 1.5 VA
Repeatability
1 %
Temperature Drift
0.1%/??C
Peak Overload (10s)
1.1 x Ipn
Time delay T1
max. 500 ms
Time delay T2
adjustable 0.1-10 s
Output
??
Number of contacts
1x changeover/ SPDT (AgNi / Silver Alloy)
Rating
10 A / AC1
Breaking capacity
2500 VA / AC1, 240 W / DC
Inrush current
10 A
Switching voltage
250 V AC1 / 24 V DC
Min. breaking capacity DC
500 mW
Indication of state
red LED
Mechanical life
1 x 107
Electrical life (AC1)
1 x 105
Other information
??
Operating temperature
-20 ... ? ??C
Storage temperature
-30 ... ? ??C
Electrical strength
4 kV (supply - output)
Operating position
any
Mounting
DIN rail EN 60715
Protection degree
IP 40 from front panel / IP 10 terminals
Overvoltage cathegory
III.
Pollution degree
2
Max. cable size (mm )2
solid wire max. 2x2.5 or 1x4 ; with sleeve max. 1x2.5 or 2x1.5
Dimensions
90 x 17,6 x 64 mm
Weight
69 g
Standards
EN 60255-6, EN 61010-1, RoHS, CE
Datasheet
Product Datasheet
Application Notes
Monitoring relay FRI serves to monitor current level in single phase AC circuits. Due to its fluent adjustment of release current, it is predestined for applications with necessity of current flow indication, and can be used as precedence relay. Output relay is off in normal state. In case the set current level is exceeded, it switches. Multivoltage supply is an advantage.
Crouzet 88865265 TK2R Double Pole Multifunction Timer with DPDT CO Contacts
TK2R Timers Syrline 17.5 mm - 2 Relays 8A :
Multi-range (0.5s - 10days)
Multi-voltage 24VDC or 12 - 240VAC
LED status indicator
Possibility of external load connection in parallel to the control input
Multifunction Timers Includes The Following :
Function K-2 Delay on de-energisation True delay OFF 2 relays
Specification
Crouzet Part Number
88865265 (Syr-Line Timer Single Pole Double Throw 2 x 8A C/O, 24VDC or 12 - 240VAC, 22.5 mm)
Function
Dual Function Timer K-2
Nominal Voltage
24VDC or 12 - 240VAC
Digital Output
2 x C/O (DPDT) (Changeover -Single Pole Double Throw-), 250VAC/DC @ 8 Amp
Min Breaking Current
10mA/12VDC
Timing Ranges
Selectable 0.6→160s
Minimum Pulse Duration
30ms/100ms with load
Repeatability
0.5%
Reset Time
120ms
Isolation
4kV
Repetition Accuracy
0.5%
Threshold Adjustment Range
10 → 100 % of the range
Termination Style
Screw
Weight
80g
Certification
CE, cULus,CCC, ROHS, Reach, WEEE
Factory Pack Qty
1
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
Shinko BCD2R1006 Series Digital Indicating Controllers
• Program control, converter function are standard features
• 5-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response)
• Drip-proof / Dust-proof IP66 (front panel only)
• 9-step pattern (for SV and time) is a standard feature
• UL/CSA Approved
• Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
• Each unit needs just 60 mm depth panel space
• EC Compliant (Details)
Specification
Shinko Part Number
BCD2R1006
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Input
Multirange (refer to datasheet)
Option 1
None
Option 2
RS485
Mounting Style
96 x 96mm Panel Mount
Load Voltage Range
24VAC/DC
Termination Style
Screw
Weight
170g
Factory Pack Qty
1
ROHS
Yes
UL
Yes
CE
Yes
Datasheet
BC Series Brochure
BC Series User Manual
BC Series RS485 Comms Manual
Shinko Product Guide
Fine Tuning Adjustments
FBS LCD 24/4M, 24VDC Surge Protection Device for IT Systems, LPZ 0A-2 of higher, 10kA
Specifications
Telebahn part number
FBS LCD 24/4M
Nominal Voltage
24VDC
No of Poles
4
Category IEC / EN / VDE
Type 2
Location of use
Communication/Signal Lines
Protection modes
L1+/L1-, L2+/L2- , for
Additional Remote Contacts
NO
Protective element
MOV
No Fault/Fault Indication
N/A
Surge discharge rating
Per pole 10kA (8/20uS)10KA) Max, 20kA (8/20uS)2.5KA) Nominal
Internal protection and safety
Thermal disconnector in each MOV
Weight
120g
Standards
IEC 61643-21; EN 61643.21; GB 18802.21
Datasheet
Product Datasheet
GDT/MOV/TVS Tester
SPD Tester
VFD4A2MS43ANSAA, 3 Phase Variable Frequency Drive, 460VAC, 1.5kW, 3.2 Amp (Normal Duty)/3.5 Amp (Heavy Duty), 460VAC L-L, 0.1-599 Hz, 142x72x143mm
Features
3 Phase VFD/VSD
4-20mA, 0-5V, 0-10V Proportional Input Control
7 x Digital Input
2 x STO Inputs
Fully enclosed IP20 (Optional IP40)
Small frame Size
Applications
Fan Motor Control
Production Lines
Transportation
Controlled Power Applications
Suitable for extreme environments such as mining
Specification
Delta Part Number
VFD4A2MS43ANSAA
Rated Operation Temperature
50°C (With Derating)
Configuration
3 Phase AC Drive
Control Voltage
4-20mA, 0-20mA, 0-10V
Digital Inputs
7 x Mix / 2 x STO
Load Current
3.2 Amp(Normal Duty) / 3.5 Amp(Heavy Duty) Per Phase
Control Range
0.1-599 Hz
Dimensions
207x109x154mm
Mounting Style
Panel Mount
Supply Voltage Range
323-528VAC
Soft Start
0-6000s
Termination Style
Screw
Unit Weight
2.5kg
Factory Pack Qty
1
Datasheet
MS300 Brochure
User Manual
Fastron FCT-D16-5-420, AC Split Core Current Transducer, 16mm Aperture, 0-5 Amp Measurement, 4-20mA Average RMS output, 24VDC Loop Powered, Class 0.5, 50-400 Hz Operation
Features
Average RMS Output
Split Core
4-20mA Current Output
Cable Mounting
24VDC Loop Powered
Isolated plastic case recognised according to UL94-V0
Advantages
Large aperture for cable up to 16mm
High isolation between primary and secondary circuits
Easy installation
Applications
Current Measurement
Energy Management
Motor Control
Actuators
Lamp Failure
Specification
LEM Part Number
AT 5 B420L
Technology
AC Current Transformer
Protection Class
IP50
Supply Voltage
24VDC Loop Powered (10mA)
Load Current (RMS)
5 Amp
Maximum Measurement Current (RMS)
6 Amp
Output
4-20mA (Average RMS)
Isolation
2.5kV (AC, 50Hz, 1 min)
Bandwidth
50 - 400Hz
Mounting Style
Din Rail Mount
Operating Temperature Range
-10°C / 65°C
Accuracy
0.5%
Aperture
16mm
Termination Style
Screw
Approvals
CE,UL,ROHS
Unit Weight
140g
Factory Pack Qty
6
Datasheet
Product Datasheet
Fastron Electronics SCT-F50-1000-5A, 5 Amp, 1000Amp measurement Split Core CT's
Features
Quick Release Split Core System
Cable Mount
5 Amp Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F50-1000-5A
Technology
Split Core AC Current Transformer
Ratio
1000/5 Amp
Aperture Size
ø 50 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
5 Amp (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
1000Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
1000g
Factory Pack Qty
9
Datasheet
Product Datasheet
Stocked Split Core CT's Listing
Application Notes
Installation Guide
Types of Current Transformers - Blog
Cable Losses and CT's
High Accuracy or High Burden Requirements for CT's