Schurter CE20.6100.151, IEC Appliance Inlet C14/M with Filter, Fuseholder 2-pole 5 x 20 mm
Features
Panel Mount : Screw-on mounting from front side
4 Functions : Appliance Inlet Protection class I, EMC Line Filter Line Switch 2-pole, Fuseholder for fuse-links 5 x 20 mm 2-pole
Line filter in standard and medical version
Quick connect terminals 6.3 x 0.8 mm
Characteristics
Compact design with optimal shielding
All single elements are already wired
Plug removal necessary for fuse-link replacement
With EMC-shield
Suitable for use in equipment according to IEC/UL 60950
Suitable for use in medical equipment according to IEC/UL 60601-1
Medical Version
M80
NOTE Requires 4305.0001,4305.0006,4305.0011,or 4305.0016 Fuse Drawer
Specification
Schurter Part Number
CE20.6100.151
Rated Voltage
250V
Rated Current
2A
Filter Stages
1 Stage Standard
Operating Temperature
-25°C to 85°C
Filter Type
Differential and Common Mode
Fuse Holder
2 Pole
Line Switch
2 Pole
Mounting
Panel Mount
Material
Nickel Plated Steel
Termination Style
C14 Male to Quick Connects
Weight
260g
Factory Pack Qty
1
Protection Class
From front side IP 40 acc. to IEC 60529
Isolation
1.7kV
VDE/UL/CSA/ROHS
Yes
Datasheet
Product Datasheet
Schurter 5500-2042, 1 Stage EMC (RFI) Line Filter for Single Phase systems
Features
Line filter in standard and medical version
1-stage - standard attenuation
Characteristics
Designed for standard applications
Protection against interference voltage from the mains Possible interferences generated in the equipment are strongly attenuated
Universal line filter for standard applications
Suitable for use in equipment according to IEC/UL 60950
Other Versions on Request
Version with wire connection
Version with varistor for overvoltage protection
Specification
Schurter Part Number
5500-2042
Rated Voltage
250V
Rated Current
10A
Filter Stages
1 Stage
Operating Temperature
-25°C to 85°C
Filter Type
Standard Attenuation
Leakage Current
0.25mA
Mounting
Panel Mount - Case 41
Material
Metal
Termination Style
Screw
Weight
55g
Factory Pack Qty
1
Protection Class
From front side IP 40 acc. to IEC 60529
Isolation
1.7kV
VDE/UL/CSA/ROHS
Yes
Datasheet
Product Datasheet
F922 Series AC Average RMS or DC Current Transducer, 9-36VDC Supply, 0-8 Amp, 4 Output types available
Features
Isolated measurement of AC or DC currents using internal Hall effect transducer.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned AC or DC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty. Otherwise 4-6 weeks
Specification
Oztherm Part Number
F922-X-XX-XX
Functions
Single Phase AC or DC Current Transducer
Supply Voltage
9-36VDC
Nominal Measurement Range
0-8 Amp (Sensor dependant)
Maximum Measurement Range
8 Amp
Alarm
C/O Relay 4Amp @ 30VDC, 0.5Amp @ 150VAC
Response Time
250mS
Accuracy @ 25 Deg C
Class 1
Bandwidth
DC - 1kHz
linearity
< 0.15%
Isolation
2.5kV
Comms
N/A
Weight
250g
Enclosure Size
79 x 60 x 85mm
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
Polyamide non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP40
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
F921 Series AC Current Transducer with Process Outputs & High and Low Sold State Alarm
Features
Isolated measurement of AC currents using internal Hall effect transducer.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned AC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty. Otherwise 4-6 weeks
Specification
Oztherm Part Number
F921-X-XX-AC-XX
Functions
Single Phase AC Current Transducer
Supply Voltage
9-36VDC
Nominal Measurement Range
0-8 Amp (Sensor dependant)
Maximum Measurement Range
8 Amp
Alarm
C/O Relay 2Amp @ 40VDC, 2Amp @ 60VAC
Response Time
250mS
Accuracy @ 25 Deg C
Class 1
Bandwidth
DC - 1kHz
linearity
< 0.15%
Isolation
2.5kV
Comms
N/A
Weight
250g
Enclosure Size
79 x 60 x 85mm
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
Polyamide non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP40
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
Fastron F312 Series Proportional Phase Control Solid State Relay Controller
Proportional Phase Controller for SSR switching
Ratings from 25A to 90 Amp @ 90-600 VAC
Use any DC Control Solid State Relay
Use any Solid State Contactor
Instantaneous turn-on outputs
Specification
Fastron Part Number
F312 Series
Switching Type
Phase Angle or Burst (Selectable)
ROHS/CE/UL
Yes
Control Voltage
0 - 10V/0 - 5V/4 - 20mA/POT Input (at time of order)
Load Current
N/A based on SSR
Surge Capability
N/A based on SSR
Special Feature
Proportional Controller for SSR
Mounting Style
DIN Rail Mount
Load Voltage Range
90-415VAC
Dielectric Strength
4kV
Termination Style
Screw Terminal
Unit Weight
360g
Factory Pack Qty
20
Datasheet
Product Datasheet
F312 User Manual
Product Notifications
Please note Changes from Gen 3 to Gen 4 (current) package design here
Equivalent Parts
Contact Us for Possible Replacement
Dynex DCR1260F42 Thyristor(SCR) Capsule, 1260Amp, 4200V, 74/26
Features
Very low forward voltage drop
Very low leakage current
International standard package
74/26 Package
Press Mounted
Double or Single Sided Cooling
Applications
Power Supplies
Rectifier for drives applications
Uncontrolled Rectifiers
Rectifiers for UPS
Battery Chargers
Field Supply for DC Motors
Water Cooled Rectifiers
DC Substation Blocking Diode
Large Generators
Specification
Dynex Part Number
DCR1260F42
Vrrm
4200V
Diode Configuration
Thyristor Capsule (PUK)
IF(av) @ 60 Deg C
1260 Amp
Package Size
ø74 x 26mm
Itsm
16.8 kA
VF(to)
0.91V
Tj(max)
125°C
rF
0.611mΩ
Gate Terminals
With 400mm Gate Leads
R th(j-c) (double sided cooled 180°sin)
0.0184°C/W
R th(c-h) (double sided cooled)
0.004°C/W
Weight
600g
Clamping Force
20 - 25kN
Factory Pack Qty
6
Certification
ROHS
Dynex Headquarters
UK
Datasheet
Product Datasheet
Alternatives
N1159NC400
Contact Us for Possible Replacement
Dynex 2022 Shorform Catalogue
Heatsink
Heatsink Profiles