Trent 100AAF Series 690V, 100 Amp aR Semiconductor I²t Fuse BS88 Style
Features
Equivalent to Mersen 6.9 URT 217/110 B099959, 6.9 URT 217/90 A099958, Bussman 110EET, ETI BS17D/70/110A/690V
British Standard Fuse Links Package
Wide Range of I²t
Ratings up to 1000 Amp
Busbar or Standoff Mounting
IEC Standard 60269.1 AND 4
690 V Voltage Rating complying with IEC 33
Applications
Protection of High Powered Semiconductors according to I²t
Short Circuit Protection
DC or AC Motor I²t Protection
Battery Fuse
Specification
Trent Part Number
100AAF
Fuse Type
I²t AR Class
Nominal Voltage
690VAC @ 50Hz
I²t Rating (IP < 30IN)
5450 A²/s
I²t Rating (IP > 30IN)
6850 A²/s
Nominal Current (RMS + DC)
100 Amp
Tested Breaking Capacity
200kA @ 690VAC
Dimensions
90.2 x 30 x 36.7mm
Hole Centers
62.4 - 76mm
Mounting Style
Busbar or Panel Mount with Standoff
Operating Temperature Range
-40°C / 125°C
Watt Loss
25W
Termination Style
M6
Unit Weight
61g
Factory Pack Qty
10
Datasheet
Product Datasheet
Cross Reference Chart
Schurter 5500-2063, 2 Stage EMC (RFI) Line Filter for Single Phase systems
Features
Line filter in standard and medical version
2-stage - high attenuation
Characteristics
Designed for standard applications
Protection against interference voltage from the mains Possible interferences generated in the equipment are strongly attenuated
Universal line filter for standard applications
Suitable for use in equipment according to IEC/UL 60950
Other Versions on Request
Version with wire connection
Version with varistor for overvoltage protection
Specification
Schurter Part Number
5500-2063
Rated Voltage
250V
Rated Current
10A
Filter Stages
2 Stage
Operating Temperature
-25°C to 85°C
Filter Type
Very High Symmetrical and Asymmetrical Attenuation
Leakage Current
2.5mA
Mounting
Panel Mount - Case 48
Material
Metal
Termination Style
Screw
Weight
275g
Factory Pack Qty
10
Protection Class
Suitable for appliances with protection class I acc. to IEC 61140
Isolation
1.7kV
VDE/UL/CSA/ROHS
Yes
Datasheet
Product Datasheet
OEM +/-15VDC Bipolar Power Supply
Open frame solution
Din Rail Mount
RMS Output with Galvanic Isolation
Opitons Include 24AC/DC, 110VAC,240VAC,415VAC
Output Current 160mA RMS
Open frame solution
Delivery in 3-5 days for small qty, Otherwise 3-4 weeks
Operating Temperature Range: 0 to 50 Deg C
Datasheet
Product Datasheet
F921 Series AC Current Transducer with Process Outputs & High and Low C/O Alarm
Features
Isolated measurement of AC currents using internal Hall effect transducer.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned AC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty. Otherwise 4-6 weeks
Specification
Oztherm Part Number
F921-X-XX-AC-XX
Functions
Single Phase AC Current Transducer
Supply Voltage
9-36VDC
Nominal Measurement Range
0-400 Amp (Sensor dependant)
Maximum Measurement Range
0-2500 Amp (with HAX 2500-S external Sensor)
Alarm
C/O Relay 4Amp @ 30VDC, 0.5Amp @ 150VAC
Response Time
250mS
Accuracy @ 25 Deg C
Class 1
Bandwidth
DC - 1kHz
linearity
< 0.15%
Isolation
2.5kV
Comms
N/A
Weight
250g
Enclosure Size
79 x 60 x 85mm
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
Polyamide non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP40
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet
F921 Series DC Current Transducer with Process Outputs & High and Low Sold State Alarm
Features
Isolated measurement of DC currents using a Hall effect transducer with external aperture.
Incorporates an integrated input level display and power supply.
Wide measurement range available
Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned DC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Applications
Process control
Transportation
Petrochemical
Industrial
Earth Leakage
Energy Monitoring/Measurement
Automation
Delivery
Delivery in 3-5 days for small qty. Otherwise 4-6 weeks
Specification
Oztherm Part Number
F921-X-XX-DC-XX-XX
Functions
Single Phase AC Current Transducer
Supply Voltage
9-36VDC
Nominal Measurement Range
0-400 Amp (Sensor dependant)
Maximum Measurement Range
2500 Amp with External Sensor
Alarm
C/O Relay 2Amp @ 40VDC, 2Amp @ 60VAC
Response Time
250mS
Accuracy @ 25 Deg C
Class 1
Bandwidth
DC - 1kHz
linearity
< 0.15%
Isolation
2.5kV
Comms
N/A
Weight
250g
Enclosure Size
79 x 60 x 85mm
Factory Pack Qty
1
EU Directives
N/A
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
Polyamide non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP40
Shock Withstand
300g 8ms Pulse . 6 Shocks in each of 3 axes
Vibration Withstand
0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes
Operating Temperature
-20 →+70 °C
Datasheet
Product Datasheet