Fastron Electronics GT-T/TO(0-150)/D1, Signal Isolator/Conditioner, DIN Rail Mount, PT100 RTD (0-150 Deg C) Input, 4-20mA output, 22-60VAC/DC supply
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
GT-T/TO(0-150)/D1(0-20mA)
Control Output
4-20mA
Input
RTD (Pt100)
Over Range
N/A
Operating Temperature
0 - 60°C
Load Voltage
22-60VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Crydom D53TP50DH + KS300, SSR 3 Phase 4-32VDC Control, 50A, 48-530VAC Load, LED Status Indicator, Cover + HSP-3 Thermal pad.
Features
Ratings from 25A to 50 Amp @ 70-480 VAC
SCR output for heavy industrial loads
Zero voltage or Instantaneous turn-on outputs
UL/CE/ROHS Approved
IP20 Cover Available
AC & DC control types
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Spec
Crydom Part Number
D53TP50DH + KS300
Switching Type
Zero Crossing
ROHS/CE/UL
Yes
Control Voltage
4-32VDC
Load Current
50 Amp (rms) per Phase
Surge Capability
597 Amp (peak)
Special Feature
LED Status Indicator + IP20 Cover + Thermal Pad
Mounting Style
Panel Mount
Load Voltage Range
48-530VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
315g
Factory Pack Qty
10
Datasheet
Product Datasheet
Equivalent
Contact Us for Possible Replacement
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Current Transducer, AT-AA9-D-4, AC Current Transducer, Average RMS, 5 Amps, 24VDC Aux, 0-10V output
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type) or 0-10V/0-5V (For Direct Voltage Type)
Each unit needs just 50mm x 120mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
AT-AA8-D-4
Control Output
0-10VÂ Average RMS
Input
0-5 Amp Rms
Over Range
x 1.2
Operating Temperature
0 - 60°C
Load Voltage
24VDC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Crydom HS072 + D2490, Solid State Relay, with Panel Mount Heatsink, 3-32VDC Control, 24-280VAC Output, Rated at 74 Amps
Features
• Ratings from 25A to 125 Amp @ 24-280 VAC
• SCR output for heavy industrial loads
• Zero voltage or instantaneous turn-on outputs
• UL/CSA/VDE Approved, CE Compliant to EN60950-1
• Improved SEMS screw and washer
• Redesigned housing with anti-rotation barriers
• AC & DC control types
• Direct bond copper substrate
• EMC compliant to Level 3
• Direct power lead frame
• Epoxy free design
Spec
Crydom Part Number
HS072 + D2490
Switching Type
Zero Crossing
ROHS
Yes (Details)
Control Voltage
3-32VDC
Load Current @ 40 Deg C
74 Amp (rms)
Surge Capability
1145 Amp (peak)
Special Feature
LED Status Indicator
Mounting Style
Panel Mount
Load Voltage Range
24 - 280VAC
EMC Compliant
Level 3
Termination Style
Screw
Unit Weight
75g
Factory Pack Qty
20
Â
Datasheet
HS072
D2490
Notifications
Please note Changes from Gen 3 to Gen 4 (current) package design here
App Notes
Why Use SSR's?
The inside story
Selecting a SSR
DC Output SSR's
Selecting a Suitable Heatsink
Use of Thermal Interface Material
How to Verify the Proper Heatsink
Effect of Forced Air Cooling
Fuse Protection of SSR's
Overvoltage Protection "P" Option MOV
SSR Reliability Whitepaper
3 Phase Motors and Heating Applications
3 Phase Motor Reversing
How to test a SSR
SSR Precautions
SSR Life Expectancy MTBF
ROHS & Reach Statement
Heatsink
SSR and Heatsink Assemblies
Fastron F18FT-4PL 5A 24VDC + F18F-4Z-C5, 14 Pin Quad Output Relay, From C 4 x 5 Amp C/O, 250VAC/30VDC Load, 24VDC Coil
Features
4 x 5 Amp @ 250VAC or 30VDC
DIN Rail Mount
Changeover Contact
Compatible with Omron MY4IN Series
UL Approved
CE Compliant to IEC 60664
IP67
Suits F18F-4Z-C5 Socket
Specification
Fastron Part Number
F18FT-4PL 5A 24VDC + F18F-4Z-C5
Switching Type
4 x 30VDC/250VAC C/O From C
No of Pins
14
Approvals
UL, CE
Control Voltage
24VDC
Load Current
4 x 5 Amp (rms)
Special Feature
LED Status Indicator
Mounting Style
DIN Rail Mount
Load Voltage Range
0-250VAC, 0-30VDC
Termination Style
PCB or Socket Mount
Unit Weight
38g
Factory Pack Qty
20
Â
Datasheet
Relay Datasheet
Socket Replacement
F18F-4Z-C5
Relay Replacement
F18FT-4PL 5A 24VDC
TCR-M-2-K COOLING Temperature Controller, Analogue Dial, 72x72mm, 230VAC, C/O Relay output, Type K Input, 0-400 Deg C
3-digit display (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated ON/OFF Relay, output, Optional COOLING or time proprtional versions output available
Each unit needs just 75 mm depth panel space
Specification
Fastron Part Number
TCR-M-2-K
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Input
Type K Thermocouple
Control Mode
Cooling ON/OFF Control
Mounting Style
72x72mm Panel Mount
Control Range
0-400 Deg C
Supply Voltage
230VAC
Termination Style
Screw
Sampling Time
50ms
Weight
270g
Factory Pack Qty
1
Â
Datasheet
TCR Datasheet and User Manual
Risbabh EM94-Z-V1-H-D, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 60-300VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display, 60-300VAC/DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 60-300VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
Â
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Â
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DCÂ power supply
Specification
Rishabh Part Number
EM94-Z-V1-H-D
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
60-300VDC
Maximum Measurement Range
60-300VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YESÂ 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
Â
IP54
Â
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Â
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Â
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Â
Crouzet 84873029, 3 Phase Voltage Monitoring Relay With 17.5mm SPDT Contacts, 3 x 208 - 480 V AC MWA, Phase Sequence, Total Failure, Can Replace  84892290, 84873034
RMC2 MWS relays control, on 3-phase networks :
Sequence Detection
Total Phase Failure
Controls its own supply voltage
True RMS measurement
LED status indication
3-phase voltage controllers which monitor :
Non Adjustable
Specification
Crouzet Part Number
84873029 (3 Phase Voltage Monitoring Relay With SPDT Contacts)
Function
Total Phase Failure, Phase Sequence
Nominal Voltage
3 x 208 → 3 x 480 V ∿
Digital Outputs
1 x C/O Relays, 250VAC/DC @ 5 Amp
Min Breaking Current
10mA/5VDC
Timing Range
0.3 → 30s (0, +10%)
Delay on Pickup
500ms
Alarm Delay on Time (max)
200ms
Reset Time
1500ms
Fixed Hysteresis
2% of Un
Maximum Measurement Cycle Time
150ms/True RMS Measurement
Measurement Accuracy
1%
Supply Voltage Range
Same as Measurement 3 x 208 → 3 x 480 V ∿
Termination Style
Screw
Weight
170g
Certification
CE, UL, CSA, GL, ROHS
Factory Pack Qty
1
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Â
Datasheet
Product Datasheet
Fastron Electronics GBMT-4-K-ANNNN, 140x420mm Digital Voltmeter, Panel Mount, Type K Thermocouple Input, 100-240VAC/VDC supply, with IR Remote Control
Adjustable Zero and Span Setting
Adjustable Display Scaling
Remote Control Included
Wall Mount
LED Tile Display
Large 4 Digit 100mm (40 Inch) LED Display
250mS Response Time
PC 94 UL V0
100mm Depth
CE Approved
Specification
Fastron Electronics Part Number
BMT-4-K-ANNNN
Conditioner Output
N/A
Input
Tyep K Thermocouple -200°C to 1360°C
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
140 x 420 mm Wall Mount
Case Material
PC - UL 94 V0
Weight
3.6kg
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Application Notes
Panel Meters Blog Articles
TRENT TGD-1PL C 25-10kA, 1 Pole Miniature Bidirectional DC Circuit Breaker C Curve 25 Amp, 10kA, 250VDC
Miniature DC Circuit Breakers are used for over current (overload and short circuit) protection of installations and devices, and as a disconnector in case of electric shock
Features :
< 50mS Trip Delay Time
1 Pole Disconnect
10kA Short Circuit Rating
Suitable for Isolation
Customised versions available
Type B, C, D Curve available
BidirectionalÂ
Standards :
IEC/EN 60898
IEC/EN/AS60898-1
IP20 (IP40 Installed) IEC 61008
CE,CB,RCM (Pending)
Specification
TRENT Part Number
TGD-1PL C 25-10kA
Functions
1 Pole MCB - C Curve
Nominal Voltage
250VDC @ 50/60Hz
Nominal Current Range
25 Amps RMS
Trip Delay Time
< 50ms
Rated Impulse Voltage
6kV
Operating Temperature
-25 to 40 Deg C
Mechanical Operations
10,000 Ops
Insulation Voltage
690V
Breaking Capacity
10kA
Approvals
CE,CB, RCM (Pending)
Standards
IEC/EN/AS60898-1, IP20 (IP40 Installed) IEC 61008 ;
Weight
350g
Enclosure Material
UL94
Factory Pack Qty
1
TRENT Headquarters
Australia
Â
Datasheet
Product Datasheet
Risbabh EM94-Z-V3-H-D, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 201-1000VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display, 60-300VAC/DC Aux Supply, Internal Logging
2 Pulse/Alarm Outputs
50-150mV Shunt Input, and nominal voltage 201-1000VDC
RS 485 communication up to 57,600 bit/s
USB Port
8MB Internal Storage
DC Measurement Only
Â
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Â
Features :
96 x 96mm Panel Mount
Accuracy class 0.5
Simple Menu
RS 485 communication up to 57,600 bit/s
USB Comms
8MB Internal Logger
60-300VAC/DCÂ power supply
Specification
Rishabh Part Number
EM94-Z-V1-H-D
Functions
kWh Meter, Energy Meter
Supply Voltage
60-300VAC/DC
Nominal Measurement Range
201-1000VDC
Maximum Measurement Range
60-300VDC
Display
Single Line LCD
Pulse/Relay Output
2
Accuracy
Class 0.5 (Energy)
USB
YES
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
RS485 Modbus RTU
YESÂ 57,600bps
Weight
450g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Environment
Â
IP54
Â
Safety
Protection Class II
Enclosure Material
Mablex with fire protection to UL94-V-O. Self extinguishing
EnclosureSize
96 x 96mm x 83.5mm (72mm behind panel)
Â
Terminals
Rising Cage 4mm² (12 AWG) cable max
Humidity
< 75% Non Condensing
Operating Temperature
-20 →+70 °C
Â
Datasheet
Product Datasheet
Software
Software User Manual
Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.
Â