FP120160P G2, 1200/5 Amp Split Core CT, Class 0.5, 10VA Series Clip On Current Transformer
Features
Quick Release Split Core System
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
IEC185, BS 7626, BSEN 60044-1 and IEC 60044-1
Applications
Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Fastron Electronics Part Number
FP120160P G2
Technology
Split Core AC Clip On Current Transformer
Ratio
1200/5
Aperture Size
83 x 163.5mm
VA Rating
10VA
Accuracy Class
Class 0.5
Output
5 Amp AC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10°C / 50°C
Continuous Current (max)
1200Amp x 1.2
Termination Style
Screw
Approvals
CE
Unit Weight
1150g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Installation Guide
Â
FP500160P G2, 5000/5 Amp Split Core CT, Class 1 15VA Series Clip On Current Transformer
Features
Quick Release Split Core System
Built In Sealable Terminal Covers
Mounting Feet Supplied
Self Powered
Rated System Voltage 0.72/3kV
IEC185, BS 7626, BSEN 60044-1 and IEC 60044-1
Applications
Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Fastron Electronics Part Number
FP500160P G2
Technology
Split Core AC Clip On Current Transformer
Ratio
5000/5
Aperture Size
83 x 163.5mm
VA Rating
15VA
Accuracy Class
Class 0.5
Output
5 Amp AC (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount/Busbar Mount
Operating Temperature Range
-10°C / 50°C
Continuous Current (max)
4000Amp x 1.2
Termination Style
Screw
Approvals
CE
Unit Weight
1150g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Installation Guide
Â
TRENT TGD-2PL C 6-10kA, 2 Pole Miniature Bidirectional DC Circuit Breaker C Curve 6 Amp, 10kA, 250VDC
Miniature DC Circuit Breakers are used for over current (overload and short circuit) protection of installations and devices, and as a disconnector in case of electric shock
Features :
< 50mS Trip Delay Time
1 Pole Disconnect
10kA Short Circuit Rating
Suitable for Isolation
Customised versions available
Type C, D Curve available
BidirectionalÂ
Standards :
IEC/EN 60898
IEC/EN/AS60898-1
IP20 (IP40 Installed) IEC 61008
CE,CB,RCM (Pending)
Specification
TRENT Part Number
TGD-2PL C 6-10kA
Functions
1 Pole MCB - C Curve
Nominal Voltage
250VDC @ 50/60Hz
Nominal Current Range
6 Amps RMS
Trip Delay Time
< 50ms
Rated Impulse Voltage
6kV
Operating Temperature
-25 to 40 Deg C
Mechanical Operations
10,000 Ops
Insulation Voltage
690V
Breaking Capacity
10kA
Approvals
CE,CB, RCM (Pending)
Standards
IEC/EN/AS60898-1, IP20 (IP40 Installed) IEC 61008 ;
Weight
350g
Enclosure Material
UL94
Factory Pack Qty
1
TRENT Headquarters
Australia
Â
Datasheet
Product Datasheet
FRS3-C40-500R-T2, 500VDC Surge Protection Device for Photovoltaic Systems, Type 2 (Class II) 40kA WITH REMOTE C/O CONTACTS
Â
Specifications
Trent part number
FRS3-C40-500R-T2
Nominal Voltage
500VDC
No of Poles
3
Category IEC / EN / VDE
Type 2 (Class II)
Location of use
String Box, Inverter, Sub Board Only
Protection modes
(+)-PE,(-)-PE,(+)-(-) PE
Additional Remote Contacts
YES NO/NC/COM
Protective element
MOV
No Fault/Fault Indication
Green Flag / Not Green Flag
Surge discharge rating
Per pole 40kA (8/20uS)9KA) Max, 20kA (8/20uS)9KA)Â Nominal
Internal protection and safety
Thermal disconnector in each MOV
Weight
420g
Standards
IEC614643-31:2018 (TUV, CE Approved)
Â
Datasheet
Product Datasheet
GDT/MOV/TVSÂ Tester
SPD Tester
Advanced Energy Basic Bus & dASM Modules, 8 Channel Communication Interface for Thyro Series SCR Controllers
Note: Basicbus not required For Thyro PX Controllers, only requires Anybus and dASM (for Dynamic Mains load optimised Burst Fire Modes)
​
Optional Connection for up to 8 Power Controllers (32 Optional)
One Address per Module
Access to controller setpoints, actual points, and parameters
Transfer of setpoints as float number in physical units
Control Function of LED's
24VDC 200mA Supply
UL and CE Approved
Thyro S, Thyro A, Thyro AX
Note Requires Anybus Module for dASM Mode(TAKT Control Only)
Communication Options :
Ethernet (Inc Ethern/IP/Profinet/Modbus TCP
Profibus DPV1
Modbus RTU
DeviceNet
Specification
Advanced Energy Part Numbers
2.000.190.002,2.000.190.003
Functions
Access to controller setpoints, actual points, and parametersTransfer of setpoints as float number in physical unitsControl Function of LED's
Supply Voltage
24VDC
Protocols
EthernetIP, Profinet, Modbus TCP ProfibusDPV1, ModbusRTU, DeviceNet (with Suitable Anybus Module)
No. of Communication Ports
Up to 8
Weight
750g
Factory Pack Qty
1
Approvals
CE, UL
Operating Temperature
-20 →+70 °C
Â
Datasheet
Product Datasheet
User Manual
User Guide
Blog for initial communication setup issue
Setting Up Comms on Thyro A Series Controllers
Thyro Touch Software and Touch Display User Guide
Anybus Device Ethernet IP Setup Guide
MC330 S ARNG SUDNNPT, Panel Mount Multifunction Meter, Class 1, 50-500VAC Autorange, 61 Parameter (U, I, P, Q, S, PF, PA, f, ϴ, THD, MD …), 4 Energy Counters, RS485 Comms, Universal 20-300VDC, 48-276VAC Aux, IP54, CT Terminals, Internal Logger
Internal 8MB Logger
Universal AC/DC Power Supply
Automatic range of nominal current up to 12.5 A (Includes 5A/1A CT Input) and nominal voltage up to 500 V L-N
Adjustable tariff clock, display of electric energy consumption in optional currency
Optional RS 232/RS 485 communication up to 115,200 bit/s
RMS values of currents and voltages
Measurements of active, reactive, apparent power and power factor
Harmonic Measurements to the 31st
Measurements of energy in all 4 quadrants Average values of measurands per interval
Â
The meter is intended for measuring, analysing and monitoring single-phase or three-phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power, power factor, phase angles, etc.) from the measured signals.
Â
Features :
Measurement of instantaneous values of more than 60 quantities (U, I, P, Q, S, PF, PA, f, f, MD, etc.).
Accuracy class 1
Internal Logger
Measurement of 20 minimal and maximal values in different time periods
Optional dual tariff inputs and pulse or relay outputs
Wide frequency range from 16 Hz to 400 Hz
RS 232/RS 485 communication up to 115,200 bit/s or Ethernet communication
MODBUS communication protocol
Up to 4 inputs or outputs (pulse outputs, alarm outputs, tariff inputs)
Universal or AC power supply
Graphic LCD 128 x 64 dots with illumination
Automatic range of nominal current up to 5 A and nominal voltage up to 600 V
Multilingual support
User-friendly PC MiQen software
Specification
Iskra Doo Part Number
MC330 S ARNG SUDNNPT
Functions
Power Quality Meter, Energy Meter
Supply Voltage
Universal 20-300VDC, 48-276VAC < 5VA
Nominal Measurement Range
500V L-N, 5 Amp
Maximum Measurement Range
600V L-N, 12.5 Amp
Alarm
N/A
Tariff Input
N/A (Optional 4 x )
Accuracy
Class 1 (I,U,F,PF,θ,THD) Class 2(Active), Class 2 (Reactive)
Battery Backup
N/A
Real Time Clock
1min/month (30ppm)
Isolation
3.5kV
Internal Logger
Yes (8MB)
RS485
2400-115200 b/s
Weight
500g
Certification
UL, CSA, ROHS
Factory Pack Qty
1
EU Directives
Degree on electrical equipment designed for use within certain voltage limits URLRS 53/00 (Directive 73/23/EEC on low voltage): SIST EN 61010-1:2002
Safety Requirement for electrical equipment for measurement, control and laboratory use, part1 : general requirement
Decree on electromagnetic Compatibility (EMC) URLRS 61/00 (Directive 89/336/EEC on electromagnetic compatibility): SIST EN 61036 item 4.5: 1998 Meters for active energy (class 1 and 2)
Safety
Protection Class II
600V rms, installation category II
300V rms, installation category III
Pollution Degree 2 in compliance with SIST EN 61010-1:2002
Enclosure Material
PC/ABS non combustable-self-extinguishability, complying with UL 94 V-0
Enclosure Protection
IP52 (IP00 for terminals) in compliance with SIST EN 60529:1997
Â
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C
Â
Datasheet
Product Datasheet
User Manual
Iskra Doo MS32-4, Motor Protection Switch, 3 Phase, 690VAC, 2.5 - 4 Amp Setting Range, Thermal & Magnetic Release
Motor Protection Circuit Breakers are a special type of circuit breaker designed for protection of a wide range of single and 3 phase AC motors against overload and short circuit. Used in industry, small machines, agricultural machines, compressors etc.
Features :
Thermal & Magnetic release
< 50mS Trip Delay Time
3 Pole Disconnect
Short Circuit Breaking Capacity up to 4kA
Voltage resettable version available
Customised versions available
Standards :
IEC/EN 60898,60947-3
IP20 (IP40 Installed) IEC 61008
AS/NZ 61009-1
Specification
Iskra Doo Part Number
MST-25-4
Functions
3 Phase Motor Protection Switch
Nominal Voltage
230/400VAC @ 50/60Hz
Nominal Current Range
2.5 - 4 Amp RMS
Trip Delay Time
< 50ms
Rated Frequency
50/60 Hz
Operating Temperature
-25 to 60 Deg C
Rated Operations
100,000 Ops
Insulation Voltage
690V
Overload Protection
Thermal Release Only
Breaking Capacity
230V(6kA) 415V(4kA) 500V(2.5kA) 690V(2kA)
Approvals
CSA, EAC
Standards
IEC/EN 60947-2/4-1/5-1, IP20 (IP40 Installed) IEC 61008 ; AS/NZ 61009-1
Weight
230g
Enclosure Material
UL94
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Alternatives
Trent FGV2 SeriesÂ
Â
Fast ONE AHF 50A-400V-4W-R, Rack Mounted Active Harmonic Filter & Static Var Generator, 35Kvar/50 Amp, 3 Phase 4 Wire, 400V-4Wire +/-20%
For Automatic Switching of Power Factor Correction Capacitors according to changing site conditions. and for the filtering or control of Harmonic Distortion
Features
Automatic Power Factor Correction up to Cos φ = 0.99
Overtemperature Alarm
Optional RS485 Comms
IEC 654-1, UL Approved
3 Year Fastron Electronics Warranty
Modular Construction for Rack or Wall Mount Installtions
Perfect for Residential Applications
Stack multiple modules for larger Power Factor Correction Requirements
Â
Specification
Fastron Part Number
Fast ONE AHF 50A-400V-4W-R
Function
Reactive Power Correction & Rack Mounted Active Harmonic Filter
Rating
50 Amp @ 50 Deg C /35Kvar
Nominal Voltage (Un)
400V-4Wire Line to Line 50Hz
Switch Delay Time
Instant Correction/Inverter Based
Desired Harmonic
0.99 IND - 0.99 CAP
LCD Display Accuracy
IGBT Temp, Grid Current Grid THDi, Grid PF, Grid Imbalance
Current imbalance
<Â 5%Â
Comms
RS485 (Optional)
Mounting Style
Rack Mount
Termination Style
Screw
Dimensions
486x183x550mm
Weight
40kg
Certification
EN 61000-6-4:2007+A1:2011
EN 61000-6-2:2005
EN 61000-3-2:2014
EN 61000-3-3:2013+A1:2019
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0, & Stainless Steel Painted RAL 1013
Enclosure protection
IP21
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...55 °C
Datasheet
User Manual
Datasheet
Fastron Electronics LZZBJ6-12/185h/2 100/1A 5P20 10VA 6.6kV, HV Protection Class Current Transformer
Features
Panel Mount
1Â Amp Output
Self Powered
Rated System Voltage 6.6kV
Applications
Indoor Substations
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Fastron Part Number
LZZBJ6-12/185h/2 100/1A 5P20 10VA 6.6kV
Technology
HV AC Current Transformer
Ratio
100/1 Amp
Aperture Size
N/A
VA Rating
10VA
Accuracy Class
Class 5P20
Output
1Â Amp (+20%)
Isolation
28kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
100Amp x 1.2
Termination Style
M12 Inserts
Unit Weight
28kg
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Application Notes
Types of Current Transformers - Blog
Cable Losses and CT's
High Accuracy or High Burden Requirements for CT's
Fastron Electronics LZZBJ6-12/185h/2 500/1A 5P20 10VA 6.6kV, HV Protection Class Current Transformer
Features
Panel Mount
1Â Amp Output
Self Powered
Rated System Voltage 6.6kV
Applications
Indoor Substations
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Fastron Part Number
LZZBJ6-12/185h/2 500/1A 5P20 10VA 6.6kV
Technology
HV AC Current Transformer
Ratio
500/1 Amp
Aperture Size
N/A
VA Rating
10VA
Accuracy Class
Class 5P20
Output
1Â Amp (+20%)
Isolation
28kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Panel Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
500Amp x 1.2
Termination Style
M12 Inserts
Unit Weight
28kg
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Application Notes
Types of Current Transformers - Blog
Cable Losses and CT's
High Accuracy or High Burden Requirements for CT's