TPR-3SL040H-F, SCR Phase/Burst Controller Fan Cooled, 400VAC 3 Wire (400V L-L, 230V L-N), 3 Phase, 1-5V/4-20/0-20mA/POT Input, with In built Fuses, 32 Amps per Phase @ 50 Deg C
Features
Phase Angle, Distributed Burst, and Time Proportional Burst Control Functions
3 Phase, or Single Phase, Angle/Burst Controller
4-20mA/1-5V/10K POT Input Proportional Control
Fully enclosed IP20
Phase Angle or Burst switching
Aluminium/Plastic Frame
Removable Cover
Applications
Electrical Ovens, Kilns, or Furnaces
HVAC Heaters
Controlled Power Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for HVAC or Industrial Environments
Specification
Fastron Part Number
TPR-3SL040H-F
Rated Operating Temperature
50°C
SCR Configuration
3 Phase AC Switch
Control Voltage
4-20mA (Default), 1-5V, 10K POT)
Load Current
32 Amps Per Phase @ 50 Deg C
Derating
2% per 1 Deg C (approx)
Control Range
0-100%
Alarms
2 x NO Relay Contact
Comms
Optional RS485 Modbus RTU
Special Feature
Internal Fuse
Mounting Style
Panel Mount
Switching Voltage Range
400VAC +/-10%
Supply Voltage
100-240VAC +/-10%
Delay on Start
NA
Soft Start
Programmable from 0 to 60 seconds
Termination Style
Screw
Unit Weight
4kg (6kg Packed)
Factory Pack Qty
1
Technical Docs
User Manual
TPR-3SL055H-F, SCR Phase/Burst Controller Fan Cooled, 400VAC 3 Wire (400V L-L, 230V L-N), 3 Phase, 1-5V/4-20/0-20mA/POT Input, with In built Fuses, 44 Amps per Phase @ 50 Deg C
Features
Phase Angle, Distributed Burst, and Time Proportional Burst Control Functions
3 Phase, or Single Phase, Angle/Burst Controller
4-20mA/1-5V/10K POT Input Proportional Control
Fully enclosed IP20
Phase Angle or Burst switching
Aluminium/Plastic Frame
Removable Cover
Applications
Electrical Ovens, Kilns, or Furnaces
HVAC Heaters
Controlled Power Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for HVAC or Industrial Environments
Specification
Fastron Part Number
TPR-3SL055H-F
Rated Operating Temperature
50°C
SCR Configuration
3 Phase AC Switch
Control Voltage
4-20mA (Default), 1-5V, 10K POT)
Load Current
44 Amps Per Phase @ 50 Deg C
Derating
2% per 1 Deg C (approx)
Control Range
0-100%
Alarms
2 x NO Relay Contact
Comms
Optional RS485 Modbus RTU
Special Feature
Internal Fuse
Mounting Style
Panel Mount
Switching Voltage Range
400VAC +/-10%
Supply Voltage
100-240VAC +/-10%
Delay on Start
NA
Soft Start
Programmable from 0 to 60 seconds
Termination Style
Screw
Unit Weight
4kg (6kg Packed)
Factory Pack Qty
1
Technical Docs
User Manual
Fastron DTC1-R/M1, DIN Rail Mount Temperature/Humidity Controller, Multirange Input, 24VAC/DC, Relay output
Optional converter function
2 Input 1 Output, and 1 Input Two Output Versions available
Optional 60 Segment Multi Pattern Program Control feature
4-digit display. Suit most industries including Temperature, Humidity, Pressure (0.5s response)
CE Approved
Each unit needs just 22.5mm width Din Rail space
EC Compliant (Details)
Various specials available for unique applications.
Specification
Fastron Part Number
DTC1-R/M1
Control Output
Relay 3A(Resistive), 1A(Inductive load cos ??=0.4), 240VAC/30VDC
Input
Multirange K/J/R/S/B/E/T/Linear Voltage Current(Optional)/N/W1/W2/Pt100
Alarm
Relay 3A(Resistive), 1A(Inductive load cos ??=0.4), 240VAC/30VDC
Options
None
Mounting Style
22.5 x 75mm Din Rail Mount
Supply Voltage
24VAC/DC
Termination Style
Screw
Weight
230g
Factory Pack Qty
1
CE
Yes
??
Selection Chart
PWM Control Wiring
Datasheet
DTC1 Brochure
DTC1User Manual
DTC1 User Manual Comms versions
Alarm Table
DTC1 (Program Control Version) User Manual
Fastron FY3 Series, Phase/Burst Controller for Primary Control of Transformer (Phase angle mode only), Voltage/Current/Power Limit Modes, For 3 Wire or 4 Wire Loads, 400VAC, 50 Amps per Phase @ 50 Deg C, Modbus RTU
Features
Phase Angle, Distributed Burst, and Time Proportional Burst Control Functions
Made in China, Low cost
3 Phase, or Single Phase, Angle/Burst Controller
4-20mA/0-10V/1-5V input Proportional Control
Fully enclosed IP20
Phase Angle or Burst switching
Aluminium Frame
Removable Cover
Modbus RTU
Applications
Electrical Ovens, Kilns, or Furnaces
HVAC Heaters
Controlled Power Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for HVAC or Industrial Environments
Specification
Fastron Part Number
FY3 Series
Rated Operating Temperature
50°C
SCR Configuration
3 Phase AC Switch
Control Voltage
4-20mA/0-10V/0-5V
Load Current
50-500 Amps Per Phase @ 50 Deg C
Derating
2% per 1 Deg C (approx)
Control Range
0-100%
Alarms
1 x NO Relay Contacts
Special Feature
Internal Fuse, Current Limit, Power Limit
Comms
Modbus RTU
Mounting Style
Panel Mount
Switching Voltage Range
400VAC +/-10%
Supply Voltage
230VAC +/-10%
Soft Start
N/A
Termination Style
Screw
Unit Weight
4kg (6kg Packed)
Factory Pack Qty
1
Technical Docs
Brochure
User Guide
Modbus Protocol Guide
Modbus Register Map
Video for How to Set Current/Voltage/Power limit
F115-4-90A, Panel Mount Single Phase Solid State Contactor, 70-480VAC, 90 Amp Switching, 90-280VAC or 4-32VDC Control Contactor Style Modules
Ratings from 50A to 350 Amp @ 70-533 VAC
Thermal Overload Detection (via Bimetal Thermal Switch)
SCR output for heavy industrial loads
Zero voltage or instantaneous turn-on outputs
UL/CE/ROHS Compliant
Direct bond copper substrate
Direct power lead frame
Epoxy free design
Optional Fuses(Loose), Varistors(mounted) or 240VAC Snubber(mounted)
Specification
Part Number
F115-4-90A
Switching Type
Zero Crossing
ROHS/CE/UL
Yes
Control Voltage
90-280VAC
Load Current
90 Amp (rms) @ 50 Deg C
Special Feature
N/A
Mounting Style
Panel Mount
Load Voltage Range
70-480VAC
Max Non Repetitive Peak Voltage
600 Vp
Termination Style
Screw Terminals
Factory Pack Qty
1
Dimensions and Fuse Kits
Part Number
Approximate Dimensions
Panel Mount Fuse Kit
DIN Rail Mount Fuse Kit
DR2260D35U
L:90 x W:22.5 x D:116mm
30-40 Amp 660VAC Fuse Kit
Trent 40 Amp Cartridge Fuse
F115-4-50A(D)
L:110 x W:125 x D:185mm (Figure 2)
50-75 Amp 660VAC Fuse Kit
Trent 63 Amp Cartridge Fuse
F115-4-90A(D)
L:155 x W:125 x D:185mm (Figure 2)
80-125 Amp 660VAC Fuse Kit
Trent 125 Amp Cartridge Fuse
F115-4-120A(D)
L:210x W:125 x D:195mm (Figure 3)
80-125 Amp 660VAC Fuse Kit
N/A
F115-4-220A(D)
L:155 x W:125 x D:195mm (Figure 4)
160-200 Amp 660VAC Fuse Kit
N/A
F115-4-250A(D)
L:255 x W:125 x D:195mm (Figure 4A)
200-250 Amp 660VAC Fuse Kit
N/A
Datasheet
F115_135 Series Datasheet
Infineon TT61N12KOF-K Dual Thyristor Module
Features
Pressure Contact Technology
Optimised for Deep Cycling
Electrically insulated base plate
Very low forward voltage drop
Very low leakage current
3600V Isolation
Industrial standard package
20mm Base Width
Applications
Power Supplies
Rectifier for drives applications
Uncontrolled Rectifiers
Rectifiers for UPS
Battery Chargers
For single and three phase bridge configurations
Field supply for DC motors
Center Tapped Transformers
Specification
Infineon Part Number
TT61N12KOF-K
Vrrm
1200V
Diode Configuration
Common Cathode Dual Thyristor Module
IF(av) @ 85 Deg C
61 Amp
Package Size
TO-240AA W:20mm L:93mm D:30mm
Itsm
1.55 kA
VF(to)
0.8V
Tj(max)
130°C
rF
3.4mΩ
Terminals
M5 Screw
Hole Centres
80mm (M6)
Gate Trigger Current
120mA
R th(j-c)
0.52°C/W
R th(c-h)
0.16°C/W
Weight
160g
Mounting Torque
4 Nm (4 Nm Terminals)
Factory Pack Qty
10
Certification
UL Listed, ROHS
Infineon Headquarters
Germany
Datasheet
Product Datasheet
Alternatives
See VSKC91/16 for Vishay Solder Bonded replacement. See TT104N14KOF-K for Infineon Pressure Contact Alternative
KW62B-With Plate, 130mm long water cooler block (Chiller) for Isolated Modules including IGBT & Diodes and SCR's
M7 Holes for Mounting to Plate.
Replacement to Semikron SKIW900/16
1000 Amp RMS Output using TT500N16KOF
1100 Amp RMS Output using MCC552-16
Copper with copper Binded inlet and outlet, sealed
Pressure Tested to 300 mbar
Nickel plated copper solid construction with aluminium mounting plate
Thermal Rating based on 25 Deg C max inlet water temperature.
Type No
Litres/min
Device
Rcw deg C/W
mbar
kg
KW62B
2
50 x 92
0.055
50
1.2
4
50 x 92
0.042
190
Datasheet
Product Datasheet
RCS-2400-3000 Three-Phase Flexible Current Sensor System(Rogowski Coils):
The RCS-2400 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-2400 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Specification
Magnelab Part Number
RCS-2400-3000
Function
AC Current Measurement
Nominal Measurement Current (Ipn)
3000 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 3000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
8 Inch
Coil Circumference
24 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
Fastron Electronics Fast ONE SVG 35kvar-400V-4W-R, 35kVar Static Var Generator(SVG)/Inverter for Reactive Power Correction and Compensation, Rack Mounted
For Automatic Switching of Power Factor Correction Capacitors according to changing site conditions.
Features
Automatic Power Factor Correction up to Cos φ = 0.99
Overtemperature Alarm
Optional RS485 Comms
IEC 654-1, UL Approved
3 Year Fastron Electronics Warranty
Modular Construction for Rack or Wall Mount Installtions
Perfect for Residential Applications
Stack multiple modules for larger Power Factor Correction Requirements
Specification
Fastron Part Number
Fast ONE SVG 35kvar-400V-4W-R
Mounting
Rack Mounted
Function
Reactive Power Correction
Configuration
4 Wire
Nominal Voltage (Un)
400VAC Line to Line 50Hz
Switch Delay Time
Instant Correction/Inverter Based
Desired Power Factor
0.99 IND - 0.99 CAP
LCD Display Accuracy
Voltage +/-0.5%, Frequency +/-0.1%, Power +/-1% Energy Class 1
Phase Angle Error
+/- 1% at I > 3% of range
Comms
RS485 (Optional)
Termination Style
Screw
Dimensions
486x183x550mm
Weight
45kg
Certification
EN 61000-6-4:2007+A1:2011
EN 61000-6-2:2005
EN 61000-3-2:2014
EN 61000-3-3:2013+A1:2019
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0, & Stainless Steel Painted RAL 1013
Enclosure protection
IP21
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...55 °C
Datasheet
User Manual
Datasheet
Fastron FTCK-6-400-XX-420-0-300-KNE, Type K Thermocouple MIMS Class A, 400mm Probe Length, 6mm Shaft Diameter w/ LARGE Terminal Head, -20 to 500 Deg C, KNE(wire entry:M20x1.5, probe entry: G1/2'')
Type K MIMS Thermocouple
Class A Accuracy
Powder Coated Die Cast Alloy Terminal Head
Low Long Term Drift
Rated for -20 to 500 Deg C Max
Spring Cable Connection
3 or 6mm or Custom
304 SS Sheath
Recommended to use BSP Fitting , or Flange for mounting
Specification
Fastron Part Number
FTCK-6-400-XX-420-0-300-KNE
Sensor Type
Type K Thermocouple
No of Wires
2
Probe Length
Various
Sheath Thickness
6mm
Sheath Material
SS 304 Stainless Steel
Accuracy
Class A
Approvals
CE, ANSI, ROHS
Cable length
Large Terminal Head (105 x 70mm), M20x1.5, probe entry: G1/2''
Terminal Head Type
Large Powder Coated Die Cast Alloy (Weather Proof), Cable Entry, M20 x1.5, Probe Entry: G1/2''
Temperature Range
-20 to 500 Deg C
Special Feature
Large Terminal Head
Mounting Style
BSP Bayonet or Flange Fitting Recommended
Weight
470-700g
Factory Pack Qty
1
Datasheet
Datasheet
Fastron Electronics FGP1-D2510-24VDC, AC Contactor, 240VAC Control Voltage, 4 Pole 4 x NO, Nominal Current = 25 Amps(AC-3) @ 240/400/500/690V
Contactors are designed to meet the requirements of heavy Duty applications. Contactors may be fitted with auxiliary contacts. Peak current is limited to the value within the contactor making capacity.
Features :
High contact reliability at low voltages
High electrical and mechanical endurance and high switching capacity
Four and Three-pole contactors
Optional auxiliary contacts
Ratings from 6 Amp to 1000 Amp
CE, CB Approved
Advantages :
Saves costs of expensive replacement
Long electrical life
Reduces watt losses during “ON” condition, saves energy
High safety
No risk of dangerous voltage
Less maintenance and downtime
Standard control voltages: 24 V 50/60 Hz, 240 V 50/60 Hz, 415 V 50/60 Hz
Specification
Fastron Electronics Part Number
FGP1-D2510-24VDC
Functions
3 Pole NO + 1NO Contactor
Nominal Voltage
230/400/500/690VAC @ 50/60Hz
Current Carrying Capacity as per UL
25 Amp Continuous @ 55 Deg C
Overload Capability
304(10s), 320(5s), 350(1s), 900(0.001s)
Main Contacts
3 x NO
Auxiliary Contacts
1 x NO
Trip Delay Time
2-10ms
Electrical Life
200,000 Ops
Operating Temperature
-25 to 55 Deg C
Mechanical Operations
10.000,000 Ops
Control Voltage
24VDC
Power Dissipation
4.6W
Approvals
CE, CB, TUV, LVD
Standards
IEC/EN 60947-4-1, AS/NZ 61009-1
Weight
200g
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet