Fast ONE AHF 100A-400V-4W-R, Rack Mounted Active Harmonic Filter & Static Var Generator, 70Kvar/100 Amp, 3 Phase 4 Wire, 400V-4Wire +/-20%
For Automatic Switching of Power Factor Correction Capacitors according to changing site conditions. and for the filtering or control of Harmonic Distortion
Features
Automatic Power Factor Correction up to Cos φ = 0.99
Overtemperature Alarm
Optional RS485 Comms
IEC 654-1, UL Approved
3 Year Fastron Electronics Warranty
Modular Construction for Rack or Wall Mount Installations
Perfect for Residential Applications
Stack multiple modules for larger Power Factor Correction Requirements
Â
Specification
Fastron Part Number
Fast ONE AHF 100A-400V-4W-R
Function
Reactive Power Correction & Rack Mounted Active Harmonic Filter
Current /Load Rating
100 Amp per Phase /70Kvar
Nominal Voltage (Un)
400V-4Wire Line to Line 50Hz
Switch Delay Time
Instant Correction/Inverter Based
Desired Harmonic
0.99 IND - 0.99 CAP
LCD Display Accuracy
IGBT Temp, Grid Current Grid THDi, Grid PF, Grid Imbalance
Current imbalance
<Â 5%Â
Comms
RS485 (Optional)
Mounting Style
Rack Mount
Termination Style
Screw
Dimensions
486x220x610mm
Weight
60kg
Certification
EN 61000-6-4:2007+A1:2011
EN 61000-6-2:2005
EN 61000-3-2:2014
EN 61000-3-3:2013+A1:2019
Factory Pack Qty
1
Material of housing
PC/ABS Unflammable, according to UL 94 V-0, & Stainless Steel Painted RAL 1013
Enclosure protection
IP21
Safety
According to EN 61 010-1, installation category III Pollution degree 2
Operating Temperature
-20...55 °C
Datasheet
Datasheet
User Manual
Fastron Electronics GTD-D-C-SP03, 0-300VDC Voltage Transducer/Transmitter, 22-60VAC/DC aux, 4-20mA output
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
GTD-D-C-SP03
Control Output
4-20mA
Input
0 - 300VDC
Over Range
x 1.5
Operating Temperature
0 - 60°C
Load Voltage
22 - 60VDC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Fastron FTM1-A80-V2-W0, Single Phase, Phase Angle/Burst Controller for Primary Control of Transformer (Phase Angle mode only), Voltage/Current/Power Limit Modes, For Single Phase Loads, 230VAC, 64 Amps @ 50 Deg C, Modbus RTU
Features
Phase Angle, Distributed Burst, and Time Proportional Burst Control Functions
Made in China, Low cost
Single Phase, Angle/Burst Controller
4-20mA/0-10V/0-5V input Proportional Control
Phase Angle or Burst switching
Digital Display and Controls
Modbus RTU
Applications
Electrical Ovens, Kilns, or Furnaces
HVAC Heaters
Controlled Power Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for HVAC or Industrial Environments
Â
Specification
Fastron Part Number
FTM1-A80-V2-W0
Rated Operating Temperature
50°C
SCR Configuration
3 Phase AC Switch
Control Voltage
4-20mA/0-10V/0-5V/POT
Load CurrentÂ
64 Amps Per Phase @ 50 Deg CÂ
Derating
2% per 1 Deg C (approx)
Control Range
0-100%
Alarms
1 x NO Relay Contacts
Special Feature
Internal Fuse, Current Limit, Power Limit
Comms
Modbus RTU
Mounting Style
Panel Mount
Switching Voltage Range
230VAC +/-10%
Supply Voltage
230VAC +/-10%
Dimensions
H:260mm W:94mm D:187mm
Soft Start
N/A
Termination Style
Screw
Unit Weight
2.5kg (4kg Packed)
Factory Pack Qty
1
Â
Technical Docs
User Manual
Brochure
Video for How to Set Current/Voltage/Power limit
LEM PCM 30-P Series Closed Loop Bipolar DC Hall Effect Sensor for Point System Monitoring, Bipolar 4-20mA Output
Features
Closed loop sensor using Hall Effect
Panel mounting
Split core design for easy installation
Insulated plastic case to UL 94-V0 Water resistant design rated to IP 67
Reverse polarity protected
Advantages
Very good linearity
Excellent accuracy
Current overload capability
No insertion losses.
Non - contact measurement (does not need a safety case)
Applications
Railway equipment
Points condition monitoring
Signal light indication
Battery supplied applications Uninterruptable Power Supplies (UPS).
Specification
LEM Part Number
PCM 30-P
Technology
Closed Loop Hall Effect
ROHS
Yes
Supply Voltage
24V
Aperture
ø15.6mm
Load Current (RMS + DC)
30 Amp
Measuring Range
+/- 60 Amp
Overload Capacity (Ampere Turns)
30000 Amp
Output
4-20mA
Standards
EN 50121-59EMC),EN 50155(temperature and humidity),EN61010-1/2 (safety)
Bandwidth
DC-1000Hz
Mounting Style
Panel Mount
Operating Temperature Range
-25°C / 70°C (55°C Continuous)
Accuracy
0.5%
Termination Style
Switchcraft EN3L4M connector
Unit Weight
120g
Factory Pack Qty
4
Â
Datasheet
Product Datasheet
Application Notes
FAQ
Fastron Electronics FAT100D420T, AC Current Transducer, 100Amp Measurement, 24mm Split Core, 4-20mA Average RMS Output, Accuracy = 1%
Features
Quick Release 24mm Split Core System
Cale Mount
4-20mA Output
24VDc Aux
Rated System Voltage 0.60/2.5kV
0.5M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Â
Specification
Fastron Part Number
FAT100D420T
Technology
24mm Split Core AC Current Transformer
Ratio
100/4-20mA
Aperture Size
ø 24 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
4-20mA (+20%)
Isolation
2.5kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
100Amp x 1.2
Termination Style
0.5M Flying leads
Unit Weight
300g
Factory Pack Qty
9
Â
Datasheet
Product Datasheet
Application Notes
Installation Guide
Fastron FTM1-A200-V4-W0, Single Phase, Phase Angle/Burst Controller for Primary Control of Transformer (Phase Angle mode only), Voltage/Current/Power Limit Modes, For Single Phase Loads, 400VAC, 160 Amps @ 50 Deg C, Modbus RTU
Features
Phase Angle, Distributed Burst, and Time Proportional Burst Control Functions
Made in China, Low cost
Single Phase, Angle/Burst Controller
4-20mA/0-10V/0-5V input Proportional Control
Phase Angle or Burst switching
Digital Display and Controls
Modbus RTU
Applications
Electrical Ovens, Kilns, or Furnaces
HVAC Heaters
Controlled Power Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for HVAC or Industrial Environments
Â
Specification
Fastron Part Number
FTM1-A200-V4-W0
Rated Operating Temperature
50°C
SCR Configuration
3 Phase AC Switch
Control Voltage
4-20mA/0-10V/0-5V/POT
Load CurrentÂ
160 Amps Per Phase @ 50 Deg CÂ
Derating
2% per 1 Deg C (approx)
Control Range
0-100%
Alarms
1 x NO Relay Contacts
Special Feature
Internal Fuse, Current Limit, Power Limit
Comms
Modbus RTU
Mounting Style
Panel Mount
Switching Voltage Range
400VAC +/-10%
Supply Voltage
230VAC +/-10%
Dimensions
H:260mm W:94mm D:187mm
Soft Start
N/A
Termination Style
Screw
Unit Weight
2.5kg (4kg Packed)
Factory Pack Qty
1
Â
Technical Docs
User Manual
Brochure
Video for How to Set Current/Voltage/Power limit
Advanced Energy Thyro-A-2A-400-45-H3, Thyro-A-2A-Series 2 Leg 3 Phase SCR Controller 45Amp 400VAC +10/-57% Burst(TAKT) Fire Mode, Economical Firing Mode, Voltage Control only
Features
400VAC +10/-57% Line to Line Voltage, Current or Power Control
Smallest footprint on the market
Built in Fuses
3 Phase, 2 Leg Economical Burst Controller Firing Mode
(0)4-20mA, 0(1)-5V, 0(2)-10V or POT input Proportional Control
Removable Cover
USB Configuration/Bias Setting
Potentiometer Adjustment
Synchronisation Function
Applications
Electrical Ovens, Kilns, or Furnaces
Primary Control of Transformer Loads in Phase or Burst Fire mode
Resistive Loads up to 6:1 Hot/Cold Ratio
AC Soft Starter (Combined with PLC)
Power Regulation Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for extreme environments such as mining
Series Optional Features
For HRL
Current Control/Feedback
Programmable Relay Alarm Output
Load Monitoring
Analogue Output
For HRLP
As above with Power Control Feedback
Communication Options
Standard Thyro Bus Module
BasicBus Module
Â
Specification
Advanced Energy Part Number
Thyro-A-2A-400-45-H3
Approvals
CE, UL508A, EU Directive 2014/35/EU & 2004/108/EC
Control Accuracy
3% at rated voltage
Rated Operating Temperature
45°C
Temperature Derating
0.9 x Inom @ 50 Deg C, 1.1 x Inom @ 35 Deg C
SCR Configuration
Single Phase AC Switch
Control Modes
2 Leg Burst(TAKT) for low dissipation
Control Input
4(0)-20mA, 0(1)-5V, 0(2)-10V, POT
Load Current
16 to 1500 Amp @ 45 Deg C (110% @ 35 Deg C Max)
Control Range
0-100%
Options
Conformal Coating for Gas or High Humidity Environments
Mounting Style
Panel Mount
Supply Voltage Range
400VAC +10/-57% (-57% with 24VDC Aux Supply)
Soft Start
Via PLC input
Termination Style
Screw
Unit Weight
2.1 to 74kg
Factory Pack Qty
1
Â
Technical Docs
Brochure
User Manual
2 Leg Control Application Blog
Thyro A Series Quick Installation Guide
Setting Up Comms on Thyro A Series Controllers
Anybus Device Ethernet IP Setup Guide
TCR-M-2-K COOLING Temperature Controller, Analogue Dial, 72x72mm, 230VAC, C/O Relay output, Type K Input, 0-400 Deg C
3-digit display (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated ON/OFF Relay, output, Optional COOLING or time proprtional versions output available
Each unit needs just 75 mm depth panel space
Specification
Fastron Part Number
TCR-M-2-K
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Input
Type K Thermocouple
Control Mode
Cooling ON/OFF Control
Mounting Style
72x72mm Panel Mount
Control Range
0-400 Deg C
Supply Voltage
230VAC
Termination Style
Screw
Sampling Time
50ms
Weight
270g
Factory Pack Qty
1
Â
Datasheet
TCR Datasheet and User Manual
Fastron FTM1-A80-V4-W0, Single Phase, Phase Angle/Burst Controller for Primary Control of Transformer (Phase Angle mode only), Voltage/Current/Power Limit Modes, For Single Phase Loads, 400VAC, 64 Amps @ 50 Deg C
Features
Phase Angle, Distributed Burst, and Time Proportional Burst Control Functions
Made in China, Low cost
Single Phase, Angle/Burst Controller
4-20mA/0-10V/0-5V input Proportional Control
Phase Angle or Burst switching
Digital Display and Controls
Applications
Electrical Ovens, Kilns, or Furnaces
HVAC Heaters
Controlled Power Applications
Electric Boilers
Brewery Heating
Industrial Light Dimming
Suitable for HVAC or Industrial Environments
Â
Specification
Fastron Part Number
FTM1-A80-V4-W0
Rated Operating Temperature
50°C
SCR Configuration
3 Phase AC Switch
Control Voltage
4-20mA/0-10V/0-5V/POT
Load CurrentÂ
64 Amps Per Phase @ 50 Deg CÂ
Derating
2% per 1 Deg C (approx)
Control Range
0-100%
Alarms
1 x NO Relay Contacts
Special Feature
Internal Fuse, Current Limit, Power Limit
Comms
N/A Optional
Mounting Style
Panel Mount
Switching Voltage Range
400VAC +/-10%
Supply Voltage
230VAC +/-10%
Dimensions
H:260mm W:94mm D:187mm
Soft Start
N/A
Termination Style
Screw
Unit Weight
2.5kg (4kg Packed)
Factory Pack Qty
1
Â
Technical Docs
User Manual
Brochure
Video for How to Set Current/Voltage/Power limit
LEM PCM 20-P Series Closed Loop Bipolar DC Hall Effect Sensor for Point System Monitoring, Bipolar 4-20mA Output
Features
Closed loop sensor using Hall Effect
Panel mounting
Split core design for easy installation
Insulated plastic case to UL 94-V0 Water resistant design rated to IP 67
Reverse polarity protected
Advantages
Very good linearity
Excellent accuracy
Current overload capability
No insertion losses.
Non - contact measurement (does not need a safety case)
Applications
Railway equipment
Points condition monitoring
Signal light indication
Battery supplied applications Uninterruptable Power Supplies (UPS).
Specification
LEM Part Number
PCM 20-P
Technology
Closed Loop Hall Effect
ROHS
Yes
Supply Voltage
24V
Aperture
ø15.6mm
Load Current (RMS + DC)
20 Amp
Measuring Range
+/- 40 Amp
Overload Capacity (Ampere Turns)
30000 Amp
Output
4-20mA
Standards
EN 50121-59EMC),EN 50155(temperature and humidity),EN61010-1/2 (safety)
Bandwidth
DC-1000Hz
Mounting Style
Panel Mount
Operating Temperature Range
-25°C / 70°C (55°C Continuous)
Accuracy
0.5%
Termination Style
Switchcraft EN3L4M connector
Unit Weight
120g
Factory Pack Qty
4
Â
Datasheet
Product Datasheet
Application Notes
FAQ
Furison FTC002-A7B(RTC), PID Temperature Controller for HVAC, 71x29mm Cutout, 100-240VAC, 2 x Relay Outputs, Includes 4 x NTC or PT1000 Sensor Inputs
3-digit display suit refrigeration temperatures to 1 Degree
Drip-proof / Dust-proof IP64 (front panel only)
Each unit needs just 71 x 29mm panel space
3 minute delay protection
Automatic 15 minutes ON, 30 minutes OFF on sensor failure
Overtemperature Alarm including 10 Amp Relay, Buzzer and LED Blinking
Ultra High temperature 99 - 120 Deg C Displays "HH"
Specification
Furison Part Number
FTC002-A7B(RTC)
Control Output
1 x SPST Relay 10A 250VAC (Compressor), 1 x SPST 8A 250VAC (Aux Relay)
Input
4 x NTC or PT1000 Probe
Cooling/Cooling Outputs
2 x 230VAC 10 Amp Relay Contact
Mounting Style
75 x 34.5mm Panel Mount
Supply Voltage
100-240VAC
Termination Style
Screw
Weight
150g
Factory Pack Qty
1
Certifications
UL, CE
Â
Datasheet
Download Datasheet