LEM ART-B22-D300-SP4 + AI-PMUL, Single Phase Rogowski Coil Set, Class 1, User Selectable 0.333v, 0.166v, True RMS 4-20mA, 0-20mA, 0-10V, 0-5V Outputs, Sensitivity, and Measurement Range, 30cm Diameter
The universal Rogowski coil integrator AI-PMUL complements LEM’s flexible clip-around coil ART and ARU range. The design is based on digital processing to give combined dynamic range, accuracy and versatility of use. It offers a wide range of output signals both RMS and instantaneous. AI-PMUL is DIN rail mounted and can be stacked for multiphase application without spacing thanks to its low power dissipation.
Input signal
Accuracy Class 1 (IEC 61869-2) [1].
Linearity error ≤ 0.10 %. Protection degree IP2X.
35 mm DIN rail mounted.
Push-in terminals.
4 selectable true RMS output signals: 0…20 mA, 4…20 mA, 0…5 V, 0…10 V.
2 selectable instantaneous output signals: 225 mV, 333 mV.
6 selectable sensitivities depending on Rogowski coil: 22.5, 70, 80, 85, 100, 120 mV/kA at 50 Hz.
12 selectable ranges: 100, 200, 300, 400, 500, 600, 800, 1000, 1500, 2000, 4000, 5000 A.
Ambient operating temperature −25...+70 °C.
Advantages
Compact design for DIN rail assembly
High accuracy Class 1 (IEC 61869-2)
Setup by user via Select / Edit buttons
Clear status indication via bi-color led
Applications
MV/LV substations on LV side: Transformer Condition Monitoring
Power metering: current measurement for active power calculation
Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation
Power quality monitoring: electrical loads and distribution system equipment
Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault
Remote Terminal Units (RTU)
Phasor Measurement Units (PMU)
Standards
IEC 61010-1: 2010
UL
EMC: IEC 61326-1:2012
Options
Cross Power Plug-in: side contacts to stack up to 3 Integrator modules and use only one power supply.
Specification
LEM Part Number
ART-B22-D300-SP4 + AI-PMUL
Function
Single Phase AC Current Measurement
Measuring Range
Selectable 5000,4000,2000,1500,1000,800,600,500,400,300,200,100Amp
Sensitivity
Selectable 22.5,70,80,85,100,120mV/kA @ 50 Hz
Output
Selectable; Signal Conditioned True RMS 0-20mA, True RMS 4-20mA, True RMS 5V, True RMS 10V or 225mV, 333mV Direct Output (1 Amp output coming soon)
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
10-32VDC
Accuracy
1% from 25 to 5000 Amp
Current Consumption
100mA (max)
Dimensions
100mm x 78mm x 15mm (Integrator), 30cm Diameter (Coils)
Mounting
Din Rail Mount
Integrator to Coil cable
4.5M Twisted and Screened
Integrator to Meter cable
User Supplied Shielded cable 1.5mm sqr, up to 6m long
Operating Temperature
-25°C - 70°C
Storage Temperature
-45°C to 80°C
Isolation (50Hz, 1 min)
1.5kV
True RMS Response Time
160-190ms
Termination Style
Push-in for 1.5mm sqr wire
Weight
58g
Factory Pack Qty
1
Certifications
UL, ROHS
Datasheet
AI-PMUL Datasheet
ART Series Datasheet
Application Notes
User Notice
1) The Rogowski coil can measure any primary current as there is no saturation effect.
2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts)
3) Frequency bandwidth and phase shift modelling schematic can be provided on request.
4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5) Considering a primary conductor of at least ⌀ 15 mm, perpendicular and in contact with the Rogowski coil.
6) Considering an external conductor of at least ⌀ 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.
Fastron Electronics AMB-A-A9-A-N, 96x48mm AC Current Panel Meter, Ammeter, 0-10 Amp AC Input, 100-240VAC/DC supply
Adjustable Zero and Span Setting
Adjustable Display Scaling
Large 4.1 Digit 20.3mm (8 Inch) LED Display
250mS Response Time
PC 94 UL V0
Each unit needs just 96 x 48mm Panel Space
90mm Depth
CE Approved
Specification
Fastron Electronics Part Number
AMB-A-A9-A-N
Conditioner Output
N/A
Input
0-10 Amp AC
Over Range
x 1.5
Operating Temperature
0 - 60°C
SupplyVoltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Display Type
4.1 Digit RED LED
Mounting Style
96 x 48mm Panel Mount
Case Material
PC - UL 94 V0
Weight
320g
Factory Pack Qty
1
Product Datasheet
Application Notes
Panel Meters Blog Articles
MS Power MSD26N16M1B, Rectifier Diode 26 Amp, 1600V, M6, Cathode stud
Features
Full blocking capability over wide temperature range
Hermetic metal case with glass insulator
Threaded stud
Applications
Power Supplies
Uncontrolled Rectifiers
Oil Cooled Circuits
Battery Chargers
Specification
MS Power Part Number
MSD26N16M1B
Vrrm
1600V
Diode Configuration
Cathode Stud
IF(av) @ 100 Deg C
39 Amp
IF(av) @ 125 Deg C
25 Amp
Itsm
375 Amp
VF(to)
0.85V
Tj(max)
180°C
rF
10mΩ
Termination Style (No Tail)
2.2mm Solder Tab
Termination Style (Stud)
M5 x 1
Tail Length to Stud
N/A
R th(j-c)
1.5°C/W
R th(c-h)
0.25°C/W
Weight
5.5g
Mounting Torque
2 Nm
Factory Pack Qty
50
Stud Size
M5
Country Of Origin
China
MS Power Headquarters
Germany
Datasheet
Product Datasheet
MS Power MSD26R16M1B, Rectifier Diode 26 Amp, 1600V, M5 x 1, Anode stud
Features
Full blocking capability over wide temperature range
Hermetic metal case with glass insulator
Threaded stud
Applications
Power Supplies
Uncontrolled Rectifiers
Oil Cooled Circuits
Battery Chargers
Specification
MS Power Part Number
MSD26R16M1B
Vrrm
1600V
Diode Configuration
Anode Stud
IF(av) @ 100 Deg C
39 Amp
IF(av) @ 125 Deg C
25 Amp
Itsm
375 Amp
VF(to)
0.85V
Tj(max)
180°C
rF
10mΩ
Termination Style (No Tail)
2.2mm Solder Tab
Termination Style (Stud)
M5 x 1
Tail Length to Stud
N/A
R th(j-c)
1.5°C/W
R th(c-h)
0.25°C/W
Weight
5.5g
Mounting Torque
2 Nm
Factory Pack Qty
50
Stud Size
M5
Country Of Origin
China
MS Power Headquarters
Germany
Datasheet
Product Datasheet
Fastron Electronics GT-T/TO(0-150)/D1, Signal Isolator/Conditioner, DIN Rail Mount, PT100 RTD (0-150 Deg C) Input, 4-20mA output, 22-60VAC/DC supply
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
GT-T/TO(0-150)/D1(0-20mA)
Control Output
4-20mA
Input
RTD (Pt100)
Over Range
N/A
Operating Temperature
0 - 60°C
Load Voltage
22-60VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Iskra Doo KNL18-10-415VAC Contactor
Capacitor duty contactors are designed to meet the requirements of capacitor duty applications. Contactors are fitted with a block of three auxiliary contacts connected in series with six quick discharge damping resistors, two per each phase. Peak current is limited to the value within the contactor making capacity.
Features :
High contact reliability at low voltages
High electrical and mechanical endurance and high switching capacity
Four and Three-pole contactors
Optional auxiliary contacts
Ratings from 6 Amp to 1000 Amp
UL, CSA Approved
Advantages :
Saves costs of expensive replacement
Long electrical life
Reduces watt losses during “ON” condition, saves energy
High safety
No risk of dangerous voltage
Less maintenance and downtime
Standard control voltages: 24 V 50/60 Hz, 240 V 50/60 Hz, 415 V 50/60 Hz
Specification
Iskra Doo Part Number
KNL18-10-415VAC
Functions
4 Pole Contactor
Nominal Voltage
230/400/500/690VAC @ 50/60Hz
Current Carrying Capacity as per UL
18 Amp Continuous @ 55 Deg C
Overload Capability
144(10s), 170(5s), 200(1s), 500(0.001s)
Auxiliary Contacts
4 x NO
Trip Delay Time
2-10ms
Electrical Life
200,000 Ops
Operating Temperature
-25 to 40 Deg C
Mechanical Operations
10.000,000 Ops
Control Voltage
415VAC
Power Dissipation
0.36W
Approvals
UL, CSA
Standards
IEC/EN 60947-4-1, AS/NZ 61009-1
Weight
200g
Enclosure Material
UL94
Factory Pack Qty
1
Datasheet
Product Datasheet
Contactor Catalogue
Iskra Contactor Catalogue
Fastron TTH-33-SA1-3, Temperature and Humidity Sensor and Transmitter, 150 x 6mm w/3M Cable
2 x 4-20mA Output 2 Wire
Humidity Measurement for RH 0 to 100 %
Long Term Stability <2% RH per year
Temp Measurement for 0 to 100 Deg C Max
150 x 6mm with 3M Cable
20 Second Response Time
12-30VDC Supply 150mA max
Thin Film Capacitor and Pt100 Temp Sensing Elements
Suitable replacement for Mecatherm T211-XH-954
Specification
Fastron Part Number
TTH-33-SA1-3
Sensor Type
RTD (Temperature) & Thin Film Capacitor (Humidity)
No of Wires
2
Shaft Length
150mm
Shaft Thickness
6mm
Approvals
CE, ROHS
Cable length
1 Meter
Temperature Range
0 to 100 Deg C
Mounting Style
Through Hole
Weight
45g
Factory Pack Qty
1
Datasheet
Datasheet
Installation Guide
Wiring Diagram
Fastron TTH-33-SA2-3, Temperature and Humidity Sensor and Transmitter, 300 x 6mm w/3M Cable
2 x 4-20mA Output 2 Wire
Humidity Measurement for RH 0 to 100 %
Long Term Stability <2% RH per year
Temp Measurement for 0 to 100 Deg C Max
300 x 6mm with 3M Cable
20 Second Response Time
12-30VDC Supply 150mA max
Thin Film Capacitor and Pt100 Temp Sensing Elements
Suitable replacement for Mecatherm T211-XH-954
Specification
Fastron Part Number
TTH-33-SA2-3
Sensor Type
RTD (Temperature) & Thin Film Capacitor (Humidity)
No of Wires
2
Shaft Length
300mm
Shaft Thickness
6mm
Approvals
CE, ROHS
Cable length
1 Meter
Temperature Range
0 to 100 Deg C
Mounting Style
Through Hole
Weight
45g
Factory Pack Qty
1
Datasheet
Datasheet
Installation Guide
Wiring Diagram
Fastron TTH-33-SA3-3, Temperature and Humidity Sensor and Transmitter,500 x 6mm w/3M Cable
2 x 4-20mA Output 2 Wire
Humidity Measurement for RH 0 to 100 %
Long Term Stability <2% RH per year
Temp Measurement for 0 to 100 Deg C Max
500 x 6mm with 3M Cable
20 Second Response Time
12-30VDC Supply 150mA max
Thin Film Capacitor and Pt100 Temp Sensing Elements
Suitable replacement for Mecatherm T211-XH-954
Specification
Fastron Part Number
TTH-33-SA3-3
Sensor Type
RTD (Temperature) & Thin Film Capacitor (Humidity)
No of Wires
2
Shaft Length
500mm
Shaft Thickness
6mm
Approvals
CE, ROHS
Cable length
1 Meter
Temperature Range
0 to 100 Deg C
Mounting Style
Through Hole
Weight
45g
Factory Pack Qty
1
Datasheet
Datasheet
Installation Guide
Wiring Diagram
Fastron TTH-32-SA3-3, Relative Humidity Sensor and Transmitter, 500 x 6mm w/3M Cable
1 x 4-20mA Output 2 Wire
Humidity Measurement for RH 0 to 100 %
Long Term Stability <2% RH per year
300 x 6mm with 3M Cable
20 Second Response Time
12-30VDC Supply 150mA max
Thin Film Capacitor Sensing Elements
Specification
Fastron Part Number
TTH-32-SA3-3
Sensor Type
Thin Film Capacitor (Humidity)
No of Wires
2
Shaft Length
500mm
Shaft Thickness
6mm
Approvals
CE, ROHS
Cable length
1 Meter
Temperature Range
0 to 100 Deg C
Mounting Style
Through Hole
Weight
45g
Factory Pack Qty
1
Datasheet
Datasheet
Installation Guide
Wiring Diagram
Eastron SDM630MCT-4L, Quad 3 Phase DIN Rail Mount kWh Meter with Easyclick, 4 x 3 Phase or 12 x Single Phase, 240VAC aux, Class 1, 100mA RJ12 CT Connect, w/RS485 Modbus RTU Comms
100mA RJ12 CT 4 x 3 Phase Connect
100mA RJ12 12 x Single Phase RJ12 CT with adapter
RS 485 communication up to 38,400 bit/s as standard
True RMS values of currents and voltages
Easyclick CT system reduces installation costs
Dual Metering System Reduces Cost and saves space
The meter is intended for measuring, and monitoring 2 x three phase or 6 x single-phase or electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals.
Features :
System Accuracy Class B/Class1
Measurement of Active and Reactive Power
Modbus RTU communication up to 38,400 bit/s communication
Graphic LCD with illumination
Specification
Eastron Part Number
SDM630MCT-4L
Functions
Quad Three Phase Energy Meter/ 12 x Single Phase Energy Meter
Supply Voltage
230V L-N +/-15% < 5VA
Nominal Measurement Range
415V L-L 230V L-N, 1/5 Amp +/-15%
Maximum Measurement Range
480V L-L 230V L-N, 1/5 Amp
Nominal CT Current Input
100mA via RJ12 Easyclick CT's
Pulse Output
N/A
Tariff Input
N/A
System Accuracy
Class 1 (I,U,F,kW,kWh) Class 2 (Reactive)
Mounting
Din Rail
Real Time Clock
1min/month (30ppm)
Internal Memory
N/A
Dimensions
72mm x 100mm x 66mm (4 modules wide)
Isolation
4kV
RS485
2400-38400 b/s (400ms Response Time)
Weight
700g
Certification
EN 61010-1 Installation Category III
Factory Pack Qty
1
Safety
IP51(Indoor)
Enclosure Material
Noryl with fire protection to UL94-V-O. Self extinguishing
Enclosure Size
DIN 42880 4 Modules
Operating Temperature
-20 →+70 °C
Documents
Product Datasheet
User Manual
Modbus Protocol
Suitable RJ12 CT's
Three Phase J12 Connected CT's
Split Core Single Phase CT's for RJ12 Connected Meters
Modbus Utility
EEM Meter Setting Software Utility