Rishabh Rish Con V(500V)-50-H-O1A2-O2A2-Z-Z-Z, AC Voltage Transducer, 50Hz 65-500VAC Full Scale, Dual 0-20mA Output, 60-300VAC/DC Supply, without Display
Dual 0-20mA Output
250mS response time
PC 94 UL V0
Each unit needs just 43.75 x 100.9 mm depth DIN Rail cabinet space
Specification
Rishabh Part Number
Rish Con V(500V)-50-H-O1A2-O2A2-Z-Z-Z
Measurement Output
Dual 0-20mA
Input
65 - 500VAC 50/60Hz
Overlaod (Continuous)
120%
Overload (1 second)
150%
Operating Temperature
-40 - 70°C
Supply Voltage
60 - 300VAC/DC
Accuracy
0.2%
Response Time
250mS
Termination Style
Screw
Mounting Style
DIN Rail Mount
Safety
IP40/IP20 EN60529 Protection Class II EN61010
Weight
400g
Factory Pack Qty
1
Datasheet
Product Datasheet
Technical Support
Rish Con P setup procedure blog
Fastron FES521-FD-420T, Solid Core AC Current Transducer, Multirange 0-10A,20A, 50A, Self Powered, Average RMS 4-20mA Output. 1% Accuracy (FCS521-SD-420E)
Compact and versatile current switches for detection of AC Currents, Multirange 0-10Amp, 0-20Amp, 0-50Amp via jumper, 4-20mA True RMS output
Features
True RMS 4-20mA output
Multirange selector
Panel mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Highly accurate low current measurement down to 1Amp
High isolation between primary and secondary circuits
Easy installation
Applications
Fault Detection
Motor or Fan Protection
Application Domain
Energy and Automation
Specification
Fastron Part Number
FES521-FD-420T
Technology
Solid Core Solid Core AC Current Transducer
Range
0-10Amp, 0-20Amp, 0-50Amp via jumper
Supply Voltage
Self Powered
Load Current (RMS)
1Amp to 50 Amp
Output
4-20mA True RMS
Isolation
2kV (AC, 50Hz, 1 min)
Bandwidth
50/60Hz
Mounting Style
Panel Mount
Operating Temperature Range
-25°C / 70°C
Accuracy
1%
Termination Style
Screw Terminals
Unit Weight
200g
Certifications
UL E320368, CE, Rohs compliant
Datasheet
Product Datasheet
Installation Guide
Fastron FES2151-FP-420E, Split Core AC Current Transducer, Multirange 0-100A,150A, 200A, Self Powered, Average RMS 4-20mA Output. 1% Accuracy FCS2151-SP-420E
Compact and versatile current switches for detection of AC Currents, Multirange 0-10Amp, 0-20Amp, 0-50Amp via jumper, 4-20mA True RMS output
Features
Average RMS 4-20mA output
Multirange selector
Panel mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Highly accurate low current measurement down to 1Amp
High isolation between primary and secondary circuits
Easy installation
Applications
Fault Detection
Motor or Fan Protection
Application Domain
Energy and Automation
Specification
Fastron Part Number
FES2151-FD-420E
Technology
Solid Core Split Core AC Current Transducer
Range
0-100Amp, 0-150Amp, 0-200Amp via jumper
Supply Voltage
Self Powered
Load Current (RMS)
1Amp to 200 Amp
Output
4-20mA Average RMS
Isolation
2kV (AC, 50Hz, 1 min)
Bandwidth
50/60Hz
Mounting Style
Panel Mount
Operating Temperature Range
-25°C / 70°C
Accuracy
1%
Termination Style
Screw Terminals
Unit Weight
200g
Certifications
UL E320368, CE, Rohs compliant
Datasheet
Product Datasheet
Installation Guide
Fastron FES521-FP-V10, Split Core AC Current Transducer, Multirange 10A, 20A, 50A, Average RMS 0-10V Output. 1% Accuracy (FCS521-FP-V10)
Compact and versatile current switches for detection of AC Currents, Multirange 0-10Amp, 0-20Amp, 0-50Amp via jumper, 0-10V True RMS output
Features
True RMS 0-10V output
Multirange selector
Panel mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Highly accurate low current measurement down to 1Amp
High isolation between primary and secondary circuits
Easy installation
Applications
Fault Detection
Motor or Fan Protection
Application Domain
Energy and Automation
Specification
Fastron Part Number
FES521-FP-V10
Technology
Split Core AC Current Transducer
Range
Selectable 0-10Amp, 0-20Amp, 0-50Amp via jumper
Supply Voltage
Self Powered
Load Current (RMS)
1Amp to 50 Amp
Output
0-10V Average RMS
Isolation
2kV (AC, 50Hz, 1 min)
Bandwidth
50/60Hz
Mounting Style
Panel Mount
Operating Temperature Range
-25°C / 70°C
Accuracy
1%
Termination Style
Screw Terminals
Unit Weight
200g
Certifications
UL E320368, CE, Rohs compliant
Datasheet
Product Datasheet
Installation Guide
Fastron Electronics GTD-DA6-A-11, Signal Conditioner/Voltage Transducer, 4-20mA input, 100-240VAC/DC aux, Dual 4-20mA outputs
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
GTD-DA6-A-11
Conditioned Output
2 x 4-20mA
Input
4-20mA
Over Range
x 1.5
Operating Temperature
0 - 60°C
Load Voltage
100-240VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Datasheet
Product Datasheet
Fastron FES2151-FP-V5, Split Core AC Current Transducer, Multirange 100A, 150A, 200A, Average RMS 0-5V Output. 1% Accuracy (FCS2151-FP-V5)
Compact and versatile current switches for detection of AC Currents, Multirange 0-100Amp, 0-150Amp, 0-200Amp via jumper, 0-5V True RMS output
Features
True RMS 0-10V output
Multirange selector
Panel mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Highly accurate low current measurement down to 1Amp
High isolation between primary and secondary circuits
Easy installation
Applications
Fault Detection
Motor or Fan Protection
Application Domain
Energy and Automation
Specification
Fastron Part Number
FES2151-FP-V5
Technology
Split Core AC Current Transducer
Range
Selectable 0-100Amp, 0-150Amp, 0-200Amp via jumper
Supply Voltage
Self Powered
Load Current (RMS)
1Amp to 50 Amp
Output
0-5V Average RMS
Isolation
2kV (AC, 50Hz, 1 min)
Bandwidth
50/60Hz
Mounting Style
Panel Mount
Operating Temperature Range
-25°C / 70°C
Accuracy
1%
Termination Style
Screw Terminals
Unit Weight
200g
Certifications
UL E320368, CE, Rohs compliant
Datasheet
Product Datasheet
Installation Guide
Magnelab HCT-0010-020, Split Core DC Hall Effect Current Sensor, 20 Amp, +/-4V Output, Split Core 10mm Aperture, X = 1%
Features
Open loop transducer using Hall effect
Compact and versatile
Panel mounting-Horizontal or Vertical
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
Very good accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Current overload capability
Low power consumption
Applications
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications.
Specification
Magnelab Part Number
HCT-0010-020
Technology
Split Core Open Loop Hall Effect
Aperture
ø10mm
ROHS
Yes
Supply Voltage
+/-15 VDC Bipolar, Isolated
Load Current (RMS + DC)
20 Amp
Measurement Range
+/-30 Amp
Output
+/-4 V
Isolation
4 kV
Bandwidth
DC
Mounting Style
Panel Mount
Operating Temperature Range
-25°C / 75°C
Accuracy
1%
Termination Style
Flying Lead
Unit Weight
80g
Factory Pack Quantity
10
Datasheet
Product Datasheet
Magnelab HCT-0010-005, Split Core DC Hall Effect Current Sensor, 5 Amp, +/-4V Output, Split Core 10mm Aperture, X = 1%
Features
Open loop transducer using Hall effect
Compact and versatile
Panel mounting-Horizontal or Vertical
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
Very good accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Current overload capability
Low power consumption
Applications
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications.
Specification
Magnelab Part Number
HCT-0010-010
Technology
Split Core Open Loop Hall Effect
Aperture
ø10mm
ROHS
Yes
Supply Voltage
+/-15 VDC Bipolar, Isolated
Load Current (RMS + DC)
5 Amp
Measurement Range
+/-7.5 Amp
Output
+/-4 V
Isolation
4 kV
Bandwidth
DC
Mounting Style
Panel Mount
Operating Temperature Range
-25°C / 75°C
Accuracy
1%
Termination Style
Flying Lead
Unit Weight
80g
Factory Pack Quantity
10
Datasheet
Product Datasheet
LEM DVM 4000-UI, Digital Voltage Transducer, Vpn = 4000V, 24VDC Supply, 4-20mA Analogue Output, 12kV Isolation
Features
Bandwidth DC to 13kHz
4-20mA Unipolar Analogue Output
Closed loop transducer using Hall effect
Digital Transducer
Compact and versatile
Panel Mount
Insulated plastic case recognized according to UL 94-V0
Advantages
Very good linearity
High accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external interference
Voltage overload capability
Low power consumption
Applications
Railway substation or locomotive
AC variable speed drives and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications
Water Treatment Electronics
Specification
LEM Part Number
DVM 4000-UI
Technology
Closed Loop Hall Effect
Aperture
No Aperture
ROHS
Yes
Supply Voltage
24 VDC, Isolated
Primary Nominal Voltage (RMS + DC)
+/- 4000V
Measurement Range
+/- 6000V
Output
4 mA at 0V, to 20mA @Vpn
Isolation
12 kV
Bandwidth
DC-13 kHz
Mounting Style
Panel Mount
Operating Temperature Range
-40°C / 85°C
Accuracy
1%
Termination Style
M5 Screw
Unit Weight
375g
Factory Pack Quantity
4
Datasheet
Product Datasheet
Application Notes
LEM Applications Manual 3rd Edition
Trent F170M1316 Series 690V Semiconductor I^2t (aR) Fuse Square Body DIN 43 653 Style, 80 Amp, 690VAC, Panel Mount 200kA, Size 000 (78mm Hole Centers)
Features
Square Body DIN 43 653
Ratings up to 400 Amp
Busbar or Standoff Mounting
IEC Standard 60269.1 AND 4
690 V Voltage Rating complying with IEC 33
Applications
Protection of High Powered Semiconductors according to I??t
Short Circuit Protection
DC or AC Motor Protection
Battery Fuse
Specification
Trent Part Number
F170M1316
Fuse Type
I^2t AR Class
Nominal Voltage
690VAC @ 50Hz
I??t Rating (660V)
2550 A^2/s
Nominal Current (RMS DC)
80 Amp
Tested Breaking Capacity
200kA @ 690VAC
Dimensions
40 x 100 x 20mm (Size 000)
Hole Centers
78mm
Mounting Style
Busbar or Panel Mount with Standoff
Operating Temperature Range
-40??C / 125??C
Watt Loss
24W
Termination Style
M8
Unit Weight
134g
Factory Pack Qty
10
Datasheet
Product Datasheet
Trent F170M1314 Series 690V Semiconductor I^2t (aR) Fuse Square Body DIN 43 653 Style, 50 Amp, 690VAC, Panel Mount 200kA, Size 000 (78mm Hole Centers)
Features
Square Body DIN 43 653
Wide Range of I^2t
Ratings up to 400 Amp
Busbar or Standoff Mounting
IEC Standard 60269.1 AND 4
690 V Voltage Rating complying with IEC 33
Applications
Protection of High Powered Semiconductors according to I??t
Short Circuit Protection
DC or AC Motor Protection
Battery Fuse
Specification
Trent Part Number
F170M1315
Fuse Type
I^2t AR Class
Nominal Voltage
690VAC @ 50Hz
I??t Rating (660V)
770 A^2/s
Nominal Current (RMS DC)
50 Amp
Tested Breaking Capacity
200kA @ 690VAC
Dimensions
40 x 100 x 20mm (Size 000)
Hole Centers
78mm
Mounting Style
Busbar or Panel Mount with Standoff
Operating Temperature Range
-40DegC / 125DegC
Watt Loss
24W
Termination Style
M8
Unit Weight
134g
Factory Pack Qty
10
Datasheet
Product Datasheet