RCS-1200-1000 0.333V, 3 Phase 1000Amp AC Measurement 4 Inch ⌀ Rogowski Coils with Integrator, Class 1 Flexible Current Sensor System:
The RCS-1200 three-phase flexible rope CT from Magnelab converts AC input current of up to 5000 amperes to an AC output of 0.333 volt.
A 9 to 36 VDC power supply is required to operate these coils. The RCS-1200 comes with an integrator which includes flexible strain relief cables.
Included is an 12 inch circumference rope CT with Integrator, and 8 feet of twisted pair (600V) output leads.
Magnelab Coils come with 10 year warranty
Suitable Alternative to Solar Edge CTRC-07500-1000
Â
Specification
Magnelab Part Number
RCS-1200-1000
Function
AC Current Measurement
Nominal Measurement Current
1000 Amp RMS
Measurement Range
10% - 130% if Ipn
Frequency Measuring Range
50-1500Hz (15th Harmonic)
Operating Voltage
9 - 36VDC
Accuracy
1% from 25 to 1000 Amp
Phase Angle
< 0.5 Degrees
Coil Diameter (⌀)
4 Inch
Coil Circumference
12 Inch
Integrator to Coil Cable
8 Feet Shielded
Maximum Voltage
600V (on bare conductor)
Operating Temperature
-15°C to 65°C
Storage Temperature
-45°C to 80°C
Power Consumption
< 2VA
Overload
20,000 Amp (continuous)
Termination Style
Screw
Weight
1200g
Certification
CE
Factory Pack Qty
1
Certifications
UL Recognized E96927 to IEEE C57.13, CAN/CSA 60044-1
Meets UL STD 61010-1, CAN/CSA C22.2 No. 61010
CE
ROHS
Datasheet
Product Datasheet
Application Notes
RCS/RCT Series Installation Guide
TCD-S-1-K HEATING Temp Controller, 48x48mm, 230VAC, C/O Relay output, Type K Input. Encoder Control,amp; Digital Display, 0-999 Deg C
Pushbutton Encoder Setpoint
3-digit display (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated ON/OFF Relay, output, Optional cooling or time proprtional versions output available
Each unit needs just 75 mm depth panel space
Specification
Fastron Part Number
TCD-S-1-K
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Input
Type K Thermocouple
Control Mode
Heating ON/OFF Control
Control Range
0- 999 Deg C
Mounting Style
48x48mm Panel Mount
Supply Voltage
230VAC
Termination Style
Screw
Sampling Time
50ms
Weight
270g
Factory Pack Qty
1
Â
Datasheet
TCD/TCR/FC5 Datasheet
TCD/TCR User Manual
Fastron Electronics SCT-F24-300, 300 Amp, 0.333v Class 1 Series Current Transformer
Features
Quick Release Split Core System
Cable Mount
0.333v Output
Self Powered
Rated System Voltage 0.60/3kV
0.9M Flying Leads
Applications
US Based Metering Equipment
Energy Monitoring
AC Power Control Systems
Power Factor Correction
Power Quality Measurements
Specification
Fastron Part Number
SCT-F24-300
Technology
Split Core AC Current Transformer
Ratio
300/0.333v
Aperture Size
ø 24 mm
VA Rating
N/A
Accuracy Class
Class 1
Output
0.333v (+20%)
Isolation
3kV (AC, 50Hz, 1 min)
Bandwidth
50-60Hz
Mounting Style
Cable Mount/Busbar Mount
Operating Temperature Range
-15°C / 45°C
Continuous Current (max)
300Amp x 1.2
Termination Style
0.9M Flying leads
Unit Weight
100g
Factory Pack Qty
9
Datasheet
Product Datasheet
Application Notes
Installation Guide
Fastron Electronics GTD-TT1-D-11, DC Voltage Transducer, - 50 to 50 Deg C input, 22-60VAC/DC aux, Dual 4-20mA Outputs
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
GTD-TT1-D-11
Conditioned Output
2 x 4-20mA (Average RMS)
Input
- 50 Deg C to 50 Deg C
Over Range
x 1.5
Operating Temperature
0 - 60°C
Load Voltage
22-60VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Fastron TTH-32-DB-1, Relative Humidity Sensor and Transmitter, 190 x 18-19mm w/1m Cable, Can replace GEFRAN TRANSMICOR T211
1 x 4-20mA Output 2 Wire
Humidity Measurement for RH 0 to 100 %
Long Term Stability <2% RH per year
190 x 18mm with 1M Cable
20 Second Response Time
12-30VDC Supply 150mA max
Thin Film Capacitor Sensing Elements
Specification
Fastron Part Number
TTH-32-DB-1
Sensor Type
Thin Film Capacitor (Humidity)
No of Wires
2
Shaft Length
190mm
Shaft Thickness
18-19mm
Approvals
CE, ROHS
Cable length
1 Meter
Temperature Range
0 to 100 Deg C
Mounting Style
Through Hole
Weight
45g
Factory Pack Qty
1
Datasheet
Datasheet
Installation Guide
Wiring Diagram
Fastron TTH-31-SA1-1, Air Temperature Sensor and Transmitter 6 x 150mm w/1M Cable
4-20mA Output 2 Wire
Temp Measurement for 0 to 100 Deg C Max
150 x 6mm with 1M Cable
20 Second Response Time
12-30VDC Supply 150mA max
Pt100 Temp Sensing Elements
Specification
Fastron Part Number
TTH-31-SA1-1
Sensor Type
RTD (Temperature)
No of Wires
2
Shaft Length
150mm
Shaft Thickness
6mm
Approvals
CE, ROHS
Cable length
1 Meter
Temperature Range
0 to 100 Deg C
Mounting Style
Through Hole
Weight
45g
Factory Pack Qty
1
Datasheet
Datasheet
Installation Guide
Wiring Diagram
Premium Quality TC Cable 500M Teflon - Type R Thermocouple Cable 500 Meter Twisted and Screened 7/0.2mm, ANSI Standard
Features
CE, ANSI, ROHS Approved
Colour Codes
Datasheet
Thermocouple Cable Brochure
TCD-L-2-K COOLING Temp Controller, 96x96mm 230VAC, C/O Relay output, Type K Input. Encoder Control,amp; Digital Display, 0-999 Deg C
Pushbutton Encoder Setpoint
3-digit display (0.5s response)
Drip-proof / Dust-proof IP66 (front panel only)
Input signals can be converted to insulated ON/OFF Relay, output, Optional cooling or time proprtional versions output available
Each unit needs just 75 mm depth panel space
Specification
Fastron Part Number
TCD-L-2-K
Control Output
Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4)
Input
Type K Thermocouple
Control Mode
Cooling ON/OFF Control
Control Range
0- 999 Deg C
Mounting Style
96x96mm Panel Mount
Supply Voltage
230VAC
Termination Style
Screw
Sampling Time
50ms
Weight
270g
Factory Pack Qty
1
Â
Datasheet
TCD/TCR/FC5 Datasheet
TCD/TCR User Manual
Fastron Electronics GT-T/TO(0-150)/D1, Signal Isolator/Conditioner, DIN Rail Mount, PT100 RTD (0-150 Deg C) Input, 4-20mA output, 22-60VAC/DC supply
Adjustable Zero and Span Setting
250mS Response Time
PC 94 UL V0
Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type)
Each unit needs just 22.5 x 114 mm depth DIN Rail cabinet space
Specification
Fastron Electronics Part Number
GT-T/TO(0-150)/D1(0-20mA)
Control Output
4-20mA
Input
RTD (Pt100)
Over Range
N/A
Operating Temperature
0 - 60°C
Load Voltage
22-60VAC/DC
Span Adjustment Range
+/-10%
Zero Adjustment Range
+/-5%
Termination Style
Screw
Mounting Style
DIN Rail Mount
Case Material
PC - UL 94 V0
Weight
170g
Factory Pack Qty
1
Â
Datasheet
Product Datasheet
Fastron TTH-31-SA2-3, Air Temperature Sensor and Transmitter 6 x 300mm w/3M Cable
4-20mA Output 2 Wire
Temp Measurement for 0 to 100 Deg C Max
300 x 6mm with 3M Cable
20 Second Response Time
12-30VDC Supply 150mA max
Pt100 Temp Sensing Elements
Specification
Fastron Part Number
TTH-31-SA2-3
Sensor Type
RTD (Temperature)
No of Wires
2
Shaft Length
300mm
Shaft Thickness
6mm
Approvals
CE, ROHS
Cable length
1 Meter
Temperature Range
0 to 100 Deg C
Mounting Style
Through Hole
Weight
45g
Factory Pack Qty
1
Datasheet
Datasheet