Secure Meters DPM48V200-2, 48mm x 96mm Digital Voltmeter, 0-250VDC Input, 0.5% Accuracy, 40 to 300VAC/DC Supply, IP54 (Optional IP65)
Features
LED Display
250mS Response Time
PC 94 UL V0
Each unit needs just 96 x 48mm Panel Space
52mm Depth
CE Approved
ROHS and REACH
Specification
Secure Part Number
DPM48V200-2
Frequency Range
45-65 Hz
Accuracy
0.5%
Input
0-250VDC
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
40-300VAC/DC
Termination Style
Screw
Mounting Style
96 x 48mm Panel Mount
Case Material
PC - UL 94 V0
Standards
IEC / EN 61010-1; IEC / EN 61010-2-030
Protection Degree
IP54 (IP65 Optional)
Weight
280g
Factory Pack Qty
1
Datasheet
Product Datasheet
Manual
DPM Series User Manual
Application Notes
Panel Meters Blog Articles
Secure Meters DPM96V360-2, 96mm x 96mm LCD Digital Voltmeter, 3 Phase 0-500VAC Input, 0.5% Accuracy, 40 to 300VAC/DC Supply, IP54 (Optional IP65)
Features
LCD Dual Display
250mS Response Time
PC 94 UL V0
Each unit needs just 96 x 96mm Panel Space
52mm Depth
CE Approved
ROHS and REACH
Specification
Secure Part Number
DPM96V360-2
Frequency Range
45-65 Hz
Accuracy
0.5%
Input
100-500VAC
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
40-300VAC/DC
Termination Style
Screw
Mounting Style
96 x 96mm Panel Mount
Case Material
PC - UL 94 V0
Standards
IP54 (IP65 Optional)
Protection Degree
IEC / EN 61010-1; IEC / EN 61010-2-0301
Weight
450g
Factory Pack Qty
1
Datasheet
Product Datasheet
Manual
DPM Series User Manual
Application Notes
Panel Meters Blog Articles
Secure Meters DPM96I360-2, 96mm x 96mm LCD Digital AC Ammeter, 3 Phase 0-6 Amp CT Inputs, 0.5% Accuracy, 40 to 300VAC/DC Supply, IP54 (Optional IP65)
Features
LCD Dual Display
250mS Response Time
PC 94 UL V0
Each unit needs just 96 x 96mm Panel Space
52mm Depth
CE Approved
ROHS and REACH
Specification
Secure Part Number
DPM96I360-2
Frequency Range
45-65 Hz
Accuracy
0.5%
Input
0-6 Amp 3 Phase CT inputs
Over Range
x 1.5
Operating Temperature
0 - 60°C
Supply Voltage
40-300VAC/DC
Termination Style
Screw
Mounting Style
96 x 96mm Panel Mount
Case Material
PC - UL 94 V0
Standards
IEC / EN 61010-1; IEC / EN 61010-2-030
Protection Degree
IP54 (IP65 Optional)
Weight
450g
Factory Pack Qty
1
Datasheet
Product Datasheet
Manual
DPM Series User Manual
Application Notes
Panel Meters Blog Articles
SSP-BLUE-4mm (2pcs), Blue 4mm Fully Sheathed Safety/Banana Plugs, 32 Amp, 1000V Rated. For Test Equipment/Leads (Current Clamps)
4mm
Fully Sheathed
Suitable for M1/M2 or other 4mm Current Clamps
32 Amp / 1000V AC (rms) or DC Maximum Rating
Crydom DRA-CN240A24, Slimline Relay & Socket, 15-30VDC Coil, 2 Amp 24-280VAC Load
Features
Output 2Amp @ 250VAC
15-30VDC Control input
DIN Rail Mount
Ultra slim package
CE Compliant to IEC 60664
IP67
Specification
Crydom Part Number
DRA-CN240A24
Switching Type
250VAC 2 Amp Load SSR
Approvals
UL, CE
ROHS
Yes (Details)
Control Voltage
15-30VDC
Load Current
2 Amp (rms)
Special Feature
LED Status Indicator
Mounting Style
Socket Mount (F41F-1Z-C2-5 12-14VAC/DC)
Load Voltage Range
250VAC Load
EMC Compliant
Level 3
Termination Style
PCB or Socket Mount
Unit Weight
6g
Factory Pack Qty
20
Datasheet
Relay Datasheet
F41F-1Z-C2-5 12-14VAC/DC Socket
Crydom DRA-CN024D24, Slimline Relay & Socket, 15-30VDC Coil, 3.5 Amp 24VDC Load
Features
Output 3.5 Amp @ 24VDC
15-30VDC Control input
DIN Rail Mount
Ultra slim package
CE Compliant to IEC 60664
IP67
Specification
Crydom Part Number
DRA-CN024D24
Switching Type
24VDC 3.5 Amp SSR
Approvals
UL, CE
ROHS
Yes (Details)
Control Voltage
15-30VDC
Load Current
3.5 Amp (rms)
Special Feature
LED Status Indicator
Mounting Style
Socket Mount (F41F-1Z-C2-5 12-14VAC/DC)
Load Voltage Range
24VDC Load
EMC Compliant
Level 3
Termination Style
PCB or Socket Mount
Unit Weight
6g
Factory Pack Qty
20
Datasheet
Relay Datasheet
F41F-1Z-C2-5 12-14VAC/DC Socket
Keysolu KS32 24-24Z2, Slimline Relay, 24VDC Coil, 2 Amp 24-280VAC Load
Features
Output 2Amp @ 250VAC
24VDC Control input
DIN Rail Mount
Ultra slim package
CE Compliant to IEC 60664
IP67
Specification
Keysolu Part Number
KS32 24-24Z2
Switching Type
250VAC 2 Amp Load SSR
Approvals
UL, CE
ROHS
Yes (Details)
Control Voltage
24VDC
Load Current
2 Amp (rms)
Special Feature
LED Status Indicator
Mounting Style
Socket Mount (F41F-1Z-C2-5 12-14VAC/DC)
Load Voltage Range
250VAC Load
EMC Compliant
Level 3
Termination Style
PCB or Socket Mount
Unit Weight
6g
Factory Pack Qty
20
Datasheet
Relay Datasheet
F41F-1Z-C2-5 12-14VAC/DC Socket
Keysolu KS32 12-24Z2, Slimline Relay, 12VDC Coil, 2 Amp 24-280VAC Load
Features
Output 2Amp @ 250VAC
12VDC Control input
DIN Rail Mount
Ultra slim package
CE Compliant to IEC 60664
IP67
Specification
Keysolu Part Number
KS32 12-24Z2
Switching Type
250VAC 2 Amp Load SSR
Approvals
UL, CE
ROHS
Yes (Details)
Control Voltage
12VDC
Load Current
2 Amp (rms)
Special Feature
LED Status Indicator
Mounting Style
Socket Mount (F41F-1Z-C2-5 12-14VAC/DC)
Load Voltage Range
250VAC Load
EMC Compliant
Level 3
Termination Style
PCB or Socket Mount
Unit Weight
6g
Factory Pack Qty
20
Datasheet
Relay Datasheet
F41F-1Z-C2-5 12-14VAC/DC Socket
Keysolu KS32 12-24Z2, Slimline Relay, 5VDC Coil, 2 Amp 24-280VAC Load
Features
Output 2Amp @ 250VAC
5VDC Control input
DIN Rail Mount
Ultra slim package
CE Compliant to IEC 60664
IP67
Specification
Keysolu Part Number
KS32 5-24 Z 2
Switching Type
250VAC 2 Amp Load SSR
Approvals
UL, CE
ROHS
Yes (Details)
Control Voltage
5VDC
Load Current
2 Amp (rms)
Special Feature
LED Status Indicator
Mounting Style
Socket Mount (F41F-1Z-C2-5 12-14VAC/DC)
Load Voltage Range
250VAC Load
EMC Compliant
Level 3
Termination Style
PCB or Socket Mount
Unit Weight
6g
Factory Pack Qty
20
Datasheet
Relay Datasheet
F41F-1Z-C2-5 12-14VAC/DC Socket
Crouzet 84873029, 3 Phase Voltage Monitoring Relay With 17.5mm SPDT Contacts, 3 x 208 - 480 V AC MWA, Phase Sequence, Total Failure, Can Replace 84892290, 84873034
RMC2 MWS relays control, on 3-phase networks :
Sequence Detection
Total Phase Failure
Controls its own supply voltage
True RMS measurement
LED status indication
3-phase voltage controllers which monitor :
Non Adjustable
Specification
Crouzet Part Number
84873029 (3 Phase Voltage Monitoring Relay With SPDT Contacts)
Function
Total Phase Failure, Phase Sequence
Nominal Voltage
3 x 208 → 3 x 480 V ∿
Digital Outputs
1 x C/O Relays, 250VAC/DC @ 5 Amp
Min Breaking Current
10mA/5VDC
Timing Range
0.3 → 30s (0, +10%)
Delay on Pickup
500ms
Alarm Delay on Time (max)
200ms
Reset Time
1500ms
Fixed Hysteresis
2% of Un
Maximum Measurement Cycle Time
150ms/True RMS Measurement
Measurement Accuracy
1%
Supply Voltage Range
Same as Measurement 3 x 208 → 3 x 480 V ∿
Termination Style
Screw
Weight
170g
Certification
CE, UL, CSA, GL, ROHS
Factory Pack Qty
1
Over Voltage Category
3 in accordance with IEC/EN 60664-1
Pollution Degree
2 in accordance with IEC/EN 61131-2
Protection rating
IP40 (Front), IP20 (Rear)
Mechanical Resistance
Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to HF Interference
Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
Operating Temperature
-20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Datasheet
Product Datasheet
Fastron 16F-SD-NC-AL, AC Current Switch, Multirange 1-10A, 10-50A, 50-200Amp, Self Powered, 10% Accuracy, 0.5 +/-0.2 Minimum ThreshholdAverage RMS Current Sensing, Normally Open Contacts, 0.3Amp @ 135VAC/DC Adjustable Trip
Compact and versatile current switches for detection of AC Currents, Multirange 1-10Amp, 10-50Amp, 50-200Amp via jumper
Features
Multirange selector
Panel mounting
Eliminates insertion loss
Isolated plastic case recognised according to UL94-V0
Advantages
Highly accurate low current measurement down to 1Amp
High isolation between primary and secondary circuits
Easy installation
Applications
Fault Detection
Motor or Fan Protection
Application Domain
Energy and Automation
Specification
Fastron Part Number
16F-SD-NC-AL
Technology
Solid Core AC Current Transformer
Alarm Type
NC Relay 0.3Amp @ 135VAC/DC
Supply Voltage
Self Powered
Load Current (RMS)
Multirange 1-10A, 10-50A, 50-200Amp
Trip Point
Adjustable
Isolation
2kV (AC, 50Hz, 1 min)
Bandwidth
50/60Hz
Mounting Style
Panel Mount
Operating Temperature Range
-25°C / 70°C
Accuracy
10% (Minimum Threshold 0.5 +/-0.2 Amp)
Termination Style
Screw Terminals
Unit Weight
200g
Certifications
UL E320368, CE, Rohs compliant
Datasheet
Product Datasheet
Iskra Doo SQ0214 L440V RC S1SS Synchroscope (Synchronoscope)
Measurement of phase difference between bus bar and generator
Five instruments in one (SQ 0x14)
Circular display of ∆ phase difference
Magnifield display of phase difference ∆ = ±20
Microprocessor processing
Simple synchronization conditions setting
Output relay for synchronisation (pulse or continuous)
''Dead busbar or generator'' functionality
Power supply from bus bar or generator
Standard 96x96 mm or 144x144 mm din housing
LCD with backlight for voltage, frequency and/or ∆ monitoring (SQ 0x14 only)
High immunity to EMC disturbances
Special functions set with three jumpers inside the instruments Status output
Green led for indication of both voltages
Ship version (Bureau veritas certificate - SQ 02x4)
Specification
Iskra Doo Part Number
SQ0214 L440V RC S1SS
Function
Phase Difference (∆ϕ) Measurement
Nominal Voltage (Un)
440VAC ± 20 % Line to Line (UL-N = 400 VMAX) @ 40-70Hz
Digital Output
Relay 250 V, 1 A, 50 Hz, 250 VA
Status Output
Open-Collector 24 Vdc + 20% @30mA
Switch On Delay Time Range
0,1 ... 1 s +/-10%
Phase Difference Setting Range
2 ... 20 °el ± 3 °el
Voltage Difference Setting Range
1 ... 10 % +/-2.5%
Dead Busbar Noise Rejection Range
10%, 20%, 30% or 40%
Power Consumption
< 4VA
Short Term Overload
2 x Un for 3 seconds
LCD Display Accuracy
Voltage 1.5%, Frequency 0.5%, Phase Difference +/-3 °el
Synchronisation Accuracy
+/- 10%
Termination Style
Screw
Weight
530g
Certification
CE
Factory Pack Qty
1
Enclosure Version
Ship Version
Material of housing
PC/ABS Unflammable, according to UL 94 V-0
Enclosure protection
IP52 for case, IP20 for terminals with protective cover
Safety
According to EN 61 010-1 400 V, installation category III Pollution degree 2
Operating Temperature
-20...55 °C
Datasheet
Product Datasheet
User Manual
Application Notes & Software Downloads
The following parameters can be set via internal jumper see User Manual for more details.
Dead Busbar Generator Function
Over and Under Frequency Synchronising
Adjustable Lenght of a Sync Pulse
The following parameters Can be set via MIPack Comms Module & SQset Setting Software
Relay - 300mS/Continuous/Programmable
Dead Busbar - Active DB/Active DB + DG & % Threshold
MIPack User Manual
Download SQSet Settign Software